14
Venting continued-
THROUGH THE WALL VENTING: (HORIZONTAL VENTING)
Cut a 3 1/2 in.
(8.9 cm)
diameter hole in the wall at the point where the vent
connector is going to pass through the wall. Use the proper cement to secure
the 90° vent terminal provided with the water heater to the vent connector. The
distance between the edges of the 90° vent terminal and the exterior wall (see
Figure 3) must be 1 in.
(2.5 cm)
. Use the proper cement and assembly
procedures to secure the vent connector joints between the terminal and the
blower outlet. Provide support brackets for every 5 feet
(1.5 m)
of horizontal
vent.
4” VENT INSTALLATION
3” VENT INSTALLATION
Figure 3