Bradford White M-1-40S6BN Скачать руководство пользователя страница 9

 

 

9

 

Venting continued-

 

  

Canadian 

Installations

1

 

US Installations

2

 

A= 

Clearance above grade, veranda, 
porch, deck or balcony 

12 inches (30 

cm) 

12 inches 

(30 cm) 

B= 

Clearance to window or door that may 
be opened 

12 inches (30 

cm) 

4 feet (1.2 m) below or 

to the side of opening; 

12 inches (30 cm) above 

opening 

C= 

Clearance to permanently closed 
window 

*b *b 

D= 

Vertical clearance to ventilated soffit 
located above the terminal within a 
horizontal distance of 2 feet (61 cm) 
from the center line of the terminal 

*b *b 

E= 

Clearance to unventilated soffit 

*b 

*b 

F= 

Clearance to outside corner 

*b 

*b 

G= 

Clearance to inside corner 

36 inches 
(91 cm)*a 

36 inches 
(91 cm)*a 

H= 

Clearance to each side of center line 
extended above meter/regulator 
assembly 

3 feet (91 cm) 

within a height 

15 feet (4.6 m) 

above the 

meter/regulator 

assembly 

*b 

I= 

Clearance to service regulator vent 
outlet or oil tank vent 

36 inches 

(91 cm) 

*b 

J= 

Clearance to non-mechanical air 
supply inlet to building or the 
combustion air inlet to any other 
appliance 

12 inches (30 

cm) 

4 feet (1.2m) below or to 

side of opening; 12 

inches (30 cm) above 

opening. 

K= 

Clearance to a mechanical air supply 
inlet 

6 feet 

(1.83 m) 

3 feet (91 cm) above if 

within 10 feet 

horizontally 

L= 

Clearance above paved sidewalk or 
paved driveway located on public 
property 

7 feet 

(2.13 m)† 

7 feet 

(2.13 m)† 

M= 

Clearance under a veranda, porch, 
deck, or balcony 

12 inches (30 

cm) ‡ 

*b 

In accordance with the current CAN/CGA-B149 

Installation Codes

In accordance with the current ANSI Z223.1-(Latest edition)/NFPA 54 

National Fuel Gas Code

† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single-
family dwellings and serves both dwellings. 
‡ Permitted only if a veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the 
floor. 
*a) A minimum clearance value determined by testing in accordance with section 2.20. 
*b) “Clearance in accordance with local installation codes and the requirements of the gas supplier”.

 

 

The vent system must terminate so that proper clearances are maintained as cited 
in local codes or the latest edition of the National Fuel Gas Code, ANSI 
Z223.1.73.4e and 7.8a, b as follows: 

1.  Do not terminate near soffit vents or crawl space or other area where condensate or 

vapor could create a nuisance or hazard or cause property damage. 

2.  Do not terminate the exhaust vent terminal where condensate or vapor could cause 

damage or could be detrimental to the operation of regulators, relief valves, or other 
equipment. 

3.  Do not terminate the exhaust vent terminal over public area or walkways where 

condensate or vapor can cause nuisance or hazard. 

4.  The vent shall terminate a minimum of 12” (25.4 cm) above expected snowfall level 

to prevent blockage of vent termination. 

Internet Version for Reference Only

Содержание M-1-40S6BN

Страница 1: ...s supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier For your...

Страница 2: ...roper usage or storage of gasoline or other flammable materials in the location where the water heater is installed the technology will resist ignition of the flammable vapors outside the confines of...

Страница 3: ...Vent pipe preparation and joining 23 Combustion Air Supply 25 Water Connections 27 Gas Connections 30 Electrical Connections 31 Wiring Diagram 32 GENERAL OPERATION 33 Lighting and Shutdown Instructio...

Страница 4: ...his appliance if any external part to the tank has been submerged in water You should contact a qualified service technician to inspect the appliance and to replace any part of the control system incl...

Страница 5: ...1 Natural Gas Installation Code Latest Edition or CAN CGA B149 2 Propane Installation Code Latest Edition The location of this water heater is of the utmost importance Before installing this water he...

