PowerBOSS™

5600W Portable Generator

OPERATION

USING THE  GENERATOR

System Ground

The generator has a system ground that connects the
generator frame components to the ground terminals on
the AC output receptacles.The system ground is connected
to the AC neutral wire (the neutral is bonded to the
generator frame).

Special Requirements

There may be Federal or State Occupational Safety and
Health Administration (OSHA) regulations, local codes, or
ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or
the local agency having jurisdiction.

• In some areas, generators are required to be registered

with local utility companies.

• If the generator is used at a construction site, there may

be additional regulations which must be observed.

Connecting to a Building’s Electrical

System

Connections for standby power to a building’s electrical
system must be made by a qualified electrician.The
connection must isolate the generator power from utility
power, and must comply with all applicable laws and
electrical codes.

Generator Location

Generator Clearance

Place generator in a well ventilated area, which will allow
for removal of deadly exhaust gas. DO NOT place
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow exhaust
gas to collect in a confined area (Figure 3). Prevailing winds
and air currents should be taken into consideration when
positioning generator.

• When using generator for backup power, notify utility

company. Use approved transfer equipment to isolate
generator from electric utility.

• Use a ground fault circuit interrupter (GFCI) in any damp or

highly conductive area, such as metal decking or steel work.

• DO NOT touch bare wires or receptacles.
• DO NOT use generator with electrical cords which are worn,

frayed, bare or otherwise damaged.

• DO NOT operate generator in the rain or wet weather.
• DO NOT handle generator or electrical cords while standing

in water, while barefoot, or while hands or feet are wet.

• DO NOT allow unqualified persons or children to operate or

service generator.

Generator produces powerful voltage.
Failure to isolate generator from power utility
can result in death or injury to electric utility
workers due to backfeed of electrical energy.

WARNING

Figure 3 — Generator Clearance

Typical Generator Shown

• Keep at least 5 ft. (152 cm) clearance on all sides of generator

including overhead.

Exhaust heat/gases can ignite combustibles,
structures or damage fuel tank causing a fire.

WARNING

Using a generator indoors WILL KILL YOU 
IN MINUTES. 

Exhaust contains carbon monoxide, a 
poison gas you cannot see or smell. 

NEVER use in the home 

or in partly enclosed 

areas such as garages. 

ONLY use outdoors and 

far from open windows, 

doors, and vents. 

Содержание 30230

Страница 1: ...da Generador Helpline 1 800 743 4115 M F 8 5 CT web www briggsandstratton com PowerBOSS is a trademark of Briggs Stratton Power Products PowerBOSS es una marca registrada de Briggs Stratton Power Products Model Modelo 030230 5600W Before using this product read this manual and follow all Safety Rules and Operating Instructions WARNING Antes de utilizar el producto lea este manual y siga todas las ...

Страница 2: ...engine operator s manual SAFETY RULES This is the safety alert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death The safety alert symbol is used with a signal word DANGER CAUTION WARNING a pictorial and or a safety message to alert you to hazards DANGER indicates a hazard which if not avoided will ...

Страница 3: ...eational vehicle RV Running generator gives off carbon monoxide an odorless colorless poison gas Breathing carbon monoxide can cause nausea fainting or death WARNING WHEN ADDING OR DRAINING FUEL Turn generator OFF and let it cool at least 2 minutes before removing fuel cap Loosen cap slowly to relieve pressure in tank Fill or drain fuel tank outdoors DO NOT overfill tank Allow space for fuel expan...

Страница 4: ...sive vapors DO NOT insert any objects through cooling slots If connected devices overheat turn them off and disconnect them from generator Shut off generator if electrical output is lost equipment sparks smokes or emits flames unit vibrates excessively Improper treatment of generator can damage it and shorten its life CAUTION WHEN ADJUSTING OR MAKING REPAIRS TOYOUR GENERATOR Disconnect the spark p...

Страница 5: ...n and serial number of generator Please have these readily available when calling for assistance Fuel Tank Capacity of seven 7 U S gallons Grounding Fastener Consult your local agency having jurisdiction for grounding requirements in your area Oil Fill Cap Dipstick Check and fill engine with oil here Recoil Starter Used to start the engine Rocker Switch Set this switch to On before using recoil st...

Страница 6: ...Engine oil Operator s manual Engine operator s manual Wheel kit If any parts are missing or damaged call the generator helpline at 1 800 743 4115 Install Wheel Kit NOTE Wheel kit is not intended for over the road use You will need the following tools to install these components 2 13mm wrenches Socket wrench with a 13mm socket Pliers Safety glasses Refer to Figure 1 and install the wheel kit as fol...

