Normal Heating Sequence (cont.) 

7.  Steady state operation. 

During steady state operation, the control monitors: 

Thermostat temperature sensor

-when set point temperature is satisfied, gas 

valve is shut down and blower will post purge for 15 seconds.  Control LED flashes 

a short flash once every 4 seconds (idle) status code. 

Pressure switch / blower temperature switch

-if either switch opens, pilot valve 

and main valve shut down.  The blower continues to run for 30 seconds attempting 

to close the circuit.  The control LED flashes 3 times with 3 second pause. 

Flame sensor

-if flame is lost, pilot & main valves are shut down, blower runs for 15 

seconds.  Control attempts to re-light pilot 4 times.  If unsuccessful, blower is shut 

down and control proceeds to 5 minute lockout.  Control re-attempts to light pilot 

starting at normal heating sequence #2. 

8.  Thermostat satisfies. (Control LED flashing once every 4 seconds). 

9.  Burner off. 

10. Blower post purges (15 seconds). 

Abnormal Operation 

1.  Flammable Vapor Sensor or Simulated Resistive Device Fault: 

a. 

If the resistance is greater than 70,000 Ohms-

the gas control immediately 

turns off all outputs.  Control waits and monitors resistance for 30 seconds.  

If the resistance is greater than 65,000 ohms after 30 seconds, the gas 

control proceeds to verify resistive delay for 2 minutes and flashes 7 times 

then once with a three second pause.  This process is repeated 5 times until 

the control either returns to normal operation or proceeds to flammable vapor 

lockout. 

b. 

If the resistance is below 3000 Ohms-

The gas control immediately turns 

off all outputs and proceeds to flash 8 times then once with three second 

pause.  The status self clears if the resistance returns to normal range for at 

least 15 seconds. 

2.  Temperature Sensor Fault: 

a. 

Temperature sensor detected open circuit

–The gas control immediately 

turns off all outputs and proceeds to flash 8 times then, 3 times with 3 

second pause.  The status self clears if the fault clears for at least 15 

seconds. 

b. 

Thermal well sensor not reading the same temperature within ±5.5°F

 –

The gas control immediately turns off all outputs and proceeds to flash 8  

Содержание ULG2PV50H56*N

Страница 1: ...L Troubleshooting Guide and Instructions for Service To be performed ONLY by qualified service providers Models Covered by This Manual URG1PV40S N URG1PV50S N URG2PV40T N URG2PV50T N URG2PV50H N ULG2P...

Страница 2: ...h Testing Replacement 19 III Blower Testing Replacement 21 IV Blower Temperature Switch Testing Replacement 23 V Gas Control Testing Replacement 25 VI Flammable Vapor Device Testing and Replacement 28...

Страница 3: ...al for more information WARNING FAILURE TO INSTALL AND MAINTAIN A NEW LISTED X TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT FROM EXCESSIVE TEMPE...

Страница 4: ...erifies proper conditions exist for safe and reliable operation If a situation outside of normal operating parameters exists the gas control diagnostic LED will flash a code to positively identify an...

Страница 5: ...l Tools Required for Service Manometer Multi Meter Electronic Probes Thermometer Water Pressure Gage Various Hand Tools A liquid U tube type or a digital magnahelic type can be used This device is use...

Страница 6: ...codes for supply pressure Gas Control ECO Limit Residential 188 F 87 C Commercial 199 F 93 C Residential Temperature Set Point Range 60 F 16 C to 160 F 71 C approximate temperatures Commercial Tempera...

Страница 7: ...oof 1 45 13 7 7 2 1 Through the Roof 2 40 12 2 7 2 1 Through the Roof 3 35 10 7 7 2 1 Through the Roof 4 30 9 2 7 2 1 3 Diameter 7 6 cm Vent Connector Lengths Terminating of Elbows Maximum Straight Le...

Страница 8: ...he Roof 1 55 16 8 7 2 1 Through the Roof 2 50 15 2 7 2 1 Through the Roof 3 45 13 7 7 2 1 4 Diameter 10 2 cm Vent Connector Lengths Terminating of Elbows Maximum Straight Length ft m Minimum Straight...

Страница 9: ...aximum 1 second minimum Post purge 15 Seconds PS Fault Delay failed open close Retry after 2 minutes Soft Lockout Retry after 5 minutes ECO Limit Lockout Indefinite see page 26 Verify Resistive Delay...

Страница 10: ...flashes 2 times with 3 second pause Gas control waits 2 minutes then blower runs for 30 seconds This cycle repeats until safety circuit opens 2 Blower energizes 3 Pressure switch proves blower vent sy...

Страница 11: ...eration 1 Flammable Vapor Sensor or Simulated Resistive Device Fault a If the resistance is greater than 70 000 Ohms the gas control immediately turns off all outputs Control waits and monitors resist...

Страница 12: ...flashes 3 times with 3 second pause The gas control waits 2 minutes before turning on the blower for another 30 seconds to see the circuit close This cycle repeats as long as there is a call for heat...

Страница 13: ...s If the recycle count has been reached the gas control turns off the blower and flashes 6 times then 3 times with 3 second pause The gas control waits 5 minutes before repeating the ignition sequence...

Страница 14: ...ilot tube block or restricted 3 Oxidation build up on pilot electrode 4 Wire damage to pilot assembly or bad connection at gas valve Page 18 Two flash three second pause Pressure switch not working cl...

