background image

P.O. Box 309, Menomonee Falls, WI  USA  53052-0309
PHONE 800.BRADLEY (800.272.3539)  FAX 262.251.5817

bradleycorp.com

Installation 

215-1279 Rev. C; ECM 10-05-011A
© 2011 Bradley Corporation
Page 1 of 16 

1/12/11

S19-876

Drench Hose Service/Retrofit Kit 

for Heat Trace Showers

Table of Contents

Pre-Installation Information  . . . . . . . . . . . . . . . . . . 2
Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Assembly of Components  . . . . . . . . . . . . . . . . . . . 3
Service Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . 3
Troubleshooting  . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Содержание S19-876

Страница 1: ...bradleycorp com Installation 215 1279 Rev C ECM 10 05 011A 2011 Bradley Corporation Page 1 of 16 1 12 11 S19 876 Drench Hose Service Retrofit Kit for Heat Trace Showers Table of Contents Pre Installation Information 2 Installation 3 Assembly of Components 3 Service Parts List 3 Troubleshooting 4 ...

Страница 2: ...l be made to prevent unauthorized shutoff The ANSI Z358 1 standard requires an uninterruptible supply of flushing fluid at a minimum 30 PSI 0 21 MPa flowing pressure Flushing fluid should be tepid per ANSI Z358 1 The inspection and testing results of this equipment should be recorded weekly to verify proper operation This equipment should be inspected annually to ensure compliance with ANSI Z358 1...

Страница 3: ...hat the upper right plastic shell can be pulled away from the unit or removed completely NOTE Other components may have to be disassembled to remove the shell 2 Expose the pipe plug by partially removing the insulation and then remove plug 3 Connect the drench hose parts as shown using pipe sealant on the threads Do not secure the flag handle permanently at this time 4 Operate the valve to ensure ...

Страница 4: ...nd replace if check fails activates at 50 F 10 C factory set Defective freeze valve if the water temperature from the valve is above 45 F 7 C Replace the freeze valve NOTE A water supply that is at least 45 F 7 C or colder will hold the freeze bleed valve open To close the valve 1 turn the water off temporarily or plug the valve until the heat trace unit s heat warms the valve 2 increase the surfa...

Отзывы: