12
Electrical Connections continued-
Heating Elements
To replace heating elements, disconnect power to the water heater, drain
tank and replace element. To remove a heating element, use a 1 1/2” screw
type element wrench that is usually available at places where plumbing
supplies can be obtained.
Do not
over-tighten the new element, as this will
cause distortion in the new element gasket. Once the element has been
replaced, follow the instructions “To Fill The Water Heater”. It is imperative
that the water heater is filled with water before the power is restored to the
heating elements.
Amperage Chart
Amperage
Fuse Size
Ground Wire Size
kW 220V 380V 415V 220V 380V 415V
(AWG)
Input
1Ø 3Ø 3Ø 1Ø 3Ø 3Ø 220V 380V 415V
6
27
9
8
35
12
10
10
14
14
9 41 14 13 60 20 20
10 14 14
12 55 18 17 70 25 25
8 12 12
13.5
61 21 19 80 30 25
8 10 12
15 68 23 21 90 30 30
8 10 10
16.5
75
25
23
100
35
30
8
10
10
18
82
27
25 110
35
35
8
10
10
GPH Recovery Capacities
kW Temperature
Rise
Input 40°F 50°F 60°F 70°F 80°F 90°F 100°F 120°F 130°F 140°F
6 62 50 41 35 31 28 25 21 19 18
9 93 74 62 53 47 41 37 31 29 27
12
124
99 83 71 62 55 50 41 38 35
13.5
140
112
93 80 70 62 56 47 43 40
15
155
125
103
89 78 69 62 52 48 44
16.5 171 137 114
98
86
76
68
57
53
49
18
186
149
124
106
93 83 74 62 57 53
Multiply kW input by 3,412 to determine BTU input:
Example: 54kW x 3412 = 184,248 BTU’s
Recovery Computation Formula
GPH= (watts x 3.412) / (8.25 x °Temp. Rise)