7- Defrosting 

1. Defrosting conditions under heating mode: 
When heating, the cumulative running time of the compressor 

45min (parameter 11)

, and the continuous running time of the compressor 

5min; 

Cooling coil temperature <-3°C (parameter 12); 

     (ambient temperature - cooling coil temperature) 

 5°C (parameter 15), and -7 °C 

 ambient temperature 

 17°C (parameter 16) for 30 seconds; 

 (ambient temperature - cooling coil temperature) 

 9°C (parameter 15 + 4°C), and a

mbient temperature < -7°C for 30 seconds; 
When the above conditions are all met, it will enter defrosting; (Note: 

 and 

 only n

eed to meet one of them) 
When the temperature of the cooling coil is faulty, and the ambient temperature is 

 

20°C, the defrosting will be timed, and the defrosting time is every 10 mins; 
 
2. Defrosting conditions at startup: 
When the stop/standby/compressor cut off time 

30min; 

-7°C 

 ambient temperature 

 3°C, and coil temperature <-3°C (parameter 12); 

When the compressor starting condition is met (the water temperature is lower than 
the backlash/starting temperature, but still not started), and the above conditions ar
e met,  it will enter defrosting; . 
 
3. Defrost operation frequency: When entering defrost, the frequency is fixed at 60Hz. 
 
4. Condition for exit the defrosting: 
After 2 minutes of defrosting, when the cooling coil temperature is 

20°C (parameter

 14) or the defrosting time reaches 10 mins (parameter 13), it will exit the defrosting. 
 
5 Defrosting steps: 
When the defrosting conditions are met, following steps will start: 
1) Compressor stops, and fan stops after 15 seconds; 
2) The four-way valve is energized at 55 seconds; 
3) The compressor restarts at 60S; 
4) The water pump keeps running; 
The following steps will be performed when the defrosting exit condition is satisfied: 
1) Compressor and fan stop; 
2) The four-way valve loses power at 55S; 
3) The fan is turned on at 60S, and the compressor starts after 5 seconds to resume 
normal heating running; 
 
6 The abnormal exit of the defrosting: 
1) When the error protection occurs during defrosting, the system immediately exits 
the defrosting and stops running; 
2) Low pressure protection is not detected during defrosting; 
       
7 Coercive defrosting: When the cooling coil temperature is lower than the defrostin
g exit temperature, press and hold the “M” + 

” buttons for 3 seconds to enter the coercive defrosting. 

 

 

 

18 

Содержание BP-110HS-SI EIP

Страница 1: ...0 STEP INVERTER Directions for installation and maintenance...

Страница 2: ...Wire control operation General diagram of the refrigerating circuit Safety and control systems Electric diagram 5 Installation p13 Rules of installation Hydraulic connections Electric connections Pro...

Страница 3: ...swimming pools Any other use not in conformity and random will be considered as dangerous and unsuitable The assembly the electric connection and the start up must be carried out by specialized and p...

Страница 4: ...3 2 8 COP A15 W26 W W 4 6 7 1 4 6 7 1 4 50 7 0 Cooling Capacity A35 W28 kW 4 3 1 0 5 3 1 5 6 2 2 3 Power Input kW 1 6 0 24 2 0 0 29 2 45 0 36 Current A 7 5 1 1 9 3 1 5 10 7 2 2 Power Supply V P Hz 22...

Страница 5: ...nometer 6 Fast connection for water outlet 7 Fast connection for water intlet 8 Wire connection for power supply 9 Evaporator 10 Fan 11 Compressor 12 High and low pressure interruptor 13 Titanium heat...

Страница 6: ...5...

Страница 7: ...eters With the function of buttons you can check current run parameters 1 F NO Meaning Range Remarks 1 Inlet water temperature 50 99 C Measured value 2 Outlet water temperature 50 99 C Measured value...

Страница 8: ...tting timer for on and off is the same the setting timer is not available When the setting timer displayed blinks Press MODE to deactivate TIMER SMART Mode Press Smart button to enter smart mode the m...

Страница 9: ...8 Light on under smart mode machine working with the standard frequency Light on under power mode machine working with the high powers Light on under silent mode machine working with the low frequency...

Страница 10: ...aporizing it is then put up in pressure and in temperature by the compressor which sends it in the condenser exchanger where it loses its heat in giving it to the water of swimming pool and comes back...

Страница 11: ...aporator in getting the heat of the water goes through in the compressor which reheats it and through in the gilled radiator which becomes condenser where it comes back to liquid state Evaporator gill...

Страница 12: ...ot damaged in case of overpressurisation of the gas The low pressure protection emits a signal when refrigerant is escaping from the conduits and the unit cannot be kept running 3 Overheating protecti...

Страница 13: ...protection off 2 When the heat pump shut down and ambient temperature 5 outlet water temperature 2 Second anti frost protection activated Heat pump will turn on automatically and run in heating mod e...

Страница 14: ...lace the fan would recycle its air and the Heat pump would be down performance The fan should not blow towards the windows or crossing point Safety distance between the swimming pool and the foot bath...

Страница 15: ...nd connect the pipe if need Hydraulic connections To respect imperatively Connection is carried out with a by pass located on the circuit of filtration upstream appliances of the chemical treatment of...

Страница 16: ...at pump exclusively the circuit breaker must be specified with curve D the fuse must be specified Am Differential protection 30 mA the length of cable between the connector block of the heat pump and...

Страница 17: ...d the current temperature Start between 1 4 minutes in the previous operation mode heating auto cooling Chose the operation mode Press the button 3S MODE Stop for 3 4 minutes reverse of cycle and rest...

Страница 18: ...Pump in these conditions the totality of the water flow goes by the Heat Pump Put into service the Heat Pump in heating mode wait for the indicated pressure being stabilized the correct setting of th...

Страница 19: ...e conditions ar e met it will enter defrosting 3 Defrost operation frequency When entering defrost the frequency is fixed at 60Hz 4 Condition for exit the defrosting After 2 minutes of defrosting when...

Страница 20: ...lains the error codes caused by a defective regulating component or by a security operation Error codes Problem Cause Solution E 03 Water over heating fault Water flow not enough Water flow switch fau...

Страница 21: ...8 Fan motor fault The PCB dial code is wrong Change to the correct dial code E 29 Return gas temperature sensor fault Connection fault Check the connection Return gas temperature sensor fault Replace...

Отзывы: