25

 

Gas Connections 

 

 

The gas supply lines must meet all requirements of the National Fuel Gas Code (ANSI 
Z223.1-Latest Edition), or in Canada CAN/CGA B149.1 Natural Gas Installation Code 
(Latest Edition) or CAN/CGA B149.2 Propane Installation Code (Latest Edition). 

 

The minimum permissible gas supply pressure for the purpose of input adjustment is 
one (1.0) inch 

(0.25 kPa) 

water column above the operating manifold pressure. See the 

rating plate and gas valve for the manifold pressure and gas type. The maximum 
permissible gas supply pressure is fourteen (14.0) inches 

(3.5 kPa)

 water column for 

natural gas and liquefied petroleum gases/propane gas. 

 

1.  Connect this water heater only to the type of gas (Natural or Propane gas) as 

shown on the rating plate. Use clean black iron pipe or equivalent material 
approved by local codes and ordinances. (Dirt and scale from the pipe can enter 
the gas valve and cause it to malfunction). The inlet gas line must have a minimum 
length of three (3) inches 

(7.6 cm)

 drip leg 

(sediment trap) 

installed as close to the 

water heater’s gas valve as possible. A ground joint union must be installed as 
close to the water heater as possible in the gas supply line feeding the water heater 
to permit servicing of the water heater. Compounds used on the threaded joints of 
the gas piping must be resistant to the action of liquefied petroleum gases/propane 
gas. DO NOT apply pipe dope to the gas valve inlet and make certain that no pipe 
dope has become lodged in the inlet screen of the gas valve. Extreme care must be 
taken to ensure no pipe dope enters the gas valve. Avoid excessive torque when 
tightening the gas supply line to the gas valve. Excessive torque may result in 
cracking of the gas valve housing and could create a gas leak. The suggested 
maximum torque is 31.5 ft. lbs. 

(4.4 kg-m).

  

 

2. 

This water heater and its gas connection must be leak tested before placing the 
water heater in operation. Check for gas leaks with a soap and water solution and a 
brush or a commercial leak detector fluid. 

NEVER USE A MATCH OR OPEN 

FLAME FOR TESTING! 

 
 

 

WARNING 

Prior to connecting the gas supply line to a gas fired water heater, ensure that 
the gas supply line does not have moisture/water or dirt/scale inside the gas 
line. Commonly this check is done at the lowest point in the gas distribution 
system prior to gas burning appliances.

 

WARNING 

The manufacturer of this water heater will not be liable for any damage or injury 
caused as a result of a cracked gas inlet as a result of excessive torque. 

 

CAUTION 

The water heater and individual shutoff valve must be disconnected from the 
gas supply piping system during any pressure testing of the system at test 
pressures in excess of 1/2 psi 

(3.5 kPa).

 The water heater must be isolated from 

the gas supply piping system by closing its manual shutoff valve during any 
pressure testing of the gas supply system at test pressures equal to or less than 
1/2 psi 

(3.5 kPa). 

The supply line must be capped when not connected to the 

water heater. 

Содержание TTW URG2PV50H6N

Страница 1: ...one Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas...

Страница 2: ...the event of improper usage or storage of gasoline or other flammable materials in the location where the water heater is installed the technology will resist ignition of the flammable vapors outside...

Страница 3: ...aration and Joining 18 Combustion Air Supply 20 Water Connections 22 Gas Connections 25 Electrical Connections 26 Wiring Diagram 27 GENERAL OPERATION 28 Lighting and Shutdown Instructions 29 Thermosta...

Страница 4: ...r You should contact a qualified service technician to inspect the appliance and to replace any part of the control system including the combination gas control which has been submerged in water See t...

Страница 5: ...lammable vapors are likely to be present Water heaters in residential garages must be installed and located or protected to avoid physical damage For other installations refer to local codes In the ab...

Страница 6: ...h little or no odor to reveal their presence NOTE DAMAGE TO THE WATER HEATER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY DO NOT OPERATE THE WATER HEATER IF EXPOSURE HAS OR WI...

Страница 7: ...uate drain The piping must be at least 3 4 inch 1 9 cm in diameter and pitched for proper drainage It is recommended that a minimum clearance of four 4 inches 10 2 cm be provided on the side of the wa...

Страница 8: ...ast three 3 inches 7 6 cm in any direction or if the appliance is to be installed in an alcove or closet the entire floor must be covered by the panel The minimum clearances to combustibles for this w...

Страница 9: ...t 2 13 m M Clearance under a veranda porch deck or balcony 12 inches 30 cm b 1 In accordance with the current CAN CGA B149 Installation Codes 2 In accordance with the current ANSI Z223 1 Latest editio...

Страница 10: ...allow noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the water heater s efficiency The acceptance of the venting system is dependent upon...

Страница 11: ...he vent pipe can be installed with a downward slope not less than 1 8 3 cm and away from the blower Approved Venting Materials For installations in the US only PVC DWV ASTM D 2665 PVC Sch 40 80 120 AS...

Страница 12: ...ing length and number of elbows are kept to the minimum distance necessary to reach the outside If the installation requires venting lengths that exceed the lengths listed for 3 7 6 cm vent pipe in Ta...

