14
SNA-Series Tankless Heater
Installation
6/10/2016
Bradley •
215-1815 Rev. E; ECN 16-17-016
SNA-SKID Series System (includes SNA and reverse configuration SNAR)
Maximum Temperature Rise (GPM & °F)
Low Flow Activation (3 gpm)
High Flow Activation (30 gpm)
Models
480/600V
Total kW
Low/High
5 gpm
Δ
T °F
6 gpm
Δ
T °F
10 gpm
Δ
T °F
16 gpm
Δ
T °F
30 gpm
Δ
T °F
40 gpm
Δ
T °F
50 gpm
Δ
T °F
60 gpm
Δ
T °F
70 gpm
Δ
T °F
80 gpm
Δ
T °F
90 gpm
Δ
T °F
100 gpm
Δ
T °F
SNA &
SNAR-1083
(108 kW each)
80/216
109
90
54
34
49
36
29
24
21
18
16
14
SNA &
SNAR-1263
(126 kW each)
94/252
128
106
65
40
57
43
34
28
24
21
19
17
SNA &
SNAR-1443
(144 kW each)
108/288
147
122
79
46
65
49
39
33
28
24
21
19
Maximum Temperature Rise (LPM & °C)
Low Flow Activation (11.4 lpm)
High Flow Activation (113.6 lpm)
Models
480/600V
Total kW
Low/High
18 .9 lpm
Δ
T °C
22 .7 lpm
Δ
T °C
37 .9 lpm
Δ
T °C
60 .6 lpm
Δ
T °C
113 .6 lpm
Δ
T °C
151 .4 lpm
Δ
T °C
189 .3 lpm
Δ
T °C
227 .1 lpm
Δ
T °C
265 lpm
Δ
T °C
302 .8 lpm
Δ
T °C
340 .7 lpm
Δ
T °C
378 .5 lpm
Δ
T °C
SNA &
SNAR-1083
(108 kW each)
80/216
60
50
30
19
27
20
16
13
12
10
9
8
SNA &
SNAR-1263
(126 kW each)
94/252
71
59
36
22
32
24
19
16
13
21
11
9
SNA &
SNAR-1443
(144 kW each)
108/288
82
68
41
26
36
27
22
18
16
13
21
11
Output heating capacity is reduced if these heaters are installed on 415V, 400V or 380V 3-ph .
Contact the factory to supply this information . Satisfactory performance of the heater is dependent upon a specific
flow rate vs temperature rise capability . If the desired temperature is not achieved, please verify the following:
1 . Circuit breaker is on and rated for the maximum power draw .
2 . Heater is drawing the proper current for the supply voltage on all 3 phases .
3 . All 3 phase indicator lights are lit (not flashing) indicating maximum power draw and maximum
amperage is being drawn .
4 . Flow rate and temperature rise requirements are compatible with the heater specifications .
5 . Verify there is no additional supply of cold water entering the line downstream of the heater .