SERIES 6A ELECTROPNEUMATIC POSITIONER
QUICK START GUIDE
6 of 12
© 2021 BRAY INTERNATIONAL, INC. ALL RIGHTS RESERVED. BRAY.COM The Information
contained herein shall not be copied, transferred, conveyed, or displayed in any manner that would
violate its proprietary nature without the express written permission of Bray International, Inc.
2.0
CALIBRATION (continued)
Step 5
Press the Menu Button
once to
reach parameter 2. Select 90°.
Step 6
Press the Menu Button
to scroll to
parameter 4.
Note: Parameter 3 is skipped for quarter-
turn actuators.
Step 7
Hold down the Up Button
until
calibration begins (>5 seconds), then
release. The device will now progress
through 5 “RUNS”, completing a series
of checks. For more information on the
calibration, please refer to the product
manual.
Note:
The calibration routine can take up
to 15 minutes.
Step 7a
Note: If an error is displayed on your
positioner during Run 2, the lower
tolerance (down tolerance) of the
adjustment wheel has been exceeded.
(If no errors are displayed, skip ahead to
step 8.)