Air 70 Rev. D
29
A = Air 70
B = Plus pcb
C = Control pcb
D = Brink Home i module; mount over the Plus pcb us-
ing the supplied bracket
E = Cable supplied with Brink home i module;
Connect the connector mounted on the cable to pcb
connection X19
Refer to the documentation supplied with this kit for more
information about application of the Brink home i module
and on how to connect it.
Chapter 10 Electric connections accessories
10.6 Connecting the
Brink home i module
(only possible for Plus pcb)
E
F
X19
230V
50Hz
A
D
C
X19
10.7 Connecting Air 70 on MODBUS (only possible for Plus pcb)
The plus pcb of the Air 70 can directly be connected to a MODBUS network (see §9.2).
Note:
When MODBUS is active, the ventilation mode of the appliance cannot be changed using the push buttons or, if applicable, the
connected 4-way switch! In addition, any connected RH or CO2 sensor will not work!
MODBUS will only function as from software versions S1.07.01 (control pcb) and S1.01.03 (plus pcb).
,IWKH$LUPXVWEHDFWLYDWHGWKURXJK02'%86WKH02'%86DGGUHVVPXVWEHVHWWRWKHQWKHUHTXLUHGDLUÀRZUDWHFDQEH
set.
Note:
,IWKHSRZHUWRWKH$LUKDVEHHQLQWHUUXSWHGERWKWKH02'%86DGGUHVVDQGWKHGHVLUHGDLUÀRZUDWHPXVWEHVHWDJDLQ
Setting values
Function
Code
0x06
MODBUS
adress
Description
Correction
factor
Signed
Values / Comments
1000
MODBUS slave address
-
no
1 - 247/ Set as standard at 11(Set only during installation procedure)
6001
Set ventilation capacity [ [m
3
/h]
1
no
15 - 70 m
3
/h
6006
Operation bypass valve
-
no
0=auto mode/ 1=bypass valve closed/ 2=bypass valve open
6007
Filter reset (command)
-
no
¿OWHUUHVHW
6012
Reset Air 70 (commando)
-
no
1 = HRV appliance reset
6013
Remote control (commando)
-
no
9HQWLODWLRQÀRZUDWHDVSHU%ULQN+59DSSOLDQFH
9HQWLODWLRQÀRZUDWHDVSHU02'%86
Setting values
Function
Code
0x06
MODBUS
adress
Description
Correction
factor
Signed
Values / Comments
4002
Appliance Type
-
no
32 = ventilation
4004
Appliance version (basic/plus)
-
no
1 = basis / 2 = plus
4009
Current temp. sensor "from atmosphere"
0.1
yes
-
4010
Current temp. sensor "from dwelling"
0.1
yes
-
4028
Current ventilation capacity supply [m
3
/h]
1
no
-
4029
Current ventilation capacity exhaust [m
3
/h]
1
no
-
4030
Position bypass valve
1
no
0=initialising/1=>open/2=>close/ 3=open/4=closed/255= position. unknown)
4031
Operation bypass valve
1
no
0=auto mode/ 1=bypass valve closed/ 2=bypass valve open
4037
Status preheater
1
no
0= initialising/ 1= not active/ 2= active/ 3= test mode/ 255= position
4038
Preheater power [%]
0.1
no
-
4039
Current fault code
0.1
no
HRV appliance fault code ( 0 = no fault)
4040
Filter message
-
no
0 = Filter clean / 1 = Filter fouled
4070
Alarm contact
1
-
0 = Not activated / 1 = Activated
4071
Internal CO2 sensor value
1
-
-
4072
Internal RH sensor value
0.1
-
-
4080
Systeem status
-
-
-
B