background image

TouchTime

®

 

Installation

4

 

3/1/2013

 Bradley 

• 215-1378 Rev. G; ECN 13-10-005

Troubleshooting

If the TouchTime

®

 push button unit does not function properly 

1. Make sure the water supply and the 24 VAC power are both turned on.

  If the water supply and the electrical power are both turned on but the push button is still not functioning, check the wiring 

following the steps outlined in procedure #2 below.

2. Check the wiring following the procedure outlined below:

a. Turn the electrical power off.

b. Check the wiring for loose connections or corrosion and correct if necessary.

c. Turn the electrical power back on and retest the push button.

  If, after checking the wiring, the push button is still not functioning properly, test the transformer following the steps outlined in 

procedure #3 below.

3. Test the transformer with a volt meter following the procedure outlined below:

a.  Turn the water supply off (the electrical power should remain on).

b. Set the volt meter to read “24 VAC.”

c.  Connect the volt meter leads to the black and brown wires as shown in the wiring diagrams found on page 4. The voltage 

reading should indicate 24 VAC ± 10%.

  If you are unable to obtain a proper voltage reading, the transformer is not working properly and needs to be replaced. 

Contact your Bradley representative to order the replacement transformer appropriate for your application.

  If the transformer is working properly, turn the water supply back on and test the solenoid following the steps outlined in 

procedure #4 below.

4. Test the solenoid valve following the procedure outlined below:

a.  Disconnect the white and gray wires from the solenoid.

b.  Disconnect the brown power cord leads from the terminal block.

c.  Connect the brown power cord leads directly to the solenoid. The solenoid coil should activate and you should hear a single 

click and a humming noise.

  If the solenoid coil does not activate, the solenoid valve is not working properly and needs to be replaced. Contact your 

Bradley representative to order the replacement solenoid valve assembly or flush valve appropriate for your application.

  If, after checking the transformer, the solenoid valve and the wiring, you are unable to activate the sprayhead by pressing the 

TouchTime

®

 push button, the TouchTime

®

 switch assembly is not working properly and needs to be replaced. Contact your 

Bradley representative to order a replacement switch assembly.

Содержание TouchTime S45-1941

Страница 1: ...he installation file this manual with the owner or maintenance department Compliance and conformity to local codes and ordinances is the responsibility of the installer Separate parts from packaging and make sure all parts are accounted for before discarding packaging material If any parts are missing do not begin installation until you obtain the missing parts Make sure that all water supply line...

Страница 2: ...t S08 311 COLD S08 312 HOT S08 313 FLUSH Ligature Resistant Push Button S08 396 Security Fixture B Insert the push button and spring into the escutcheon then insert the escutcheon into through the hole in the front of the fixture C Thread the sensor through the mounting bracket and the fixture onto the escutcheon and secure the valve to the fixture by turning nut 1 4 turn past finger tight NOTE Us...

Страница 3: ...hart below for wire color descriptions TOUCHTIME SWITCH BLACK RED RED YELLOW TAPE WIRE NUT supplied by installer To Customer 120v supply SOLENOID VALVE BLACK WIRE BROWN WIRE OUTPUT WIRES see chart below for wire color descriptions TOUCHTIME SWITCH TRANSFORMER BLACK RED RED YELLOW TAPE WIRE NUT supplied by installer To Customer 120v supply TRANSFORMER 2 FEMALE CONNECTORS Transformer may be hard wir...

Страница 4: ...e reading should indicate 24 VAC 10 If you are unable to obtain a proper voltage reading the transformer is not working properly and needs to be replaced Contact your Bradley representative to order the replacement transformer appropriate for your application If the transformer is working properly turn the water supply back on and test the solenoid following the steps outlined in procedure 4 below...

Отзывы: