Briggs & Stratton Power Products Backup Power System
Owner’s Manual

12

BEFORE INITIAL START-UP

Engine Oil

This engine is shipped from the factory filled with the
recommended oil. Before starting the engine, check oil level
and ensure that engine is serviced as described on page 18
in “Checking Oil Level”.

CAUTION!

Any attempt to crank or start the

engine before it has been properly serviced with the
recommended oil will result in an engine failure that
is not covered under warranty.

Oil Considerations

Your Backup Power System is equipped with an engine that
has been pre-run at the factory and does not require the
traditional “break-in”  procedure.

In order to provide a greater “backup” capability, the
system is filled with synthetic oil (API SJ/CF 5W-30W).This
allows for system operation in the widest range of
temperature and climate conditions.

NOTE: The use of synthetic oil DOES NOT alter the
required oil change intervals described later in the
Maintenance section of this manual.

Battery Connection

The Backup Power System is supplied with a 12 Volt DC
18 Amp-Hour sealed rechargeable battery. It is installed in
the unit and the battery cables are connected at the
factory.The unit’s 15 Amp fuse has been removed for
shipping (this prevents the unit from starting).

CAUTION!

Do Not install the 15 Amp fuse until

all plumbing and wiring has been completed and
inspected. Failure to install the fuse as described in
the Installation Manual could cause the engine to
start.

NOTE: With the battery installed, utility power supplied to
the Automatic Transfer Switch, and the unit in AUTO mode,
the battery receives a trickle charge while the engine is not
running.The trickle charger cannot be used to recharge a
battery that is completely discharged.

Gaseous Fuel System

• Ensure that all fuel pipe connections are tight, secure and

without leaks.

• Ensure that all shutoff valves are OPEN and that

adequate pressure is available.

If you smell ‘raw’ gaseous fuel (natural or LP) near the unit,
immediately turn off the gas supply to the generator.
Contact your gas utility or the system installer for
assistance in determining the source of the smell.

The AUTO/OFF/MANUAL  Switch

This three-position device is referred to herein as
“AUTO/OFF/MANUAL”. It is found on the control panel, as
shown earlier, and is used as follows:

• “AUTO” position is the normal operating position. If a

utility power outage is sensed, the system will start the
generator, let it reach stable operating speed, then
connect generator power to the sub-panel.
When utility power is restored, the system reconnects
utility power to the sub-panel, lets the engine ‘cool
down’, shuts off the generator, and waits for the next
utility power outage.

• “OFF” position turns off a running generator, takes the

system out of Automatic mode and resets faults.The unit
will not exercise, but the ‘Set Exercise’ setting is not lost.

• “MANUAL” position starts the engine but does not

disconnect utility power from the sub-panel. It is used for
maintenance or diagnostic functions.

CAUTION!

With the switch set to AUTO, the

engine may crank and start at any time without
warning. Such automatic starting normally occurs
when utility source voltage drops below a preset
level or during the normal exercise cycle.To prevent
possible injury that might be caused by such sudden
starts, always set the AUTO/OFF/MANUAL switch
to OFF and remove the 15 Amp fuse before
working on or around the generator or transfer
switch.

The other controls and devices installed on the control
panel are described on page 10, “Know Your System
Control Panel”.

Содержание 1461-2

Страница 1: ...ision 2 12 04 2001 Visit our Generac website www generac portables com NOT INTENDED FOR USE AS PRIMARY POWER IN PLACE OF UTILITY OR IN LIFE SUPPORT APPLICATIONS OWNER S MANUAL 8000 10000 Watt Backup P...

Страница 2: ...imer 13 MANUAL OPERATION 14 Transfer to Generator Power 14 Transfer Back to Utility Power 14 SPECIFICATIONS 14 Generator 14 Engine 14 MAINTENANCE 15 Fault Detection System 15 Reset Fault Detection Sys...

Страница 3: ...equipment when you are physically or mentally fatigued An adequate unobstructed flow of cooling and ventilating air is critical for generator operation Do Not alter the installation or permit even par...

Страница 4: ...ntact the store at which you purchased your Briggs Stratton Backup Power System your dealer or your utility power provider The BPS Warranty is VOID unless the system is installed by certified electric...

Страница 5: ...5 and minimum propane content of 90 CAUTION This equipment is equipped with an automatic safety gas fuel shut off valve Do Not operate the equipment if the fuel shut off valve is missing or inoperativ...

Страница 6: ...interruption The essential circuits are gathered in a special circuit breaker box referred to as the Essential Circuit sub panel that is connected by conduit to the transfer switch This breaker box i...

Страница 7: ...g This rating is applicable to installations served by a reliable normal utility source This rating is only applicable to variable loads with an average load factor of 80 of the standby rating for a m...

Страница 8: ...s making delivery note all damage on the freight bill and affix his signature under the consignor s memo of loss or damage If loss or damage is noted after delivery separate the damaged materials and...

Страница 9: ...ise to comply with most residential codes Oil Dip Stick Used to check the engine oil level Oil Drain Hose Provided to facilitate oil changing Oil Fill Cap Remove to service the engine with recommended...

Страница 10: ...or the next utility power outage While waiting it maintains battery with trickle charge OFF position turns off running generator takes system out of Automatic mode and resets any detected faults MANUA...

Страница 11: ...away from the unit while pulling the door down and out of the upper door channel The door will come free of the generator enclosure The battery door and the air intake door do not have locks or lift h...

Страница 12: ...ger cannot be used to recharge a battery that is completely discharged Gaseous Fuel System Ensure that all fuel pipe connections are tight secure and without leaks Ensure that all shutoff valves are O...

Страница 13: ...tor Let the system go through its entire automatic operation sequence 5 With the generator output supplying its loads turn ON the main distribution panel circuit breaker that supplies utility power to...

Страница 14: ...ct procedure is followed The exerciser does not need to be re set if the 15 Amp fuse is removed or changed The exerciser will need to be re set if the 12 Volt DC battery is disconnected If you want to...

Страница 15: ...nerac part number 188443 Replace the battery in the battery compartment after it has been fully recharged connecting the NEGATIVE cable last Install the 15 Amp fuse Reset the Fault Detection system as...

Страница 16: ...problem you may need to contact your installer or Generac Technical Services for assistance When the problem is corrected reset the Fault Detection system as described above Engine Overspeed This faul...

Страница 17: ...decrease the insulation resistance of these windings To Clean the Generator CAUTION Never insert any object or tool through the air cooling slots even if the engine is not running Use a damp cloth to...

Страница 18: ...into the engine Figure 7 Changing the Oil and Oil Filter Oil capacity is approximately 1 1 2 quarts 48 ounces or 1 6 liters when changing oil and filter Use only 5W 30 API Service Grade SJ or greater...

Страница 19: ...Stratton parts or their equivalent The use of replacement parts which are not of equivalent quality may damage the engine Clean the foam precleaner every 25 hours and the cartridge every 100 hours of...

Страница 20: ...TY AND WILL ADVERSELY AFFECT SYSTEM OPERATION To assure smooth operation keep governor linkage springs and controls free of debris Valve Lash Valve lash must be checked while engine is cold after ever...

Страница 21: ...6 3 Contact Generac Portable Products service facility Engine will not start or starts and runs rough 1 15 Amp fuse missing or blown 2 Dirty air cleaner 3 Out of fuel 4 Spark plug wire not connected...

Страница 22: ...Briggs Stratton Power Products Backup Power System Owner s Manual 22 UNIT SCHEMATIC DIAGRAM...

Страница 23: ...Briggs Stratton Power Products Backup Power System Owner s Manual 23 UNIT WIRING DIAGRAM PLG...

Страница 24: ...Briggs Stratton Power Products Backup Power System Owner s Manual 24 TRANSFER SWITCH SCHEMATIC DIAGRAM...

Страница 25: ...Briggs Stratton Power Products Backup Power System Owner s Manual 25 TRANSFER SWITCH WIRING DIAGRAM...

Страница 26: ...Briggs Stratton Power Products Backup Power System Owner s Manual 26 UNIT EXPLODED VIEW...

Страница 27: ...41 H185961GS 1 CORNER Alt Air Inlet Left 42 26850GS 3 WASHER Ext M6 1 4 Shakeproof 43 B4300GS 2 BOLT SWAG 1 4 20 44 B4769GS 1 CONTACTOR Starter Item Part Qty Description 45 186375GS 1 CLAMP Hose 46 1...

Страница 28: ...Briggs Stratton Power Products Backup Power System Owner s Manual 28 ENCLOSURE EXPLODED VIEW...

Страница 29: ...Inlet Right 20 H186047GS 1 RAIL Support Upper Engine Side 21 H185969GS 1 DOOR Engine Air Inlet 22 H185964GS 1 CORNER Engine Left Side 23 H187235GS 1 BAFFLE with Insulation 24 74908GS 12 TAPTITE M5 25...

Страница 30: ...Briggs Stratton Power Products Backup Power System Owner s Manual 30 INSULATION SET EXPLODED VIEW...

Страница 31: ...8GS 1 BAFFLE Horizontal Alt Side 8 H187232GS 2 DOOR with Insulation 9 189144GS 1 DECAL Unit 10 H185972GS 1 BASE Mounting 11 186641GS 1 DECAL Operation Instructions 12 186646GS 1 DECAL Warning Engine C...

Страница 32: ...5 B4910GS 1 ASSEMBLY Housing 6 B4911GS 1 CAP 7 B4912GS 1 COVER Blind End 8 B4913GS 1 COVER Top Black 9 B4914GS 2 CAPACITOR 25mF 450V 10 B4915GS 1 BEARING 62052RS C3 11 B4916GS 1 CAPACITOR Diode Varist...

Страница 33: ...RACKET Resistor 10 B4867GS 1 RESISTOR 25W 5 OHM 11 57345GS 2 NEUTRAL 4 Prong 12 186413GS 4 STANDOFF Control Board 13 B4300GS 6 BOLT Swage 1 4 20 Item Part Qty Description 14 87799GS 1 SWITCH Set Exerc...

Страница 34: ...Briggs Stratton Power Products Backup Power System Owner s Manual 34 TRANSFER SWITCH EXPLODEDVIEW...

Страница 35: ...S 4 FLAT WASHER 10 15 B5052GS 1 TERMINAL STRIP 16 22264GS 10 LOCK WASHER 8 17 51715GS 10 NUT M4 18 22097GS 1 LOCK WASHER 1 4 19 49813GS 1 NUT M6 20 B5084GS 1 DECAL UL Type 21 B5083GS 1 DECAL UL Listed...

Страница 36: ...Briggs Stratton Power Products Backup Power System Owner s Manual 36 ENGINE EXPLODED VIEW Briggs Stratton 18 hp Engine Model 354445 0123 E1...

Страница 37: ...Briggs Stratton Power Products Backup Power System Owner s Manual 37...

Страница 38: ...Briggs Stratton Power Products Backup Power System Owner s Manual 38...

Страница 39: ...Briggs Stratton Power Products Backup Power System Owner s Manual 39...

Страница 40: ...Briggs Stratton Power Products Backup Power System Owner s Manual 40...

Страница 41: ...67 691985 Knob Air Cleaner 468 690690 O Ring Seal Oil Pump Screen 479 692537 Screw Oil Pump Screen 503 691532 Strap Starter 505 690238 Nut Governor Control Lever 506 690872 Screw Carburetor Cover 506A...

Страница 42: ...Briggs Stratton Power Products Backup Power System Owner s Manual 42 NOTES...

Страница 43: ...s you should contact a B S Service Representative at 1 414 259 5262 The emission warranty is a defects warranty Defects are judged on normal engine performance The warranty is not related to an in use...

Страница 44: ...TO THE FOLLOWING Cost of normal maintenance adjustments installation and start up Units sold rated or used for Prime Power applications as the Company has defined Prime Power Contact a Generac Portabl...

Отзывы: