Bradford White Copper Brute B4 Скачать руководство пользователя страница 11

Internet Version for Reference Only

 

BRADFORD WHITE

Page 10

Copper Brute B4 Volume Water Heaters

Page 11

NOTE: 

It is possible to have hard and soft 

water in the same city. Check with the local water 

companies.

If an installer sees damage to any water handling 

equipment at the installation site, it should be repaired 

as soon as possible to help reduce maintenance costs. 

If there is erosion, resize the pump to reduce water 

velocity before the tube ruptures. If scaling is bad, 

set up a heat exchanger tube-cleaning maintenance 

schedule to prevent heat exchanger tube cracking 

and wear. Not fixing the condition will mean serious 

damage to the heater and the water system.

NOTES: 

•        In areas where the water supply is soft or 

corrosive, the heater must have cupronickel tubes 

in the heat exchanger. 

•        Bradford White does not warrant heat exchangers 

damaged by scaling, corrosion, or erosion.

2.6.3  Freeze Protection

Although Copper Brute heaters are design 

certified for outdoor installations, such installations 

are not recommended in areas subject to freezing 

temperatures unless proper precautions are taken. 

Consult the local factory representative or Bradford 

White for additional information.

2.6.4  Water Hardness

Consider the water hardness when selecting a 

pump for the heater (see Table 3). Hard water needs a 

pump which can provide high flow to prevent scaling, 

while soft water needs low flow to prevent erosion.

2.6.5  Pump Requirements

The Copper Brute heater has a factory installed 

pump which is for heater-to-tank circulation only. 

Pump performance is shown in Table 4.

The pump that is mounted on the heater is sized 

for the heat exchanger and 30 feet (9.1m) of 1-1/2" 

pipe, including six (6) 90° elbows. If more piping is 

needed, contact Bradford White for options.

The water temperature entering the Copper Brute 

must be at least 110°F (43°C). 

Figures 20, 21 and 22 show typical piping 

arrangements. For assistance with other piping 

methods, contact Bradford White.

24.    Fasten the capillary tube(s) by squeezing the 

retaining clip together, then tighten the screw.

25.    Feed the two brown wires through the top hole 

on the left side until the conduit elbow is against 

the jacket. 

26.    Fasten the conduit by sliding the retaining nut 

over the two brown wires (inside the control 

compartment) then screwing it down finger-tight 

on the conduit elbow.

27.    Straighten the capillary tubing and fasten it to the 

side of the heater under the channel. Use the self-

tapping screws to fasten the channel to the jacket.

28.    Feed the two white wires into the control 

compartment. Attach one wire to the terminal 

in the manual reset hi-limit switch. If one is not 

installed, attach it to terminal No. 1. Connect the 

other wire to the red wire attached to the fuse 

holder.

29.    Attach the two brown wires to terminals No. 5 

and 6 on the terminal strip. Keep all wiring away 

from surfaces that will get hot during heater 

operation.

30.    Replace the gap closures and tighten the screws 

securely.

31.    Replace the three grommets and the cap.
32.    Reinstall the drain plug and drain valves.
33.    Slip the flue collector assembly back down inside 

the enclosure.

34.    Carefully slip a hand inside to make sure there 

are no gaps between the heat exchanger and the 

flue collector.

35.    Check to make sure the wiring is not pinched 

against sharp edges, or resting on the collector 

assembly.

36.    Replace the two flue collector holddown clamps.
37.    Replace the top assembly and fasten it with the 

hex-head screws. 

38.    Replace the front cover.
39.    Reinstall the vent cap or drafthood if one was 

removed.

40.    On indoor installations (sizes 175-250), insert the 

draft hood switch plug into the receptacle on the 

left side of the heater.

2.6.2  Water Chemistry

Bradford White equipment is designed to be used 

in a variety of water conditions. With the proper pump, 

the water velocity in the heat exchanger tubes is kept 

high enough to prevent scaling from hard water, yet 

low enough to avoid erosion by soft water. 