Страница 6: ...WATER HEATER IF EXPOSURE HAS OR WILL OCCUR DO NOT STORE ANY POTENTIALLY CORROSIVE COMPOUNDS IN THE VICINITY OF THE WATER HEATER WARNING Liquefied petroleum gases propane gas are heavier than air and w...

Страница 7: ...cm in diameter and pitched for proper drainage It is recommended that a minimum clearance of four 4 inches 10 2 cm be provided on the side of the water heater for servicing and maintenance of the com...

Страница 8: ...st be covered by the panel The minimum clearances to combustibles for this water heater are zero 0 inch 0 cm from the sides and rear five 5 inches 12 7 cm from the front of the jacket zero 0 inch 0 cm...

Страница 9: ...2 13 m M Clearance under a veranda porch deck or balcony 12 inches 30 cm b 1 In accordance with the current CAN CGA B149 Installation Codes 2 In accordance with the current ANSI Z223 1 Latest edition...

Страница 10: ...bient temperature and humidity of venting space vent distance and slope and product usage In order to effectively control condensate from adversely affecting the mechanical components of the water hea...

Страница 11: ...vent pipe for the vent connector Table 2 lists the venting distances allowed with 4 10 2 cm diameter vent pipe When venting with 4 10 2 cm vent pipe use a 4 10 2 cm to 3 7 6 cm reducer to exit through...

Страница 12: ...the Roof 2 80 24 4 15 4 6 Through the Roof 3 75 22 9 15 4 6 Through the Roof 4 70 21 3 15 4 6 NOTE When using 4 10 2 cm vent pipe use a 4 10 1 cm to 3 7 6 cm reducer and exit the building wall with 3...

Страница 13: ...nal provided with the water heater to the vent connector The distance between the edge of the 90 vent terminal and the exterior wall see Figure 3 must be 1 in 2 5 cm Use the proper cement and assembly...

Страница 14: ...The National Fuel Gas Code ANSI Z223 1 Latest Edition or CGA CAN B149 Installation Code latest edition Figure 4 NOTE For installations requiring both horizontal and vertical runs the following rule m...

Страница 15: ...an or equal to 12 30 5 cm above the ground or anticipated snow level the installation must be modified as shown below see Figure 5 Refer to Table 3 for maximum venting lengths using 3 7 6 cm vent pipe...

Страница 16: ...straight Length ft m Terminating Reduce 4 to 3 Reduce 10 1 cm to 7 6 cm of Elbows 48 65 gal Min straight Length ft m 2 90 Elbows with 1 90 Elbow 1 85 25 9 10 3 1 2 90 Elbows with 1 90 Elbow 2 80 24 4...

Страница 17: ...distances allowed with 3 7 6 cm diameter vent pipe When venting with 3 7 6 cm vent pipe use a 3 7 6 cm to 2 5 1 cm reducer to exit through the building wall with 2 5 1 cm vent pipe Use the 2 5 1 cm v...

Страница 18: ...Through the Roof 0 120 36 6 15 4 6 Through the Roof 1 115 35 15 4 6 Through the Roof 2 110 33 5 15 4 6 Through the Roof 3 105 32 0 15 4 6 Through the Roof 4 100 30 5 15 4 6 NOTE When using 3 7 6 cm v...

Страница 19: ...dge of the 45 vent terminal and the exterior wall see Figure 7 must be at least 1 in 2 5 cm Use the proper cement and assembly procedures to secure the vent connector joints between the terminal and t...

Страница 20: ...s through the roof and ceiling and install the vent connector as shown in Figure 8 Make sure that the installation meets the local codes and or The National Fuel Gas Code ANSI Z223 1 Latest Edition or...

Страница 21: ...gure 9 Refer to Table 7 for maximum venting lengths using 2 5 1 cm vent pipe or Table 8 for maximum lengths using 3 7 6 cm vent pipe 2 VENT INSTALLATION 3 VENT INSTALLATION Figure 9 NOTE For installat...

Страница 22: ...ting Reduce 3 to 2 Reduce 7 6 cm to 5 1 cm of Elbows Maximum Length ft m Minimum Length ft m 2 90 Elbows with Vent Terminal 1 115 35 1 10 3 1 2 90 Elbows with Vent Terminal 2 110 33 5 10 3 1 2 90 Elbo...

Страница 23: ...fittings a Cutting Tools i A square cut must be achieved with a miter box saw or pipe cutter to ensure a proper mating with the female If a pipe cutter is used the burr created at the outer edge of t...

Страница 24: ...of the pipe 4 Joining a Joints should be made immediately after cement is applied b After fully inserting pipe into fitting socket hold joint together for about 15 to 20 seconds c Remove excess cement...

Страница 25: ...avily insulated caulked vapor barrier etc additional air may need to be provided using the methods described under CONFINED SPACES All Air From Outdoors or Specially Engineered Installations Confined...

Страница 26: ...the outdoors or spaces crawl or attic that freely communicate with the outdoors 1 When directly communicating with the outdoors each opening must have a minimum free area of 1 square inch per 4000 BT...

Страница 27: ...this water heater in a closed system without provisions for controlling thermal expansion Your water supplier or local plumbing inspector should be contacted on how to control this situation After ins...

Страница 28: ...rovided and marked for this purpose on the water heater Note Some models may already be equipped or supplied with a combination temperature and pressure relief valve Verify that the combination temper...

Страница 29: ...hot water in branch supply lines Such valves are available from the manufacturer of this water heater or a local plumbing supplier Please consult with a plumbing professional WARNING Hydrogen gas can...

Страница 30: ...the gas valve inlet and make certain that no pipe dope has become lodged in the inlet screen of the gas valve Extreme care must be taken to ensure no pipe dope enters the gas valve Avoid excessive tor...

Страница 31: ...used to turn on and off lights If wiring in conduit is required cut the flexible line cord flush with the bushing Remove the junction box cover and pull the pressure switch outside of the junction bo...

Страница 32: ...32 Electrical Connections Figure 10 continued A C B Y Figure 10 Internet Version for Reference Only...

Страница 33: ...the cold water supply shut off valve 4 Open the drain valve on the water heater by turning the stem counter clockwise The drain valve has threads on the end that will allow the connection of a standa...

Страница 34: ...liance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under...

Страница 35: ...prevent overheating Should overheating occur turn off the electrical supply to the water heater and contact a qualified service technician Thermostat Adjustment The thermostat dial is adjusted to it...

Страница 36: ...lame becomes blue On 75 gallon models fired on LPG or propane adjust the air shutter as described above until the yellow flame is minimized note the burner flame may contain a mixture of yellow and bl...

Страница 37: ...that they are burning properly See Burner Flame Check section on page 36 If sooting or other burner anomalies are evident shut down the water heater by turning off the gas per the instructions listed...

Страница 38: ...e not exact duplicates of Thoroughly inspect and replace as needed burner inner door gasket and or sight window gasket any time burner inner door is removed or disturbed Replace water heater if involv...

Страница 39: ...tlet nipple has been installed to extend tank life The anode rod should be inspected periodically every 2 years and replaced when necessary to prolong tank life Water conditions in your area will infl...

Страница 40: ...er Phone No CAUTION FOR YOUR SAFETY DO NOT ATTEMPT REPAIR OF COMBINATION GAS CONTROL BURNERS OR GAS PIPING REFER REPAIRS TO A QUALIFIED SERVICE TECHNICIAN Manufactured under one or more of the followi...

Страница 41: ...re below set point of thermostat 1 Unstable pilot 2 Pilot tube block or restricted 3 Oxidation build up on pilot electrode 4 Wire damage to pilot assembly or bad connection at gas valve 1 Pressure swi...

Страница 42: ...pause Soft lockout Pilot flame extinguished System resets after 5 minutes 1 Unstable pilot 2 Pilot tube blocked or restricted 3 Oxidation build up on pilot electrode 4 Wire damage to pilot assembly o...

Страница 43: ...lue Baffle 16 Cast Iron Burner 5 Honeywell Gas Control Valve 17 Main Burner Orifice 6 Drain Valve 18 Gas Feedline 7 Fiberglass Insulation not shown 19 Flammable Vapors Sensor 8 Foam Insulation not sho...

Страница 44: ...reatment must not be introduced into potable water used for space heating 3 This water heater must not be connected to an existing heating system or component s previously used with a non potable wate...

Отзывы: