HIGH EFFICIENCY COMMERCIAL BOILERS AND VOLUME WATER HEATERS
Section 1 -
GENERAL INFORMATION
WARNING
Brute units
must
be installed in accordance with the
procedures detailed in this manual, or the Bradford
White warranty will be voided. The installation must
conform to the requirements of the local jurisdiction
having authority, and, in the United States, to the latest
edition of the National Fuel Gas Code, ANSI Z223.1/
NFPA54. In Canada, the installation must conform
to the latest edition of CSA B149.1 Natural Gas and
Propane Gas Installation Code, and/or local codes.
Where required by the authority having jurisdiction,
the installation of Brute boilers must conform to
the Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1. Any
modifications to the boiler, its gas controls, or wiring
may void the warranty. If field conditions require
modifications, consult the factory representative before
initiating such modifications.
1.1 Introduction
This manual provides information necessary for the
installation, operation, and maintenance of Bradford White
Brute appliances. Read it carefully before starting the
installation.
All application and installation procedures should be reviewed
completely before proceeding with the installation. Consult
the Bradford White factory, or local factory representative,
with any problems or questions regarding this equipment.
Experience has shown that most operating problems are
caused by improper installation.
Brute is protected against over pressurization. A pressure
relief valve is included with each Brute. Some Brutes may
require that the PRV be installed prior to filling the system.
DANGER
The inlet gas pressure to the appliance must not
exceed 13” W.C. (3.2kPa).
All installations must be made in accordance with
1) American National Standard Z223.1/NFPA54-Latest
Edition “National Fuel Gas Code” or
2) CSA B149.1 “Natural Gas and Propane Installation Code”
or in Canada reference the B149.1 latest edition and with
the requirement of the local utility or other authorities having
jurisdiction. Such applicable requirements take precedence over
the general instructions contained herein. All electrical wiring
is to be done in accordance with the local codes, or in the
absence of local codes, with:
1) The National Electrical Code ANSI/NFPA No. 70-latest
Edition, or 2) CSA STD. C22.1 “Canadian Electrical Code
- Part 1”. This appliance must be electrically grounded in
accordance with these codes.
1.2 Model Identification
Consult the rating plate on the unit. The following information
describes the model number structure.
(1-3)
Model Series Designation
B N T = Bradford White, Brute
(4)
Usage
H = Hydronic
V = Volume Water
(5-7)
Size
1 5 0 = 150,000 BTU/hr input
1 9 9 = 199,000 BTU/hr input, BNTV only
2 1 0 = 210,000 BTU/hr input, BNTH only
2 8 5 = 285,000 BTU/hr input
3 9 9 = 399,000 BTU/hr input
5 0 0 = 500,000 BTU/hr input
6 0 0 = 600,000 BTU/hr input
7 5 0 = 750,000 BTU/hr input
8 5 0 = 850,000 BTU/hr input
(8)
Fuel
N = Natural Gas
P = LP Gas
(9)
Options Code
X = Standard Unit
J = CSD-1, FM, GAP, IL Code
(size 500-850 only)
C - STANDARD (Canada)
D - CSD-1 (Canada)
E - OUTDOOR
F - OUTDOOR (Canada)
G - CSD-1, OUTDOOR
H - CSD-1, OUTDOOR (Canada)
(10)
Pump Options
N = Pump included
(150-500 only)
X = No pump
(configuration available for all sizes)
W = HLW w/ Pump
(option for BNTV only)
L = HLW w/out Pump
(option for BNTV only)
(11)
Revision
3 = Third version
Model Nomenclature
2
3
4
5
6 7
8
9
10
11
SERIES
Bradford White
Brute
USAGE
H -
HYDRONIC
V -
VOLUME
WATER
SIZE
MBTU/h
1 5 0
1 9 9
2 1 0
2 8 5
3 9 9
5 0 0
6 0 0
7 5 0
8 5 0
FUEL
N -
NATURAL
P -
PROPANE
OPTIONS CODE
X -
STANDARD
J -
CSD-1, FM, GAP,
IL
(500-850 only)
C -
STANDARD (Canada)
D -
CSD-1 (Canada)
E -
OUTDOOR
F -
OUTDOOR (Canada)
G -
CSD-1, OUTDOOR
H -
CSD-1, OUTDOOR
(Canada)
PUMP OPTIONS
N -
PUMP INCL.
(150-500 only)
X -
NO PUMP
W -
HLW w/PUMP
(opt for BNTV only)
L -
HLW w/out
PUMP
(opt for BNTV only)
REVISION
3 -
THIRD
REG DESIGNATION
B
3
N
T
B
-
INTERNAL USE
1
B
Содержание Copper Brute II BWCH 2000
Страница 4: ...BRADFORD WHITE...
Страница 26: ...Page 22 BRADFORD WHITE 150 285 Figure 23 Minimum Venting Distance...
Страница 32: ...Page 28 BRADFORD WHITE Figure 24 Hydronic Piping Single Boiler Zoning with Circulators Brute TM...
Страница 48: ...Page 44 BRADFORD WHITE Figure 38 Ladder Diagram 7 9 Ladder Diagram...
Страница 96: ...Page 92 BRADFORD WHITE Parts Illustration 4 Internal Components Sizes 750 850...
Страница 98: ...Page 94 BRADFORD WHITE Parts Illustration 6 Gas Train Components Sizes 600 850...
Страница 100: ...Page 96 BRADFORD WHITE Parts Illustration 8 Electrical Components Front Battery CR2032 Touchscreen Back...
Страница 102: ...Page 98 BRADFORD WHITE Notes...
Страница 103: ...Page 99 Brute HIGH EFFICIENCY COMMERCIAL BOILERS AND VOLUME WATER HEATERS Notes...