Hardness           Grains per                  Parts

Category               Gallon                   per Million 

 

                              

Soft                  1 through 7.5           17 through 128

Normal             7.6 through 17         129 through 291

Hard                Over 17                   Over 291

Table 3.  Water Hardness.

Содержание Copper Brute B4

Страница 1: ...tion and or operation will void the warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do...

Страница 2: ...rt Up Procedure 21 3 3 Setting the Temperature Controls 21 3 3 1 Remote Water Heater Temperature Control 21 3 3 2 Internal Water Heater Temperature Control 22 3 4 Adjustment for Minimum Input Rate mod...

Страница 3: ...sporter The transporter will not accept a claim from the shipper Bradford White The warranty does not cover damage caused by improper installation operation or field modification 1 3 Technical Assista...

Страница 4: ...Fired Heaters ANSI ASME CSD 1 Any changes to the heater gas controls gas orifices wiring or draft diverter may void the warranty If field conditions require a change to any of the above consult the fa...

Страница 5: ...of all the gas fired ap pliances within the enclosure Alcove Installation acceptable An alcove suitable for the installa tion of a heater is a restricted sec tion of a room not separated from the roo...

Страница 6: ...For Combustible Floors Flashing 4x4 Stringer Roof Base Rail 20 Gauge Galvanized Sheet Metal Cap Roofing 2 3 3 Flooring Typical Installation Do not install the heater directly on carpeting without pla...

Страница 7: ...each opening must have a minimum free area of at least one square inch for each 4 000 BTU h input of the total input rating of all appliances in the enclosed area In Canada refer to CGAB149 1 and 2 2...

Страница 8: ...nal designated Field Interlock to keep the heater from firing unless there is a positive draft 2 5 2 Replacement of Existing Heater When a heater is removed from a common venting system the venting sy...

Страница 9: ...mp Flue Collector REAR TILE COVER FLOW SWITCH CONDUIT GAP CLOSURE GROMMET DRAIN VALVE METAL CHANNEL FOR CAPILLARY TUBE TERMINAL STRIP HEAT EXCHANGER ASSEMBLY GAP CLOSURE DRAIN PLUG DRAIN VALVE REAR TI...

Страница 10: ...nal strip disconnect the two brown wires from No 5 and No 6 terminals 15 Remove the flow switch conduit retaining clip and the elbow leading into the jacket 16 Reach inside the control compartment and...

Страница 11: ...ten the capillary tube s by squeezing the retaining clip together then tighten the screw 25 Feed the two brown wires through the top hole on the left side until the conduit elbow is against the jacket...

Страница 12: ...4 3 2 30 17 Hard 23 1 5 18 1 5 5 22 12 400 2 Soft 34 2 1 13 3 4 1 19 11 Normal 34 2 1 13 3 4 1 19 11 Hard 46 2 9 23 4 7 1 14 8 4 Soft 17 0 7 11 1 3 4 37 21 Normal 17 0 7 11 1 3 4 37 21 Hard 23 1 5 19...

Страница 13: ...lve Bldg Loop Circ Pump Hot Water Return from Building Throttling Valve Check Valve Bldg Loop Circ Pump Cold Water Conventional Tank To Drain Hot Water to Building Optional Cold Water Supply When Adeq...

Страница 14: ...that will create a closed water supply system Contact the water supplier or local plumbing inspector on how to control this situation During the heating cycle of the heater the water expands creating...

Страница 15: ...ndividual shutoff valve from the supply gas system during pressure test of the system at pressures higher than 1 2 psi 3 4 kPa 8 Gas supply pressures to the heater are listed in Table 6 NOTE The heate...

Страница 16: ...eaks using a soap solution Caution Since some leak test solutions including soap and water may cause corrosion or stress cracking rinse the piping with water after testing 2 7 2 Special Precautions fo...