Страница 7: ...an fresh regular UNLEADED fuel with a minimum of 87 octane DO NOT use fuel which contains Methanol DO NOT mix oil with fuel 2 Clean area around fuel fill cap remove cap 3 Slowly add regular unleaded fuel to fuel tank Be careful not to overfill Allow at least 1 5 of tank space for fuel expansion Figure 2 4 Install fuel cap and let any spilled fuel evaporate before starting engine CAUTION Refer to e...

Страница 8: ...aust gas is kept away from any windows doors ventilation intakes or other openings that can allow exhaust gas to collect in a confined area Figure 3 Prevailing winds and air currents should be taken into consideration when positioning generator When using generator for backup power notify utility company Use approved transfer equipment to isolate generator from electric utility Use a ground fault ...

Страница 9: ...art generator and let engine stabilize before connecting electrical loads Connect electrical loads in OFF position then turn ON for operation Turn electrical loads OFF and disconnect from generator before stopping generator Exceeding generators wattage amperage capacity can damage generator and or electrical devices connected to it CAUTION When starting engine pull cord slowly until resistance is ...

Страница 10: ...e phase loads requiring up to 5 600 watts of power 5 6 kW at 23 3 Amps for 240 Volts or two independent 120 Volt loads at 20 Amps each The outlet is protected by push to reset circuit breakers 120 Volt AC 20 Amp Duplex Receptacles Each duplex receptacle Figure 6 is protected against overload by a push to reset circuit breaker Use each receptacle to operate 120 Volt AC single phase 60 Hz electrical...

Страница 11: ...he generator output to stabilize engine runs smoothly and attached device operates properly 4 Plug in and turn on the next load 5 Again permit the generator to stabilize 6 Repeat steps 4 and 5 for each additional load NEVER add more loads than the generator capacity Take special care to consider surge loads in generator capacity as described above Wattages listed are approximate only Check tool or...

Страница 12: ...NOT use a garden hose to clean generator Water can enter engine fuel system and cause problems In addition if water enters generator through cooling air slots some of the water will be retained in voids and cracks of the rotor and stator winding insulation Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings Generator Cleani...

Страница 13: ...vent gum from forming in fuel system or on essential carburetor parts add fuel stabilizer into fuel tank and fill with fresh fuel Run the unit for several minutes to circulate the additive through the carburetor The unit and fuel can then be stored for up to 24 months Fuel stabilizer can be purchased locally DO NOT store fuel from one season to another unless it has been treated as described above...

Страница 14: ...or runs good at no load but bogs down when loads are connected 1 Short circuit in a connected load 2 Generator is overloaded 3 Shorted generator circuit 1 Disconnect shorted electrical load 2 See Don t Overload Generator 3 Contact Authorized service facility Generator will not start or starts and runs rough Low oil level Fill crankcase to proper level or place generator on level surface Generator ...

Страница 15: ...nty repair and apologize to you for being inconvenienced Any Authorized Service Dealer may perform warranty repairs Most warranty repairs are handled routinely but sometimes requests for warranty service may not be appropriate For example warranty service would not apply if equipment damage occurred because of misuse lack of routine maintenance shipping handling warehousing or improper installatio...

Страница 16: ...la Agencia de Protección Ambiental Para mayor información acerca de la garantía consulte con el manual del operario del motor REGLAS DE SEGURIDAD Éste es el símbolo de alerta de seguridad Sirve para advertir al usuario de un posible riesgo para su integridad física Siga todos los mensajes de seguridad que figuren después de este símbolo para evitar lesiones o incluso la muerte El símbolo de alerta...

Страница 17: ...ispas llamas abiertas pilotos calor y otras fuentes de ignición NO encienda un cigarrillo o fume CUANDO PONGA EN FUNCIONAMIENTO EL EQUIPO Compruebe que la bujía el silenciador el tapón del depósito de combustible y el filtro de aire están instalados NO arranque el motor sin la bujía instalada CUANDO OPERE EL EQUIPO NO incline el motor o el equipo de tal manera que la combustible se pueda derramar ...

Страница 18: ... polvo suciedad o vapores corrosivos NO inserte cualquier objeto a través de las ranuras de enfriamiento Si los aparatos conectados se sobrecalientan apáguelos y desconéctelos del generador Apague el generador si Se pierde la salida eléctrica El equipo produce chispas humo o emite llamas La unidad vibra de una manera excesiva El tratamiento inadecuado del generador puede dañarlo y acortar su vida ...

Страница 19: ... Colóquelo en la posición Off Apagado para detener un motor en funcionamiento Palanca del Cebador Usada cuando se está dando arranque a un motor frío Tapa del Depósito del Aceite Llene el motor con aceite aquí Tanque del Combustible El tanque tiene una capacidad de 7 galones americanos de gasolina sin contenido de plomo Tomacorriente Dobles de 120 Voltios AC 20 Amperios Pueden ser utilizados para ...

Страница 20: ...ontenido de la Caja Revise todo el contenido comparándolo con la lista a continuación Unidad Principal Aceite del Motor Manual del Operario Manual del Operario del Motor Juego de Ruedas Si cualquier parte falta o está dañada llame a la Línea de Ayuda del Generador al 1 800 743 4115 Instale el Juego de Ruedas NOTA Este Juego de Ruedas no ha sido diseñado para ser usado en la carretera Necesitará la...

Страница 21: ...el combustible retire la tapa 3 Agregue lentamente combustible regular SIN PLOMO al tanque de combustible Use un embudo para evitar que se derrame Llene el tanque lentamente hasta aproximadamente 1 5 por debajo de la parte la cima del cuello del tubo de llenado Figura 9 4 Instale la tapa del tanque de combustible y la espera para algún combustible rociado para evaporar PRECAUCIÓN Consulte el manua...

Страница 22: ...e Figura 10 Tenga en cuenta los vientos y las corriente de aire preponderantes cuando elija la ubicación del generador Cuando use un generador como poder de energía auxiliar notifique a la compañía de utilidades Use el equipo de transferencia aprobado para aislar el generador de otra utilidad eléctrica Use un interruptor para la falla del circuito de tierra GFCI en cualquier área bastante húmeda o...

Страница 23: ...Apague OFF las cargas eléctricas y desconéctelas del generador antes de parar el generador El sobrepasar la capacidad del amperaje y vataje del generador puede dañar al generador y los aparatos eléctricos conectados al mismo PRECAUCIÓN Válvula del Combustible en posición On Figura 11 Válvula de Combustible Cuando arranque el motor tire lentamente del cable hasta sentir una resistencia y a continua...

Страница 24: ... de energía a 23 3 Amperios para 120 Voltios 5 600 vatios de energía 5 6 kW a 23 3 Amperios para 240 Voltios La salida está protegida por un corto circuito de del tipo empuje para reposicionar 120 Volt AC 20 Amp Receptáculos Dobles Cada receptáculo Figura 13 está protegido en contra de sobrecargas por un corto circuitos de del tipo empuje para reposicionar Use cada receptáculo para operar 120 Volt...

Страница 25: ...tor funciona suavemente y el aparato conectado al mismo trabaja adecuadamente 4 Conecte y encienda la próxima carga 5 De nuevo permita que el generador se estabilice 6 Repita los pasos 4 y 5 para cada carga adicional que usted tenga NUNCA añada más cargas sobre la capacidad del generador Tome una atención especial en considerar las cargas de corriente según la capacidad del generador como se descr...

Страница 26: ...ibles en su superficie exterior NOTA NO recomendamos el uso de mangueras de jardín para limpiar el generador El agua podría introducirse en el sistema de combustible del motor y causar problemas Además si el agua se introduce al generador a través de las ranuras para aire de enfriamiento algo del agua quedará retenida en los espacios vacíos y grietas del aislamiento del devanado del estator y roto...

Страница 27: ...comienza a oxidarse El óxido y o la suciedad en la gasolina le causará problemas Almacene la unidad en un área limpia y seca DIAGNOSITICOS DE AVERÍAS Problemo Accion Causa El motor está funcionando pero no existe salida de AC disponsible 1 El interruptor automático de circuito está abierto 2 Conexión mal o defectuosa del juego de cables 3 El dispositivo conectado está dañado 4 Avería en el generad...

Страница 28: ...itarios destinados al mantenimiento de las constantes vitales Esta garantía excluye los fallos debidos a hechos fortuitos y a otros acontecimientos de fuerza mayor que escapan al control del fabricante BRIGGS STRATTON POWER PRODUCTS GROUP LLC JEFFERSON WI EE UU Segundo año despide sólo 198189S Rev 0 02 01 2006 POLÍTICA DE GARANTÍA PARA EL PROPIETARIO DE GENERADOR PORTÁTIL BRIGGS STRATTON POWER PRO...

Отзывы: