TDB3104, WF3204
Installation
16
1/15/2013
Bradley
• 215-1078 Rev. T; ECN 12-00-004
7
Electrical connections for Adaptive Infrared
START-UP NOTE: Do not use for two minutes after making
power connection. The sensors will take up to eight minutes
(without being used) to adapt to the bowl if another object is
detected during the two-minute start-up period.
A
Connect the three wires from the infrared module
assembly to the valve assembly. Attach two
of the female connect wires to the solenoids.
Attach the male connect wire to one of the 24
VAC transformer leads. Attach the remaining
transformer lead to the solenoid wire adapter.
B
Connect 24 VAC transformer provided to power
source.
C
Turn supplies on. Open stop valves completely.
D
Open volume control valve completely and check
piping installation for leaks.
E
Pass your hand in front of each sensor until air is
purged from the lines.
Infrared Module
(S50-367)
Window
(269-1351)
Valve
Assembly
Stop Valve
(S27-340)
24 VAC Transformer
(S83-134)
Female
Connect
Male
Connect
Infrared
Module Female
Connect Wire
H
C
A
Loosen Cap Screw about 1/4" (4-6 turns)
and lift up cover (do not remove).
B
Using cover, turn cartridge gently until
desired water temperature is reached. Do
not turn past stops as this may damage
unit. Push cover down and tighten screw.
This valve is NOT factory preset. Upon installation, the temperature of this
valve must be checked and adjusted to ensure delivery of a safe water
temperature. Water in excess of 110°F (43°C) may cause scalding.
8
Adjust the Temperature
D
Attach pedestal access panel with
hardware provided.
C
Clean sprayhead if necessary. Adjust the
volume control to control the flow of water.