Страница 17: ...K FIELD INTERLOCK REMOVE JUMPER WHEN USED 2 AMP FUSE HI LIMIT CONTROL TEMP RESET MANUAL STRIP TERMINAL TRANSFORMER VENT DAMPER ACTUATOR M VENT DAMPER AND DRAFTHOOD SWITCH M RESET PILOT BURNER WITH THE...

Страница 18: ...WITH SPARK ELECTRODE SPARK O BR Y GAS VALVE PV MV PV MV Y O LINK FUSIBLE W W TR TH TR GAS VALVE ALTERNATE TH O Y BR POWER SWITCH T B 3 RELAY PUMP A 1 R W BK BL GROUNDING BK PUMP BR BR CONDUCTOR POWER...

Страница 19: ...RING 24V 115V FIELD WIRING 24V 115V GAS VALVE PILOT BURNER WITH THERMOCOUPLE 1 2 3 4 5 6 7 8 9 10 11 12 R R R R R R Y Y Y Y BK BK BK BK BR BR BR BR BR BR BR O W W W W BL BK P 1 2 3 4 5 G A T B 1 3 24V...

Страница 20: ...TE R RED Y YELLOW BL BLUE BR BROWN O ORANGE G GREEN P PURPLE FACTORY WIRING 24V 115V FIELD WIRING 24V 115V R R 24V 115V BK BR W Y Y W R R R BR O Y BK BL W R R BR BR BR Y O BR BR BK W BK BK W G Y BR O...

Страница 21: ...If you smell gas follow these rules 1 DO NOT light matches DO NOT turn electric lights or switches on or off in area DO NOT use an electric fan to remove the gas from area 2 Shut off gas at LP tank 3...

Страница 22: ...F 3 C above the automatic reset high limit For units that only have a manual reset high limit no automatic reset high limit set the manual reset high limit 20 F 11 C above the outlet temperature to av...

Страница 23: ...he gas and electric controls installed on the heaters are designed for both dependable operation and long life Safe operation of the heater depends on their proper functioning NOTE The warranty does n...

Страница 24: ...15 Install the anti rotation bracket to the inner panel and fasten with two screws see Figure 32 and the three screws to heater 16 Connect the service union in the gas line and screw the main gas pipe...

Страница 25: ...s with a wet brush or fine water spray before servicing the heat exchanger 2 Remove the heat baffles and check for a light accumulation of soot or corrosion on the outside of the heat exchanger tubes...

Страница 26: ...atural gas and between 11 and 14 inches W C for propane units see Table 6 5 1 2 Checking the Manifold Regulated Gas Pressure 1 Attach a manometer or a dry gas pressure gauge to heater jacket see Figur...

Страница 27: ...st lock fuse holder If it is burned replace it with a 2 amp fuse Part No E0084400 If there is a short the cause of the short must be found and repaired Do not jumper or bypass the fuse 6 Make sure the...

Страница 28: ...t the fusible link flame roll out switch if installed 1 Touch the voltmeter lead to the lower terminal on the terminal block see Figure 39 Figure 38 Testing the manual reset hi limit switch Figure 39...

Страница 29: ...yellow wire terminal on the transformer 2 Touch the other voltmeter lead to the red 24V terminal on the ignition control 3 If the voltmeter reads voltage the temperature control and the manual reset...

Страница 30: ...oltage replace the ignition control 6 If the voltmeter reads 24 to 28VAC but there is no pilot ignition check for a air in gas lines b restrictions in gas line valve or pilot tubing c clogged pilot or...

Страница 31: ...ot the other examine the external control It may require service or replacement 1 Check all wire connections ignition cable and using a mirror make sure there is a pilot flame 2 If everything appears...

Страница 32: ...nce Only C O R P O R A T I O N B W RADFORD HITE H2317000 Ambler PA 19002 Tech Service 800 334 3393 Service Parts 800 538 2020 Warranty Service 800 531 2111 www Bradford White com Litho in U S A Bradfo...

Отзывы: