I nstal l ati on
Operating manual for PROFIBUS fieldbus | 2015-07 | V1.7 EN
23
3.1 Configuration of the drive controller for PROFIBUS
In order that the drive controller can be controlled by the fieldbus, the
following basic parameters must be set using the FKOpc tool, MMI or
PROFIBUS master:
Set parameter 1.130 (target value source) to fieldbus "9"
Set parameter 1.131 (target value approval) to fieldbus "6"
3.2 FKO bus address
DANGER
Risk of death due to electrical shock!
Death or serious injury!
De-energise drive controller and secure it against being restarted.
In order that an FKO, equipped with a PROFIBUS communication card, can
be clearly recognised in a PROFIBUS system, it must be assigned an
address. The assignment can take place:
By setting the address via the rotary switches "Switch 1" and "Switch 2"
found on the printed circuit board (PCB).
By setting the parameter 6.060 "Fieldbus address"
(see chapter "Parameter list“ of the operating manual)
Use FKOpc, MMI or PROFIBUS master for parameterisation.