Level 0
Level 1 (On screen)
Level 2 (On screen)
Parameters (On screen)
*
High Battery Voltage Threshold
(HIGH VOLT THRESHOLD)
9.0 – 32.0 volt
*
High Battery Voltage Delay
(HIGH VOLT DELAY)
5 – 1800 sec
Maintenance
(MAINTENANCE)
Maintenance Alarm
(MAINT ALARM)
Alarm Action
(ACTION)
Notification/Warning
Due At Engine Hours
(DUE AT ENGINE HOURS)
10 – 65000 Hrs
Alarm Due Date
(ALARM DUE
DATE)
Alarm Due Date
DD/MM/YYYY
Rotary Actuator
(ROTARY
ACTUATOR)
General
(GENERAL)
*
Actuator Application
(ACTUATOR APPLN)
As E-Governor/As Start / Stop
Device
*
Actuator Speed
(ACTUATOR SPEED)
1 – 10 x 25 Hz
*
Actuator Direction
(ACTUATOR DIRECTION)
(Clockwise/Anti–Clockwise) to
Stop
Engine Start
Strategy
(ENG START
STRGY)
*
Cranking Steps
(CRANKING STEPS)
5 – 5000
*
Initial Low Speed Delay
(INIT LOW SPEED DELAY)
0 – 180 sec
*
Initial Low Speed
(INIT LOW SPEED)
500 – 1800 RPM
*
PID Trigger Speed
(PID TRIGGER SPEED)
20 – 2800 RPM
*
Ramp Up Time
(RAMP UP TIME)
1 – 180 sec
*
PID on Time
(PID ON TIME)
1 – 180 sec
*
LIM P Gain
(LIM P GAIN)
0 – 1000
*
LIM I Gain
(LIM I GAIN)
0 – 2000
*
LIM D Gain
(LIM D GAIN)
0 – 1000
*
Cold Sweep Enable
(COLD SWEEP ENABLE)
Yes/No
*
Cold Sweep Angle
(COLD SWEEP ANGLE)
0 – 180 Deg
Generator EGov
Configuration
(GEN EGOV CNFG)
*
Set Speed Selection
(SET SPEED SELECTION)
Fixed Speed(0% Droop)/
Speed Bias Input (0-5 V)/
Load Based Droop
*
Droop
(DROOP)
0 – 4 %
*
Target Speed
(TARGET SPEED)
500 – 4000 RPM
*
Proportional Gain (Kp)
(PROPORTIONAL GAIN)
0 – 1000
*
Integral Gain (Ki)
0 – 2000