Страница 13: ...15 4 6 Through the Roof 2 170 51 8 15 4 6 Through the Roof 3 165 50 3 15 4 6 Through the Roof 4 160 48 8 15 4 6 NOTE When using 4 10 2 cm vent pipe use a 4 10 1 cm to 3 7 6 cm reducer and exit the bu...

Страница 14: ...90 vent terminal provided with the water heater to the vent connector The distance between the edges of the 90 vent terminal and the exterior wall see Figure 3 must be 1 in 2 5 cm Use the proper cemen...

Страница 15: ...l codes and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code latest edition Figure 4 NOTE For installations requiring both horizontal and vertical runs the fo...

Страница 16: ...ight greater than or equal to 12 30 5 cm above the ground or anticipated snow level the installation must be modified as shown below see Figure 5 Refer to Table 3 for maximum venting lengths using 3 7...

Страница 17: ...TIONS Terminating Reduce 4 to 3 Reduce 10 1 cm to 7 6 cm of Elbows Max straight Length ft m Min straight Length ft m 48 gal 2 90 Elbows with 1 90 Elbow 1 160 48 8 10 3 1 2 90 Elbows with 1 90 Elbow 2...

Страница 18: ...applicator tools to ensure proper preparation and joining of pipe and fittings a Cutting Tools i A square cut must be achieved with a miter box saw or pipe cutter to ensure a proper mating with the f...

Страница 19: ...at around the end of the pipe 4 Joining a Joints should be made immediately after cement is applied b After fully inserting pipe into fitting socket hold joint together for about 15 to 20 seconds c Re...

Страница 20: ...le weather stripping heavily insulated caulked vapor barrier etc additional air may need to be provided using the methods described under CONFINED SPACES All Air From Outdoors or Specially Engineered...

Страница 21: ...ly or by ducts with the outdoors or spaces crawl or attic that freely communicate with the outdoors 1 When directly communicating with the outdoors each opening must have a minimum free area of 1 squa...

Страница 22: ...on DO NOT operate this water heater in a closed system without provisions for controlling thermal expansion Your water supplier or local plumbing inspector should be contacted on how to control this s...

Страница 23: ...relief valve into the opening provided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with a combination temperature and pressure relief valve Ve...

Страница 24: ...scalds Water temperature over 125 F Feel water before bathing or before setting temperature are available showering Temperature limiting valves Review this instruction manual at water heater scalded A...

Страница 25: ...to the gas valve inlet and make certain that no pipe dope has become lodged in the inlet screen of the gas valve Extreme care must be taken to ensure no pipe dope enters the gas valve Avoid excessive...

Страница 26: ...water heater and use the flexible cord provided Do not plug the line cord into a receptacle that can have its power supply interrupted by a switch that is used to turn on and off lights If wiring in...

Страница 27: ...27 Wiring Diagram Figure 6...

Страница 28: ...ter heater 3 Close the cold water supply shut off valve 4 Open the drain valve on the water heater by turning the stem counter clockwise The drain valve has threads on the end that will allow the conn...

Страница 29: ...29 Lighting and Shutdown instructions...

Страница 30: ...tleship Grey faceplate is approximately 180 F maximum set point Figure 7 DANGER Hotter water increases the risk of scald injury Scalding may occur within five 5 seconds at a temperature setting of 140...

Страница 31: ...n adjustable air shutter See Figure 8 At periodic intervals a visual check of the main burner and pilot flames should be made to determine if they are burning properly The main burner flame should lig...

Страница 32: ...burner flames to determine that they are burning properly See Burner Flame Check If sooting or other burner anomalies are evident shut down the water heater by turning off the gas per the instructions...

Страница 33: ...omponents which are not exact duplicates of Thoroughly inspect and replace as needed burner inner door gasket and or sight window gasket any time burner inner door is removed or disturbed Replace wate...

Страница 34: ...installed to extend tank life The anode rod should be inspected periodically every 2 years and replaced when necessary to prolong tank life Water conditions in your area will influence the time inter...

Страница 35: ...7 517 7 409 925 7 458 341 7 559 293 7 621 238 7 634 976 7 650 859 7 665 210 7 665 211 7 699 026 7 866 168 7 900 589 7 971 560 7 992 526 8 082 888 8 146 772 Other U S and Foreign patent applications pe...

Страница 36: ...use Pressure switch not working closed position 1 Pressure switch tubing kinked or blocked 2 Blocked pressure tap on switch 3 Faulty pressure switch Three flashes three second pause Pressure switch or...

Страница 37: ...ired false pilot flame sensed System auto resets Pilot valve stuck in open position Seven flashes three second pause Flammable vapor sensor fault detected see warning label 1 Flammable vapor present 2...

Страница 38: ...tion air through the combustion system 5 The pressure switch closes 6 The control senses the closed pressure switch and starts the ignition process by providing a spark at the pilot electrode and allo...

Страница 39: ...Main Burner Orifice 5 Honeywell Gas Control Valve 18 Gas Feedline 6 Drain Valve 19 Flammable Vapors Sensor 7 Fiberglass Insulation not shown 20 Sensor Harness 8 Foam Insulation not shown 21 Inner Door...

Страница 40: ...sed for boiler treatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a...