Страница 15: ...s out of specification 1 4 Page 18 5 Refer to installation manual 6 Page 25 Six four flash three second pause Undesired false pilot flame sensed System auto resets Pilot valve stuck in open position R...

Страница 16: ...lue flame with a minimum of yellow tips Main burner must be free from any debris accumulation that may affect burner operation Burner Cleaning Step 1 Position the gas control power switch to the OFF p...

Страница 17: ...burner screen and burner venturi and remove any loose debris accumulation Inspect burner screen for any openings larger than the normal screen openings Step 13 Remove main burner orifice from feedlin...

Страница 18: ...not be in contact with pilot hood if so carefully adjust electrode to a gap of distance of 3 32 09 from pilot hood Step 6 Visually inspect pilot tubing for kinks or cracks If damage is found replace p...

Страница 19: ...the OFF position Step 2 Remove the three screws Phillips screw driver from control access cover on blower assembly and remove cover see photo 1 Step 3 Carefully remove pressure switch from blower hous...

Страница 20: ...Step 4 Disconnect tubing from pressure switch see photo 5 Step 5 Disconnect yellow wires from pressure switch see photo 6 Step 6 Reconnect wires from step 5 to new pressure switch Step 7 Reconnect tub...

Страница 21: ...wer switch to ON position and adjust control to call for heat Step 2 Remove the three screws Phillip s screw driver from control access cover on blower assembly and remove cover see photo 7 WARNING 11...

Страница 22: ...r with gasket from water heater Blower Installation Step 8 Clean any debris from jacket head of water heater Step 9 Set new blower with gasket in place using locating pins on blower flange to line up...

Страница 23: ...on gas control to the OFF position Step 2 Remove the three screws Phillip s screw driver from control access cover on blower and remove cover see photo 14 Step 3 Locate blower temperature switch see p...

Страница 24: ...tep 5 With an appropriate tool such as side cutters snip the retaining lug from the blower housing to allow removal of temperature switch see photo 18 Step 6 Remove switch from blower housing Step 7 I...

Страница 25: ...3 Connect manometer to pressure tap Step 4 Follow instructions located on the lighting instructions label and proceed to light the main burner and observe manometer reading Step 5 Proper operating ra...

Страница 26: ...perature Inside Tank Step 1 Position gas control power switch to OFF position Step 2 Draw approximately 4 gallons of water from drain valve into a container and discard Draw an additional gallon and i...

Страница 27: ...ontrol Step 7 Disconnect pilot tube from gas control and move away from gas control Step 8 Remove gas control from water heater by rotating counter clockwise DO NOT use a wrench on the gas control bod...

Страница 28: ...sing a multi meter set to the ohms setting check resistance of flammable vapor sensor Resistance must be within 3 000 ohms and 48 000 ohms If outside of this range replace Flammable Vapor Sensor CAUTI...

Страница 29: ...oltage Trace NOTE This procedure assumes a cool tank Remove three screws Phillips screw driver from control access cover on blower and remove cover see photo 21 WARNING 115 volt potential exposure Use...

Страница 30: ...uit Trace Step 1 Verify 115 VAC and proper polarity at wall outlet Step 2 With unit plugged in and control power switch in the ON position verify LED status WARNING 115 volt potential exposure Use cau...

Страница 31: ...t nipple dip tube Inlet nipple diptube should be free of cracks and any blockage Hydrojet slots should be open and free of any blockage Any damage such as cracks restriction due to deformation or unin...

Страница 32: ...p 5 Visually inspect outlet nipple anode Outlet nipple anode should show signs of depletion this is normal If depletion is of the original anode diameter approximately diameter replacement is recommen...

Страница 33: ...r deterioration and any missing restrictors Clean any scale or debris build up Replace with new baffle as necessary Step 8 Reinstall baffle into flue tube Be sure hanger tabs are inserted into notch l...

Страница 34: ...ve the connectors attached to the resettable thermal switch on the manifold mount Step 7 Remove the flammable vapor sensor from the clip by pushing down the tab to open the clip Step 8 Remove inner do...

Страница 35: ...tion chamber surface before installing the inner door gasket assembly Step 2 Place the left side inner door into position first Using the hex drive screws secure left side inner door in place DO NOT O...

Страница 36: ...tegrity around combustion opening Secure right side inner door using hex drive screws DO NOT OVER TIGHTEN SCREWS Verify both left and right sides of inner door are properly positioned and sealed again...

Страница 37: ...the red colored button located at the center of the switch The overheating condition must be determined prior to putting the water heater back into service Probable Cause for Resettable Thermal Switc...

Страница 38: ...n place Be sure contact surface of resettable thermal switch and manifold mount are free of any debris Secure resettable thermal switch into place using screws from step 6 DO NOT OVER TIGHTEN SCREWS S...

Страница 39: ...y scale or other debris accumulation Using a soft brush clear jacket openings from any dirt dust restrictions or other obstructions Step 6 Remove any debris from burner assembly per the burner cleanin...

Страница 40: ...ent terminals in relation to each other and terminals from other appliances can have an effect on the potential for blockage due to ice or snow See the installation instructions for recommended positi...

Страница 41: ...T P Valve 16 NPT Plug 17 Burner Assy 18 Pilot Assembly 19 Pilot Orifice 20 Pilot Assy 21 Main Burner 22 Resettable Thermal Switch 23 Main Burner Mount 24 FV sensor mount plate 25 Main Burner Orifice 2...

Страница 42: ......

Страница 43: ......

Страница 44: ......

Отзывы: