How to Use this Manual 

This manual serves as a supplement to the Defender Atmospheric service manual, p/n

238-44943-00.  Please refer to the Defender Atmospheric service manual for all features on 

this water heater that are consistent with a Defender (standard) Atmospheric water heater. 

It is intended for this manual to be used by qualified service personnel for the primary purpose

of troubleshooting and repair of the Bradford White Programmable Efficiency water heaters. 

Understanding the sequence of operation section of this manual will contribute greatly to

troubleshooting the water heater. 

The Honeywell WV4460E Electronic Gas Control will display error codes in the event of

abnormal operation. Diagnostic codes are listed in the troubleshooting chart beginning on page 

13 of this service manual. The troubleshooting chart will also indicate the probable cause for 

the diagnostic code and direct the service professional to a service procedure to properly 

diagnose the abnormal operation. 

Contact the Bradford White technical support group immediately if diagnosis cannot be made

using the methods described in this service manual. 

Tools Required for Service

Manometer:

 A liquid “U” tube type or a digital (magna-helic) type can be used. This device is 

used to measure gas and/or air pressure and vacuum. 

Multi-Meter: 

A digital type is strongly recommended. This device is used to measure electrical

values. The meter you select must have the capability to measure volts AC, volts DC, amps, 

micro-amps and ohms. 

Electronic Probes: 

In some cases, standard multi-meter probes will damage or simply not be 

effective to obtain certain voltage and ohm reading. It will be necessary to have special 

electronic “pin” type multi-meter probes.  These probes are available at most electronic 

wholesale outlets.  

Thermometer:

Used to measure water temperature. An accurate thermometer is 

recommended. 

Water Pressure Gage:

 Used to measure water supply pressure. Also used to determine tank 

pressure by adapting to the drain valve of the heater. 

Gas Control Service Tool:

 BWC p/n 239-45991-00. A specialized tool designed to remove

the gas control from the thermal well.  Available from your Bradford White parts supplier and is 

supplied with replacement gas controls. 

Various Hand Tools:

 Pipe wrench, channel locks, open end wrenches (3/8", 7/16", 1/2"), 12" 

crescent wrench, Allen wrench set, screw drivers (common & Phillips), 1/4" nut driver, pliers

(common & needle nose), socket set, side cutters, wire cutters, wire strippers, wire crimpers,

torpedo level, small shop vac, step ladder, flashlight, and 5 gallon pail. 

How to Use this Manual 

6

Содержание PE2XR504T Series

Страница 1: ...SUPPLEMENT Troubleshooting Guide and Instructions for Service To be performed ONLY by qualified service providers Models Covered by This Manual PE4403S F BN SX PE440T F BN SX PE4503 F BN SX PE2XR504T...

Страница 2: ...t Maintenance _________________________________________ 19 Pilot Inspection Testing and Replacement Thermal Well Testing ______________________________________ 21 Determine Water Temperature Inside Ta...

Страница 3: ...to life and property and will nullify the warranty If sweat fittings are to be used DO NOT apply heat to the nipples on top of the water heater Sweat the tubing to the adapter before fitting the adapt...

Страница 4: ...uefied petroleum gases propane gas and natural gas have an odorant added by the gas supplier that aids in the detection of the gas Most people recognize this odor as a sulfur or rotten egg smell Other...

Страница 5: ...rmal operating parameters exists the gas control diagnostic LED will flash a code to positively identify an operational issue This service manual is designed to facilitate problem diagnosis and enhanc...

Страница 6: ...tube type or a digital magna helic type can be used This device is used to measure gas and or air pressure and vacuum Multi Meter A digital type is strongly recommended This device is used to measure...

Страница 7: ...for Natural Gas 11 w c for Propane 14 w c maximum for Natural Gas Propane Approved Vent Materials Single or Double Wall Metal Vent Pipe Minimum Clearance for Servicing 18 from top 24 from front 4 from...

Страница 8: ...out Indefinite See page 11 to reset Verify Resistive Delay Retry after 2 minutes repeats 5 times Simulated Resistive Load Lockout Indefinite cycle power to reset Hardware Error Lockout Indefinite self...

Страница 9: ...a 3 second pause The gas control waits 2 minutes Then the control cuts power to the relay This cycle repeats until the safety circuit opens 2 Relay Energized 3 Safety Circuit Check If the safety circu...

Страница 10: ...out The gas control re attempts to light the pilot starting at Normal Heating Sequence 2 8 Thermostat Satisfies Gas control LED flashes once every 4 seconds 9 Burner Off 10 Relay De energized 15 secon...

Страница 11: ...ds before returning to desired temperature setting 3 Safety Circuit Fault A Safety Circuit Failed to Close The gas control proceeds to flash 3 times with a 3 second pause The gas control waits 5 minut...

Страница 12: ...3 second pause The gas control waits 5 minutes before repeating the ignition sequence B Flame Sensed Out of Sequence The gas control only looks for pilot flame when the relay is energized If flame is...

Страница 13: ...rking Faulty relay 1 Verify cord sets are fully plugged in 2 See Relay Replacement on page 28 Three flashes three second pause Relay not working Faulty relay 1 Verify cord sets are fully plugged in 2...

Страница 14: ...ammable vapor sensor exposed to excessive moisture 3 Flammable vapor sensor exposed to extreme ambient temperature 4 Resettable thermal switch open See Flammable Vapor Sensor Testing on page 27 Eight...

Страница 15: ...ensor out of specification x 63 Ignition successful but flame lost during run cycle Soft lockout x 64 Internal gas valve fault detected x 85 Soft Lockout due to maximum number of recycles exceeded las...

Страница 16: ...cond pause Leak sensor malfunction 1 Leak Sensor resistor removed 2 Leak Sensor improperly connected to Accessory Module Amber Five flashes and three second pause Gas control missing not connected 1 W...

Страница 17: ...rner should light smoothly from the pilot and burn with a blue flame with a minimum of yellow tips Steel burner models self adjust air to gas ratio mixture and do not have an adjustable air shutter Th...

Страница 18: ...from the combustion chamber Step 9 Thoroughly inspect the burner surface area and burner port area and remove any loose debris Step 10 Unscrew the burner from the main burner orifice Step 11 Remove th...

Страница 19: ...and Replacement Note The Pilot Maintenance section replaces page 13 in the Defender Atmospheric service manual p n 238 44943 00 Step 1 Move the gas control power switch to the OFF position Step 2 Unp...

Страница 20: ...amber Step 9 Remove the pilot assembly from the main feedline using a 1 4 nut driver Step 10 Visually inspect the spark igniter flame sense wire for damage Replace the pilot assembly if damage is foun...

Страница 21: ...of the pilot assembly using a 7 16 wrench b Remove the pilot tube and pilot orifice c Inspect the pilot tubing and pilot orifice for blockages Clean or replace as necessary Step 16 Re assemble the pil...

Страница 22: ...ter Temperature Inside the Tank procedure If the values are correct replace the gas control otherwise replace the thermal well Determine Water Temperature Inside Tank Note The Determine Tank Temperatu...

Страница 23: ...22771 22163 21573 21000 20445 50 19906 19383 18876 18383 17905 17440 16990 16553 16128 15715 60 15314 14925 14548 14180 13823 13477 13140 12812 12494 12185 70 11884 11592 11308 11032 10763 10502 1024...

Страница 24: ...Turn off the gas supply to the water heater and disconnect the gas piping from the gas control Step 4 Disconnect the pilot tube using a 7 16 wrench and the main burner feedline with a 3 4 wrench from...

Страница 25: ...s piping from the gas control Step 4 Disconnect the pilot tube using a 7 16 wrench and the main burner feedline with a 3 4 wrench from the gas control Step 5 Disconnect the wire harnesses and spark ig...

Страница 26: ...ow for proper gas control installation Tighten the thermal well using a 1 5 16 wrench Step 2 Route the wire leads back into relief opening Step 3 Align the slots located on the thermal well flange wit...

Страница 27: ...nstallation and Operation manual Flammable Vapor Sensor Testing Note The Flammable Vapor Sensor Testing section is in addition to the Defender Atmospheric service manual p n 238 44943 00 Step 1 Move t...

Страница 28: ...ddition to the Defender Atmospheric service manual p n 238 44943 00 Step 1 Verify 120VAC and proper polarity are at the wall outlet Step 2 With the water heater plugged in and the gas control power sw...

Страница 29: ...nect the 4 wires attached to the relay Step 6 Remove the relay from its socket Step 7 Install the new relay p n 233 47642 00 Step 8 Re connect the wires removed in Step 5 to their proper locations Ste...

Страница 30: ..._______________________________________________________ ____________________________________________________________ ____________________________________________________________ ______________________...

Страница 31: ...door 3 Jacket head 17 Accessory Module 4 Jacket 18 Junction box wire harness 5 Heat trap outlet 19 Thermal well 6 Anode Outlet Device 20 Gas control 7 Heat trap inlet 21 FV sensor RTS wire harness 8 B...

Страница 32: ...Email parts bradfordwhite com techserv bradfordwhite com www bradfordwhite com...

Отзывы: