Replace filter pad frames. Ensure they are

the correct way up.

If water flow appears low, there may be a

problem with foreign material clogging the
pump or pump strainer. To correct, remove
pump, dismantle base, clean and re-
assemble.

Post-season Maintenance

!

!

!

!

!

!

!

!

!

!

Turn off the power supply to the cooler.
Remove pad frames
Turn off the isolating switch inside the

cooler.

Remove pad frames. Clean them by

hosing them with clean water, but do not
use excess pressure because you might
create holes in the pad media.

Remove and clean the special water

"spreader" plates located under each edge
of the top panel. Do not disconnect from
water hose. When replacing them, check
underneath to see that the spreaders are
correctly located in the notches under the
top panel.

Drain all the water form the cooler by

removing the overflow or overflow bleed
funnel. Do NOT put it back until next
season. Do not lose the O-ring seal.

Disconnect the water supply pipe from the

tank. Make sure no water is left in the float
valve.

Clean the bottom tank thoroughly.
Replace pads frames.
Cover the cooler for winter if desired.

All units can benefit from routine
preventative maintenance. This may be
required more frequently if you are
operating under harsh conditions.
To perform Preventative Maintenance,
follow the instructions for

Pre-Season

Maintenance

at regular intervals.

In some areas and for some commercial
installations local regulations have specific
requirements for the maintenance of
evaporative air conditioning systems.
Generally these involve regular cleaning and
maintenance at (3) monthly intervals or more
frequently if necessary.

Preventative Maintenance:

Check Your Local Regulations:

3

Maintenance

To ensure that your air cooler continues to
provide reliable service for many years, it
requires some routine maintenance. There
are two forms of maintenance:
(1) pre and post season maintenance, and
(2) preventative maintenance.

Turn off the water supply.
Turn off the power supply.
Remove the filter pad frames. Insert a

screwdriver into the slots at the bottom of
the pad frames and lever upwards. Pull
the bottom of the pad frames away from
the unit, then lower the frames out of the
cabinet (Fig. 3).

Turn off the isolating switch.
Hose both sides of the filter pads

CAREFULLY

.  Ensure that the wood

wool pad material is evenly distributed,
especially make sure that there is no gaps
or holes at the TOP of PADS.

Pre-season Maintenance

Do not replace this item until

next season. Do not lose the "O" ring
seal.

!

!

!

!

!

!

!

!

!

!

(do not use excess water

pressure as this may create "holes" in
the pad material)

Check and, if necessary, clean the water

spreaders located inside the roof above
the filter pads.

Drain the water from the unit by

removing the overflow or overflow bleed
funnel.

Check pulleys for wear and correct

alignment.

Check "V" belt for wear.
Thoroughly clean and dry the bottom of

the water tank.

SEELEY INTERNATIONAL

OWNER

S MANUAL

3

Содержание ILL1461-A

Страница 1: ... English EA OWNER S MANUAL EA Evaporative Cooler ILL1461 A ...

Страница 2: ... i EA Evaporative Cooler Introduction Wall Control Functions Maintenance Troubleshooting Installation Checklist 3 2 1 4 5 ...

Страница 3: ... concerning use of the appliance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance SEELEY INTERNATIONAL OWNER S MANUAL EFFECTIVE COOLING To provide efficient cooling or ventilation the building must have sufficient exhaust openings to outdoors in the form of doors windows or other vents To assist air circulation open windows o...

Страница 4: ...nditions close openings facing the wind Generally openings opposite the supply vents are best Some experimentation will soon show the arrangement most suited to your requirements For a multiple outlet system this is generally 1 one window opened 100 to 150 mm per outlet For a short time when operating with new filter pads you may detect an odour like wet timber This is the filter material becoming...

Страница 5: ...some areas and for some commercial installations local regulations have specific requirements for the maintenance of evaporative air conditioning systems Generally these involve regular cleaning and maintenance at 3 monthly intervals or more frequently if necessary Preventative Maintenance Check Your Local Regulations 3 Maintenance To ensure that your air cooler continues to provide reliable servi...

Страница 6: ...orners woodwool pads only Air restriction in ductwork Check that the tap is turned on Check pump and pump strainer Check water distribution systems Ensure pump COOL is turned on Adjust door window opening Tease the woodwool out evenly or replace pads Call Dealer to investigate and rectify No air flow Clogged or Dirty Filter pads Circuit breaker tripped or unit fuse blown Broken fan belt Electrical...

Страница 7: ...lt min All control functions checked Owner instructed in correct operating procedure Owners Name Telephone Address Dealer Installer Date Installed Model No Serial No If you have followed the instructions and still have problems the Braemar service network is only a phone call away They can help with any aspect of operation you may not be sure of or arrange for a service person to fix any faults Ho...

Страница 8: ...ordingly specifications are subject to change without notice Please consult with your dealer to confirm the specifications of the model selected When you contact your Dealer regarding service or warranty please quote the cooler model number and serial number as shown below 859972 C Affix serial model number ker here stic seeleyinternational com AU 1110 ...

Отзывы: