SERIES 6A ELECTROPNEUMATIC POSITIONER
QUICK START GUIDE
5 of 12
© 2021 BRAY INTERNATIONAL, INC. ALL RIGHTS RESERVED. BRAY.COM The Information
contained herein shall not be copied, transferred, conveyed, or displayed in any manner that would
violate its proprietary nature without the express written permission of Bray International, Inc.
2.0 CALIBRATION
Step 1
Power on the unit with a 4 to 20 mA signal.
Note:
Make sure signal does not order turn-
off during calibration process.
Step 2
Press the Menu Button
for >5 seconds to enter into Configuration
mode.
Step 3
Once in Configuration mode parameter 1 is
displayed in the bottom left hand corner of
the positioner screen. Parameter 1 allows
the user to select the type of actuator
being paired with the device.
Step 4
Use the Up Button
to scroll through the
available options (in ascending order) until
you reach “turn”. This option is for quarter
turn actuators.
Note:
To scroll through parameters in
descending order, hold down the
Menu Button
while using the Down
Button
to scroll through the parameters
until you find “turn”.