Condensing PDV Series
6
Specifications
Power Supply
Dedicated 115 VAC, 60 Hz, 15A
Gas Supply Pipe Minimum 1/2” NPT (schedule 40 black iron pipe recommended)
Approved Gas
Type
Natural Gas or L.P., unit must match gas type supplied
Gas Pressure
5.0” w.c. min. for Natural Gas, 11.0” w.c. min. for L.P., 14.0” w.c. maximum (Natural
Gas & Propane)
Venting System Power vent through the wall or vertical through the roof
Approved Vent
Materials
PVC, CPVC or ABS
Minimum
Clearance for
Servicing
18” from top, 24” from front, 4” sides and rear
Water Supply
Pressure
150 psi maximum allowable working pressure. Check local codes for supply
pressure.
Gas Control
ECO Limit
Residential 188°F (87°C), Commercial 199°F (93°C)
Residential
Temperature Set
Point Range
60°F (16°C) to 160°F (71°C) (approximate temperatures)
Commercial
Temperature Set
Point Range
80°F (27°C) to 180°F (82°C) (approximate temperatures)
Blower
Temperature
Switch
Normally closed, opens @ 155°F (68°C), auto reset @ approximately 135°F (57°C)
Exhaust
Pressure Switch
Normally open
Closes on vacuum increase @ -2.15” w.c.
Intake
Pressure Switch
Normally closed
Opens on vacuum increase @ -0.8” w.c.
Blower
115 VAC, 60 Hz, 3.3 amps, 3000 RPM @ 1.5” w.c.
Glossary of Terms
BTU
British Thermal Units
psi
Pounds per Square Inch
GPM
Gallons per Minute
RPM Revolutions per minute
Hz
Hertz
ECO Energy Cut Out
kWhr
Kilowatt Hour
VAC Volts Alternating Current
LED
Light Emitting Diode
“w.c. Inches of Water Column
NPT
National Pipe Thread
ºC
Degrees Centigrade
Ohms
Ohms of resistance
ºF
Degrees Fahrenheit
6