background image

Adjustment – Poppet Seat  

Balance Pressure A/M Adjustment

NOTICE

The Poppet Seat Adjuster is factory set and sealed  

before the positioner is shipped. Do not adjust  

Auto / Manual default setting (Automatic) as shown.

Troubleshooting

Positioner does not respond to the input signal

1. Check the supply pressure to the actuator. The

supply must be at least 40 psi / 2.7 Bar / 0.27 MPa

2. Check if input signal is properly supplied to the

positioner. The signal range should be 3-15 psi.

3. Check if the positioner’s nozzle 

(5) 

has been 

blocked. If the nozzle has been blocked by any

substances, please contact your local

Bray distributor for a replacement.

4. Check if feedback shaft has been adjusted

properly and engaged to actuator pinion.

The pressure of OUT 1 reaches exhausting 
pressure level and does not come back down

1. Check Auto/Manual (A/M) switch. For proper

operation it must be in the “A” position.

2. Check for a gap or damage between the nozzle

(5)

 and the flapper 

(13)

. If damaged, please con-

tact your local Bray distributor.

Hunting occurs

• Check if feedback springs 

(15)

 have been dis-

placed.

• Hunting may occur when the positioner is

attached to a very small capacity actuator (ex:

Bray Series 92/93 size 48). In such case, install

an output orifice for OUT 1 and OUT 2 per the

following steps.
1. Remove Pilot Valve Assembly 

(Figure 2)

.

2. Remove the O-ring from OUT 1 and OUT 2

port, install orifice in and reinstall the O-ring

to OUT 1 and OUT 2 again. When mounting

the output orifice, pay attention not to let dust

or debris enter the orifice 

(Figure 16)

.

3. If hunting does not stop after installing the

output orifice, please contact your local

Bray distributor. 

Actuator only operates Open or Closed

1. Check tubing connection
2. Check cam direction

Linearity is too low

1. Check if Zero and Span has been properly adjusted.
2. Check if supply air pressure level is stable from

the regulator. If the level is unstable, replace the

regulator.

O-ring

Orifice Diameter

Orifice

OUT 1

OUT 2

O-ring

Orifice Diameter

Orifice

OUT 1

OUT 2

Bray

®

 is a registered trademark of  BRAY INTERNATIONAL, Inc. 

© 2013 Bray International.  All rights reserved.

OM-6P-001  11-2013  

R

CONTROLS

Figure 15

Figure 14

A/M 

Automatic/ Manual

Poppet Seal 

Adjuster

A/M 

A/M 

Bray Series 6P

Operation and Maintenance Manual

Jamieson Equipment Company

www.jamiesonequipment.com

toll free 800.875.0280

Содержание 6P Series

Страница 1: ...SERIES 6P Pneumatic Positioner OPERATION AND MAINTENANCE MANUAL R CONTROLS...

Страница 2: ...s a potential situation which if not avoided may result in an undesirable result or state including property damage CAUTION Beware of moving parts when positioner is operated CAUTION Do not dismantle...

Страница 3: ...duction 4 Product Description 4 Manufacturer Warranty 4 Operation Logic 5 Label Description 6 Specifications 6 Parts and Assembly 7 Dimensions 8 Installation 8 Bracket Information 9 Piping Connection...

Страница 4: ...ese products are used for the purposes for which they were designed and manufactured Bray does not warrant its products against chemical or stress corrosion or against any other failure other than fro...

Страница 5: ...poppet 14 to seat and vent the outer chambers 10 As the actuator s inner pressure increases the actuator stem 8 rotates When the signal input pressure decreases the spool 1 moves to the left reversin...

Страница 6: ...ection 1 4 NPTF Gauge Connection 1 8 NPTF Protection IP66 Cam Linear Optional Reverse Acting Ambient Temperature Ranges Std 4 F to 158 F 20 C to 70 C High 4 F to 248 F 20 C to 120 C Low 40 F to 158 F...

Страница 7: ...7 Parts and Assembly Figure 2 ZEROADJUSTMENT CONNECTOR COVER FEEDBACKSHAFT PILOTVALVE SPANADJUSTMENT INPUTBELLOWS Auto ManualAdjustment CAM DOMEGEAR SIGNALIN SUPPLYIN OUTPUT1 OUTPUT2 Auto Manual Adjus...

Страница 8: ...for hex head bolts Before installation be sure to check for the following installation components 1 1 Main Body 2 1 bracket set 3 pcs 3 8 pcs of hex head bolt M8 x 1 25P w washers 4 12 pcs of M7 alle...

Страница 9: ...ator rests with no supply pressure If a Double Acting actuator is used check actuator stem s rotation direction clockwise or counter clockwise by supplying pressure 3 Attach the Series 6P to the brack...

Страница 10: ...ng Return Actuator When mounting on the Bray S93 Spring Return Actuator OUT 1 should be connected to port A left port when facing the ports and OUT 2 should be plugged This generates increasing pressu...

Страница 11: ...Span 1 After setting the Zero Point increase the signal pressure to 15 psi Loosen the locking screw slightly and rotate or turn the Span Adjustment Screw clockwise or counter clockwise until the actu...

Страница 12: ...been dis placed Hunting may occur when the positioner is attached to a very small capacity actuator ex Bray Series 92 93 size 48 In such case install an output orifice for OUT 1 and OUT 2 per the foll...