Bradley Thermostatic Mixing Valve (HL 200) with Optional Cabinet
Model S59-3200 Series

Installation and Maintenance Instructions

2

Bradley Corporation • 215-1299 Rev. H; EN 06-909

1/29/07

Bradley Thermostatic Mixing Valve Warranty

Bradley Corporation warrants to commercial and institutional purchasers only each fixture free from defects
in material and workmanship under normal use and service upon the following terms and conditions:

1. We will replace, without charge, any part which proves to be defective within one year from the date of

our invoice at our option, F.O.B. Menomonee Falls, Wisconsin.

2. This warranty does not cover installation or any other labor charge and does not apply to fixtures which

have been damaged by accident, abuse or improper maintenance.

3. The repair or replacement of the defective fixtures as stated in this warranty shall constitute the sole

remedy of the purchaser, and the sole liability of the Bradley Corporation under this warranty. Bradley
Corporation shall not otherwise be liable under any circumstances for incidental, consequential or indirect
charges caused by defects in fixtures or any delay in the repair or replacement thereof.

4. This warranty extends only to commercial and institutional purchases and does not extend to any others,

including consumer, customers of commercial and institutional purchasers.

5. This warranty is in lieu of all other warranties expressed or implied, including any implied warranty of

merchants ability or fitness for a particular purpose, or otherwise.

Pre-Installation Information

Overview

The Model HL 200 Thermostatic Mixing Valve consists of a liquid-filled thermal motor and a
piston control mechanism with positive shut-off of hot when there is a loss of cold water supply
or thermostat failure. The valve body and cap is constructed of bronze with replaceable corrosion-
resistant components, including a stainless steel piston and liner. The valve comes equipped with
integral check stops that have removable strainers. The valve may be mounted in any position. 

The valve controls temperature within ±3° from a low flow to a maximum flow rate for a given
pressure differential. The maximum inlet temperature of the valve is 200°F (93°C), and the
maximum operating pressure is 125 PSI (860 kPA).

Cabinet:

The optional recess-mounted or surface-mounted cabinet is constructed of 18-gauge

stainless steel with a 16-gauge stainless steel door. The cabinet finish is either stainless steel or
baked white enamel. The optional cabinet window is made of Plexiglass.

Supplies recommended for installation:

• lockable shut-off on the outlet if tempered water is supplied to one or more

remote showers

• lockable shut-off on the inlets/supplies
• (6) 3/8" wall anchors and fasteners for surface-mounted cabinet
• (4) 1/4" fasteners (and wall anchors, if necessary) for recess-mounted cabinet
• unions on all connections to facilitate removal of valve

Tools required for temperature adjustment:

• 5/32" Allen key
• blade screwdriver

Содержание HL 200

Страница 1: ...tatic Mixing Valve HL 200 with Optional Cabinet Model S59 3200 Valve only Model S59 3200RE with Recess Mounted Enamel Cabinet Model S59 3200RS with Recess Mounted Stainless Steel Cabinet Model S59 3200SE with Surface Mounted Enamel Cabinet Model S59 3200SS with Surface Mounted Stainless Steel Cabinet Inlet Connections 2 NPT Outlet Connections 2 NPT Temperature Range 90 120 F Maximum Pressure 125 P...

Страница 2: ...ll other warranties expressed or implied including any implied warranty of merchants ability or fitness for a particular purpose or otherwise Pre Installation Information Overview The Model HL 200 Thermostatic Mixing Valve consists of a liquid filled thermal motor and a piston control mechanism with positive shut off of hot when there is a loss of cold water supply or thermostat failure The valve ...

Страница 3: ...rature 4 Pressurize the thermostatic mixing valve and check for pipe leaks 5 Slowly open the outlet valve to fill the piping system 6 Check the temperature when approximately 10 GPM water flow is reached equivalent to four standard showers and adjust if necessary the range of the valve is 90 F 120 F 32 C 49 C To adjust the temperature follow the procedure below remove the slotted cover screw to ex...

Страница 4: ...quired anchors supplied by installer 3 Insert the cabinet into the wall opening and secure into place with four 1 4 wall fasteners supplied by installer 4 Install two anchors and screws through the valve bracket in back of the cabinet into a secure brace supplied by installer or into the wall This must be done to provide adequate support for the valve 5 Install the valve nipples and one half of th...

Страница 5: ... mounting hole locations at the dimensions shown in Figure 4 Install six 3 8 wall anchors supplied by installer 2 Position the cabinet onto the wall and secure into place with six 3 8 wall fasteners supplied by installer 3 Install the valve nipples and one half of the union ball valve using pipe dope or teflon tape Then install the other half of the union ball valve onto the inlet and outlet pipin...

Страница 6: ...page 3 for temperature readjustment 3 As soon as the water reaches the proper temperature turn on the recirculating pump make certain the proper system temperature has been achieved before proceeding 4 Check the water temperature at the return pump If the temperature exceeds the appropriate level by 2 F adjust the temperature high limit switch this will turn off the pump Wait until the return wate...

Страница 7: ...hould be the piston is not moving freely and needs to be cleaned along with the piston liner Clean the piston and liner following the method outlined below remove the control section assembly from the valve body remove the top cap and thermostat unthread the liner from the cap it is glued together the O rings must be removed and a propane torch may be required to melt the glue and loosen the liner...

Страница 8: ... GPM is flowing through the valve 2 Remove the slotted cover screw to expose the set screw 3 Using a 5 32 hex head Allen key turn the set screw counterclockwise to increase the temperature or clockwise to decrease the temperature 4 When the adjustment is complete replace the cover screw and turn off the water Thermostatic Mixing Valve Troubleshooting NOTE Before attempting to troubleshoot the valv...

Страница 9: ...n See Adjust the temperature on page 8 and follow the step by step procedure Problem External leaks in the system Cause Either the NPT joints or O rings have been damaged Solution Replace the O rings where necessary For replacement of O rings contact your Bradley representative and ask for O Ring Seal Kit part number S65 195 Problem Temperature fluctuation Cause Thermostat is slowly failing Soluti...

Страница 10: ...ription 12 1 Thermostat 14 1 O Ring 19 1 O Ring Center Section Kit S65 302 Item Qty Description 2 1 O Ring 3 1 Liner 4 1 Washer 5 1 Screw 6 1 Spring 7 1 Lower Overheat Chamber 8 1 Spring 9 1 Washer 10 1 Piston 11 1 Upper Overheat Chamber 12 1 Thermostat 13 1 Pushrod 14 1 O Ring 15 1 O Ring 16 1 O Ring 17 1 Control Cap 18 4 Bolt 19 1 O Ring 20 1 Top Cap 21 1 Set Screw 22 1 Screw Check Stop Kit S65 ...

Отзывы: