Not for
Reproduction
Page | 12
Level 0
Level 1 (On screen)
Level 2 (On screen)
Parameters (On screen)
Sensor
(DISCONN ON LOP SENS)
*
Pressure Sensor Monitoring
Threshold
(DISCONN LOP THRESH)
0.5 – 10.0 bar
*
Monitor Pressure Switch Before
Crank
(MON LLOP BEFR CRANK)
Disable/Enable
*
Monitor Pressure Sensor Before
Crank
(MON LOP BEFR CRANK)
Disable/Enable
*
Disconnect On Oil Pressure
Switch
(DISCONN ON LLOP SW)
Disable/Enable
*
Pressure Switch Transient Time
(LLOP SW TRANS TIME)
0.0 – 3.0 sec
*
Crank Disconnect At Alt
Frequency
(DISCONN AT ALT FREQ)
10 – 70 Hz
*
Crank Disconnect At Engine
Speed
(DISCONN AT ENG SPEED)
150 – 4000 rpm
Speed Monitoring
(SPEED MONITOR)
*
Engine Speed Sense Source
(SPEED SENSE SOURCE)
Sensor input only/
Alternator output only/
Primary Sensor/Secondary
Alternator/
Primary Alternator/Secondary
Sensor
*
Flywheel Teeth
(FLYWHEEL TEETH)
1 – 300
*
Under-speed Shutdown
(UNDER SPEED SHUTDOWN)
Disable/Enable
*
Under-speed Threshold
(UNDER SPD THRESHOLD)
0 – 3600 rpm
*
Under-speed Delay
(UNDER SPD DELAY)
1 – 60 sec
*
Over-speed Threshold
(OVER SPD THRESHOLD)
700 – 4500 rpm
*
Over-speed Delay
(OVER SPEED DELAY)
0.1 – 20 sec
*
Gross Over-speed Threshold
(GROSS OS THRESHOLD)
100 – 200 %
Battery Monitoring
(BATTERY
MONITOR)
*
Low Battery Voltage Action
(LOW VOLT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown
*
Low Battery Voltage Threshold
(LOW VOLT THRESHOLD)
8.0 – 31.0 volt
*
Low Battery Voltage Delay
(LOW VOLT DELAY)
5 – 1800 sec
*
High Battery Voltage Action
(HIGH VOLT ACTION)
None/Notification/Warning/
Electrical Trip/Shutdown