Water Connections continued- 

 
 

WARNING 

For protection against excessive temperatures and pressure, install 
temperature and pressure protective equipment required by local codes, 
but not less than a combination temperature and pressure relief valve 
certified by a nationally recognized testing laboratory that maintains 
periodic inspection of production of listed equipment or materials, as 
meeting the Requirements for 

Relief Valves and Automatic Gas Shutoff 

Devices for Hot Water Supply Systems, ANSI Z21.22

, and the Standard 

CAN1-4.4 Temperature, Pressure, Temperature and Pressure Relief 
Valves and Vacuum Relief Valves

.  The combination temperature and 

pressure relief valve shall be marked with a maximum set pressure, not to 
exceed the maximum working pressure of the water heater.  The 
combination temperature and pressure relief valve shall also have an 
hourly rated temperature steam BTU discharge capacity not less than the 
hourly input rating of the water heater. 
 
Install the combination temperature and pressure relief valve into the 
opening on the water heater, which is provided for this purpose. 
 
Note:  Some models may already be equipped or supplied with a 
combination temperature and pressure relief valves.  Verify that this 
combination temperature and pressure relief valve complies with local 
codes.  If the combination temperature and pressure relief valve does not 
comply with local codes, replace it with one that does.  Follow the 
installation instructions provided on this page. 
 
Install a discharge line so that water discharged from the combination 
temperature and pressure relief valve will exit within six (6) inches 

(15.3 

cm)

 above, or any distance below the structural floor and at a location 

where dischargers cannot contact any live electrical part.  This discharge 
line is to be installed complete drainage of both the temperature and 
pressure relief valve and the discharge line can occur.  The discharge 
opening must not be subjected to blockage or freezing.  

DO NOT

 thread, 

plug or cap the discharge line.  It is recommended that a minimum of four 
(4) inches 

(10.2 cm)

 be provided on the side of the water heater for 

servicing and maintenance of the combination temperature and pressure 
relief valve. 
 
Do not place a valve between the combination temperature and pressure 
relief valve and the tank.

 

Содержание 45837F

Страница 1: ...OMPLY WITH THESE INSTRUCTIONS READ THESE INSTRUCTIONS THOROUGHLY BEFORE STARTING For your family s comfort safety and convenience it is recommended this water heater be installed and serviced by a plu...

Страница 2: ...fer to it when questions arise If you have any specific questions concerning your warranty please consult the plumbing professional from whom your water heater was purchased For your records we recomm...

Страница 3: ...fied for the purpose of heating potable water The installation and use of this water heater for any purpose other than the heating of potable water may cause damage to the water heater and create a ha...

Страница 4: ...llation and operating instructions select a location for the water heater where the floor is level and is easily accessible to a power supply and water connections It is recommended that the water hea...

Страница 5: ...nimum length and width of at least 4 in 10 2 cm greater than the diameter of the water heater The drain pan as described above can be purchased from your plumbing professional The drain pan must be pi...

Страница 6: ...a back flow preventer in the cold water supply provisions must be made to control thermal expansion DO NOT operate this water heater in a closed system without a provision for controlling thermal exp...

Страница 7: ...he water heater which is provided for this purpose Note Some models may already be equipped or supplied with a combination temperature and pressure relief valves Verify that this combination temperatu...

Страница 8: ...d from your local plumbing supplier Please consult a plumbing professional WARNING Hydrogen gas can be produced in the hot water system served by this water heater when there has been no usage for a l...

Страница 9: ...hest risk of being Children disabled and elderly instantly or death from scalds Water temperature over 125 F Feel water before bathing or before setting temperature available showering Temperature lim...

Страница 10: ...10 Water Connections continued Figure 2A Dual Temperature System With Mixing Valve 50A 80A 120A Figure 2B Dual Temperature System With Mixing Valve 6A 12A 20A 30A 40A...

Страница 11: ...11 Water Connections continued Figure 3A Single Installation With Storage Tank Gravity Circulation 50A 80A 120A Figure 3B Single Installation With Storage Tank Gravity Circulation 6A 12A 20A 30A 40A...

Страница 12: ...12 Water Connections continued Figure 4A Dual Water Heater Installation 50A 80A 120A Figure 4B Dual Water Heater Installation 6A 12A 20A 30A 40A...

Страница 13: ...odels and transformer have been made at the factory DO NOT alter any of the internal wiring Wiring connections may loosen during shipment Check all connections for tightness To make the wiring connect...

Страница 14: ...ory installed internal fusing to comply with Underwriters Laboratories requirements GPH Recovery Capacities kW Temperature Rise Input 40 F 50 F 60 F 70 F 80 F 90 F 100 F 120 F 140 F 3 31 25 21 18 16 1...

Страница 15: ...alve combination temperature and pressure relief valve and the hot and cold water connections 5 Reconnect power supply to water heater TO DRAIN THE WATER HEATER Should it become necessary to completel...

Страница 16: ...alve several times until the valve seats properly without leaking and operates freely DANGER Hotter water increases the risk of scald injury Scalding may occur within five 5 seconds at a temperature s...

Страница 17: ...essure relief valve on the appliance discharges periodically this may be due to thermal expansion in a closed water supply system Contact the water supplier or local plumbing inspector on how to corre...

Страница 18: ...R HEATER ARE WARRANTED Complete the following information and retain for future reference Model No Serial No Service Phone Days Nights Address Supplier Supplier Phone No CAUTION FOR YOUR SAFETY DO NOT...

Страница 19: ...contactors interconnect these two systems In order to clearly illustrate the electrical circuits two wiring diagrams are provided These diagrams are labeled as the Power Circuit Wiring Diagram and the...

Страница 20: ...settings are exceeded The operation and setting of these controls are described in the manual provided by the control manufacturer This manual is included with the water heater Installation and Operat...

Страница 21: ...alve a low pressure condition can develop when water is removed through the water heater drain valve Low Water Level Control This control will interrupt the electrical current to the contactor coil wh...

Страница 22: ...d for certain faults Referring to the control circuit wiring diagram the alarm will activate when any one of the following events occur The Hi Limit control has been tripped The High Water Pressure Co...

Страница 23: ...drain valve Heating Element Sequencers Heating element sequencers are available in order to stage the activation of the heating elements thereby reducing the inrush current to the water heater The se...

Страница 24: ...e circuit to the electrical elements The power circuits are available with internal circuit fusing and without internal circuit fusing Refer to the water heater power circuit wiring diagram attached t...

Отзывы: