Installation 

S19-322

Bradley • 

215-1845 Rev. B; ECN 17-05-068 

11/21/2017

4 Complete electrical supply connections

WARNING  To prevent personal injury and damage to the components, follow all manufacturer's 

warnings and instructions when performing any maintenance or installation of 
components used in this emergency signaling system.

A

Run electric power conduit (3/4" 
conduit hub, customer provided) and 
AWG 18 minimum power wire into 
the hole to the floating terminal block 
per the wiring schematic .

B

Re-attach connector from control box 
to front panel (located on the lower 
right hand corner of the control board) .

Compliance and conformity to local codes and 
ordinances is the responsibility of the installer.

C

Re-attach the cover and tighten the 
four screws .

Do not exceed 14 AWG wire.

5 Test the Signaling System

Testing the signaling system for the first time using the drench shower may expose the flow switch to 
an unnecessary water hammer since the downstream piping may be empty of water. The flow switch is 
designed to withstand such a water hammer, but using the smaller eyewash flow is recommended.

A

Apply power to the alarm branch 
circuit . The alarm should remain 
in the OFF position and the green 
beacon light will turn on at a steady 
state .

B

Open the eyewash valve . The horn 
should sound and the beacon light 
will become a signal light and flash 
amber shortly after water flows from 
the system .

C

Close the eyewash valve . Once flow 
is discontinued, the horn will shut off 
and the beacon/signal light return to 
green steady state .

E

Repeat steps A through D, this time 
using the drench shower only .

Discontinuing the flow will automatically 
reset the silence feature.

The signaling system is designed to work properly 
even if both the eyewash and drench shower are 
used simultaneously. The signaling system will 
continue to operate so long as either the eyewash 
or drench shower is still in use.

The horn will continue to sound and 
beacon/signal light will continue to flash 
as long as the fixture is activated.

See wiring diagram and schematic 
on pages 11-12.

D

Turn on supply power to the signaling 
system . Test the signaling system at 
this time .

Содержание S19-322

Страница 1: ...19 322 Recessed Emergency Signaling System Table of Contents Pre Installation Information 2 3 Components 4 Install Flow Switch 5 Mount Signaling Assembly 6 Connect Signaling Assembly 6 Complete Electr...

Страница 2: ...ginning installation and after installation is complete Test the unit for leaks and adequate water flow Main water supply should be ON at all times unless system is being serviced Provisions shall be...

Страница 3: ...ire a minimum of 30 PSI 0 21MPa flowing pressure Weekly activation must be conducted on all plumbed emergency equipment to ensure a suitable flushing fluid supply is present and any sediment build up...

Страница 4: ...d black and white wires 7 178mm 1 13 16 46mm 13 13 16 351mm NPT Hub Plugged Brass Sensor Body Brass Adapter and Tee 1 2 eyewash or 1 drench shower NPT Inlet and Outlet NEMA 3R Junction Box and Cover E...

Страница 5: ...must be in the vertical position with the water pipe horizontal The water flow must be in the direction marked by the arrow on the flow switch body Use teflon tape or pipe sealant supplied by installe...

Страница 6: ...customer provided 3 Connect Signaling Assembly to Flow Switch Make sure cable is not taut to prevent undue stress to cable and connector A Connect the flow switch to the signaling system by plugging...

Страница 7: ...be empty of water The flow switch is designed to withstand such a water hammer but using the smaller eyewash flow is recommended A Apply power to the alarm branch circuit The alarm should remain in t...

Страница 8: ...ng properly once the power is restored by activating the fixture attached to the signaling station Signaling System Maintenance The Bradley Emergency Signaling System is designed to be virtually maint...

Страница 9: ...nt 2 4 gallons per minute is required Installation error Check all electrical connections including power supply at the quick connect cable from the signal station to the flow switch Horn sounds and s...

Страница 10: ...4 4X 200 6 269 524 1 Cond Cable 6 79 269 2477 1 Ring Lug 1 4 22 16 AWG 80 269 1421 1 Flow Switch 1 1 4 T DPDT 80 269 1522 1 Flow Switch 1 2 T DPDT Item Part No Qty Description 81 269 1902 1 J Box 1 G...

Страница 11: ...JUMPER RED 90 264VAC INPUT FLOATING TERMINAL BLOCK WHT WHT BLK BLK GRN GRN FLEX CABLE CONNECTOR BLK BLU RED UNUSED BLU AUX RED AUX BLK AUX FLOW SWITCH DPDT GROUND WIRE CUT 3 AND ATTACHED TO FLOW SWIT...

Страница 12: ...ELAY COIL NORMALLY OPEN NORMALLY CLOSED LIGHT HORN FLOW SWITCH FLOW SENSOR COMPONENT SOLDERED WIRE LEGEND CONTACT CONTACT INTERNAL JUMPER TERMINAL BLOCK CONNECTION UNSWITCHED 24 VDC OUTPUT S83 346 S83...