background image

3

Installation 

S19-120T

Bradley • 

215-148CP Rev. N; ECN 17-05-039 

7/18/2017

Supplies Required

•  Pipe sealant and teflon tape
•  Piping to 1" NPT water supply inlet
•  Adequate supply pipe supports
•  Minimum 4" (102 mm) drain to 

accommodate 30 gallons (115 liters) per 
minute discharge for shower waste

•  Sign-mounting hardware

Assemble components

1.  Assemble components as shown on page 4.

2.  Apply pipe sealant or tape (by installer) to 

all male-threaded pipe joints.

3.  Bottom edge of showerhead should be 

7'-0" (2134 mm) from the floor.

Connect water supply

NOTICE!  Do not rely on Bradley’s Drench 

Shower to support supply piping.

1.  Connect water supply piping to 1" NPT 

inlet on unit (piping supplied by installer). 
Provide adequate supports (supplied 
by installer) for supply pipe using pipe 
hangers or other means.

2.  Mount the safety sign to the wall using 

sign-mounting hardware supplied by 
installer.

5-1/4"

(133mm)

9"

(229mm)

 Ø 10-3/4"

(273mm)

15-7/8" 

(403mm)

7'-0"

(2134mm) 

Suggested 

Height to 

Floor

24"

(610mm)

3-5/8" 

(92mm)

Отзывы: