Ac ce ssi ng dat a vi a P ROFI BUS
Operating manual for PROFIBUS fieldbus | 2015-07 | V1.7 EN
43
4.3.4 Parameter
The following parameters can be accessed non-cyclically for reading and
writing.
IMPORTANT INFORMATION
Changing a parameter value via the fieldbus includes direct
EEPROM write access.
INFORMATION
The data below is listed sorted in ascending order by "Number*".
PROFIBUS
FKO parameter
Slot Index
Parameter
Number*
Accepted
Name in German
Minimum
Maximum
Unit
1
0
0
1,020
2: Always
Minimum frequency
0
400
Hz
1
1
1
1,021
2: Always
Maximum frequency
5
400
Hz
1
3
3
1,050
2: Always
Deceleration time 1
0.1
1000
s
1
4
4
1,051
2: Always
Run up time 1
0.1
1000
s
1
48
48
1,052
2: Always
Deceleration time 2
0.1
1000
s
1
49
49
1,053
2: Always
Run up time 2
0.1
1000
s
1
50
50
1,054
2: Always
Ramp selection
0
9
1
172
172
1,088
2: Always
Deceleration time 3
0.1
1000
s
1
8
8
1,100
2: Always
Operating mode
0
3
1
5
5
1,130
2: Always
Target value source
0
10
1
7
7
1,131
2: Always
Target value approval
0
16
1
81
81
1,132
2: Always
Start protection
0
8
1
41
41
1,150
2: Always
Rotation direction
0
16
1
53
53
1,180
2: Always
Acknowledge function
0
7