15
Troubleshooting
Condensing PV Series
15
LED Status
Control Status
Probable Cause
Service Procedure
Six-one flash,
three second
pause
Failed to light
pilot.
System auto
resets.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad
connection at gas valve.
5. Low gas pressure.
Page 18
Six-two flash,
three second
pause
Pressure switch
or blower temp
switch opened
during burner
operation.
System auto
resets.
1. Vent blockage or improper vent
configuration.
2. Pressure switch tubing kinked or blocked.
3. Faulty pressure switch.
4. Vent termination being affected by wind.
5. Blower not spinning up to speed.
6. Blower temp or exhaust temp too high.
7. Faulty blower temperature switch.
8. Blocked condensate trap.
1. Check vent or vent
tables.
2. & 3. Page 19
4. Refer to venting
section of
installation manual.
5. Page 21
6. & 7. Page 23
8. Page 39
Six-three flash,
three second
pause
Pilot flame
extinguished.
System auto
resets.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad
connection at gas valve.
5. Insufficient combustion air.
6. Gas pressure is out of specification.
1.-4. Page 18
5. Refer to installation
manual
6. Page 25
Six-four flash,
three second
pause
Undesired-false
pilot flame
sensed.
System auto
resets.
Pilot valve stuck in open position.
Replace gas control,
page 27
Seven flash,
three second
pause
Simulated
Resistive Device
fault detected.
Simulated resistance device harness out of
specification or disconnected.
Page 29
Eight-one flash,
three second
pause
Simulated
Resistive Device
out of
specification.
Simulated resistive device out of
specification. Possible short.
Page 29
Eight-two flash,
three second
pause
Temperature
sensor fault.
1. Damage to temperature sensor wire.
2. Temperature sensor resistance out of
range.
Page 27
Eight-three flash,
three second
pause
Gas valve
electronics fault
detected.
1. Control needs to be reset.
2. Control is wet or physically damaged.
1. Interrupt power
supply.
2. Replace gas control,
page 27
Eight-four flash,
three second
pause
Gas valve fault
detected.
1. Control needs to be reset.
2. Control is wet or physically damaged.
1. Interrupt power
supply.
2. Replace gas control,
page 27