CAP. 6 - MAINTENANCE
MULTIGAS 8500
6.5
REFRIGERANT GAS SCALE CHECK WITH SAMPLE WEIGHT
AND CALIBRATION, IF NEEDED, (SERVICE KIT)
Place a sample weight on the tank and check that the changes in weight are adequately
detected by the machine scale.
Place the clamp that is
part of the service kit
under the tank
Position a 10 kg
sample weight on the
clamp and check that
the weight increases by
10 kg +/- 50 g, in
case of errors in excess
execute
a
new
calibration.
Note: to verify that the item 4. sample weight support bracket doesn’t touch any component;
in case of contact, use a reference weight of 5 kg.
6.6
NEW OIL SCALE CHECK WITH SAMPLE WEIGHT AND
CALIBRATION, IF NEEDED, (SERVICE KIT)
Place a sample weight in the new oil bottle (part of the service kit) and check that the
changes to the weight are adequately detected by the machine scale. In case of errors
greater than ± 10 g execute a new oil weights calibration.
6.7
EXHAUSTED OIL SCALE CHECK WITH SAMPLE WEIGHT AND
CALIBRATION, IF NEEDED, (SERVICE KIT)
Place a sample weight in the exhausted oil bottle (part of the service kit) and check that the
changes to the weight are adequately detected by the machine scale. In case of errors
greater than ± 10 g execute a new oil weights calibration.
Содержание multigas 8500
Страница 11: ...ENGLISH 11 78 CAP 5 INSTALLATION MULTIGAS 8500...
Страница 46: ...ENGLISH 46 78 CAP 9 UPDATE MULTIGAS 8500 Select update device...
Страница 53: ...ENGLISH 53 78 CAP 11 REFRIGERANT FLUID CIRCUIT MULTIGAS 8500 RECOVERY...
Страница 54: ...ENGLISH 54 78 CAP 11 REFRIGERANT FLUID CIRCUIT MULTIGAS 8500 VACUUM...
Страница 55: ...ENGLISH 55 78 CAP 11 REFRIGERANT FLUID CIRCUIT MULTIGAS 8500 OIL TRACER INJECTION...
Страница 56: ...ENGLISH 56 78 CAP 11 REFRIGERANT FLUID CIRCUIT MULTIGAS 8500 RECHARGE...
Страница 57: ...ENGLISH 57 78 CAP 11 REFRIGERANT FLUID CIRCUIT MULTIGAS 8500 NON CONDENSABLE GASES DISCHARGE...
Страница 66: ...ENGLISH 66 78 CAP 14 SPARE PARTS MULTIGAS 8500...