22
Elan 10 2.0 / Elan 16 2.0 / Elan 25 2.1 Revision D
&KDSWHU)DXOWV
Fault
code
Cause
Action appliance
Action installer
E101
Output temperature sensor
fault.
- Fan is switched off.
Take the voltage from the appliance.
Replace temperature sensor.
Put voltage back on appliance; fault
has automatically been reset.
E102
Water temperature sensor fault. - Fan is switched off.
Take the voltage from the appliance.
Replace temperature sensor.
Put voltage back on appliance; fault
has automatically been reset
E104
System fan fault.
- Appliance does nothing.
Take the voltage from the appliance.
Check
cabling.
Replace
fan.
Put voltage back on appliance; fault
has automatically been reset.
E105
Fault relay output X15 no. 5 &
nr.6 or nr.7 & nr.8; relay with
too high power on either of the
two outputs or short-circuit at
one of these two outputs (max.
P$9'&
-
)DQUXQVDWPLQLPXPDLUÀRZUDWH
Check wiring and connection value
connected relay.
E106
Unknown switch position of
optional multiple switch.
-
)DQUXQVDWPLQLPXPDLUÀRZUDWH
Take the voltage from the appliance.
Check correctness of connection
multiple switch; correct installation
modular connector.
E107
External fault input X15 no. 3
& no.4.
- An appliance that is connected to the
Elan has a fault, e.g. instance conden-
sing unit.
Check all appliances connected to
the Elan and correct the fault.
E152
Flash memory fault.
- Fault in control pcb system.
Take the voltage from the appliance.
Replace control pcb.
Put voltage back on appliance; fault
has automatically been reset.
E999
'LSVZLWFKHVRQFRQWUROSFE
not set correctly.
-
$SSOLDQFHGRHVQRWKLQJUHGIDXOW/('
RQRSWLRQDOPXOWLSOHVZLWFKLVQRW
activated either.
Take the voltage from the appliance.
Set dipswitches to correct position
VHH
.
Put voltage back on appliance; fault
has automatically been reset.
Note!
If mode 2 of a multiple switch does not work, the modular connector of the multiple switch has been connected the wrong way round.
Cut off one of the RJ connectors to the multiple switch and mount a new connector the other way round.