Procedure for Checking Thermostat Sensor 

 

Set the thermostat above water temperature (see temperature adjustment section) and observe system through one (1) 
complete cycle.  Make sure system operates as desired. 

 

To check the sensor, compare the resistance of the sensor wires (either outside black to center wire with yellow marking) 
as measured by an ohmmeter to the water temperature as measured by an accurate thermometer.  Thermistor resistance 
increases as the temperature decreases.  The tables below show the correct sensor resistance at various temperatures.  
Both thermistors in the sensor assembly should have approximately the same readings.  Replace the sensor if the ohm 
reading in the chart does not approximate the reading from the sensor at the temperature measured in the tank.  Use a 
thermometer or thermocouple to measure the temperature from the hot water outlet or T&P valve. 

 

In Degrees F 

°F 0 1 2 3 4 5 6 7 8 9 

40  26109 25400 24712 24045 23399 22771 22163 21573 21000 20445 

50  19906 19383 18876 18383 17905 17440 16990 16553 16128 15715 

60  15314 14925 14548 14180 13823 13477 13140 12812 12494 12185 

70  11884 11592 11308 11032 10763 10502 10248 10000  9760  9526 

80  9299 9078 8862 8653 8449 8250 8057 7869 7685 7507 

90  7333 7165 7000 6839 6683 6531 6383 6238 6098 5961 

100  5827 5697 5570 5446 5326 5208 5094 4982 4873 4767 

110  4663 4562 4464 4368 4274 4183 4094 4006 3922 3839 

120  3758 3679 3602 3527 3453 3382 3312 3244 3177 3112 

130  3048 2986 2925 2866 2808 2752 3697 3643 2590 2538 

140  2488 2439 2391 2344 2298 2253 2209 2166 2124 2083 

150  2043 2004 1966 1928 1891 1856 1820 1786 1753 1720 

160  1688 1656 1625 1595 1566 1567 1509 1481 1454 1427 

170  1402 1376 1351 1327 1303 1280 1257 1235 1213 1191 

180  1170 1150 1129 1110 1090 1071 1053 1035 1017  999 

190 982 965 949 933 917 901 886 871 857 842 

200 828 814 801 788 775 762 749 737 725 713 

 

In Degrees C

 

°C 0 1 2 3 4 5 6 7 8 9 

32648 31026 29495 28049 26682 25389 24166 23010 21915 20879 

10  19898 18968 18088 17253 16461 15710 14998 14322 13680 13071 

20  12492 11942 11419 10922 10450 10000  9572  9165  8778  8409 

30  8057 7722 7403 7099 6808 8532 6268 6016 5775 5546 

40  5327 5117 4917 4726 4543 4368 4201 4042 3889 3742 

50  3602 3468 3340 3217 3099 2986 2878 2774 2675 2579 

60  2488 2400 2316 2235 2157 2083 2011 1942 1876 1813 

70  1752 1693 1637 1582 1530 1480 1432 1385 1340 1297 

80  1256 1216 1177 1140 1105 1070 1037 1005  974  944 

90  916 888 861 835 810 786 763 741 719 698 

 
 

Содержание 100T399-SOLA

Страница 1: ...not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas su...

Страница 2: ...f the water heater provides for setting and displaying the temperature setpoint and monitoring the status of the water heater Durable direct spark ignition system The temperature adjustment range is 7...

Страница 3: ...le that can have the power supply interrupted by a switch that is used to control lights or another appliance If wiring in conduit is required cut the line cord close to the control board and make the...

Страница 4: ...rod sparks to the burner and gas valve opens burner ignition 5 Flame signal confirmed 6 Blower remains at reduced speed for a short time to stabilize flame 7 Blower increases to full speed for full i...

Страница 5: ...it F or degrees Celsius C and the status of the water heater Standby or Run For energy efficient operation of your water heater the suggested initial temperature setting is 120 F 49 C During the winte...

Страница 6: ...highly recommended that the setpoint be adjusted to the lowest temperature possible for the needs of the installation Make sure the water heater control display is not in a public area that can resul...

Страница 7: ...d Temperature Up button until desired setpoint temperature appears in the display Step 2 Press DONE button for new setting to take effect immediately If the DONE button is not pressed the new temperat...

Страница 8: ...DONE button is not pressed the new temperature setting will take effect in approximately 10 seconds NOTICE Pressing the NEXT button instead of DONE will enter the display to show unused screens such a...

Страница 9: ...between F or C Press DONE when selection is complete Display will revert back to DHW setpoint NOTICE Pressing the NEXT button instead of DONE will enter the display to show RMT for Remote Firing Cont...

Страница 10: ...y indicating that the control cycled through the maximum number of ignition retries for ignition The control will make another 4 ignition attempts after the 15 minute waiting period 10 If the exhaust...

Страница 11: ...c Mode for 12 5 minutes after the last button press for viewing unless Done button is pressed to exit Diagnostic Mode Step 2 The display will show the flame sense current in microamps when the burner...

Страница 12: ...xt button and the display will show the temperature sensor reading Step 6 Press lower right Next button and the display will show the manual firing rate adjustment This function is not currently used...

Страница 13: ...ons Check to make sure the wiring connections on the control module from terminals J4 10 and J8 2 are connected together 62 Fan speed not proved Check the PWM wire harness connection from the blower t...

Страница 14: ...reattempt ignition after 15 minute waiting period Check gas valve wiring and gas valve operation during the ignition cycle If burner lights but quickly goes out check the flame sensor wire or the flam...

Страница 15: ...11592 11308 11032 10763 10502 10248 10000 9760 9526 80 9299 9078 8862 8653 8449 8250 8057 7869 7685 7507 90 7333 7165 7000 6839 6683 6531 6383 6238 6098 5961 100 5827 5697 5570 5446 5326 5208 5094 49...

Страница 16: ...16 Condensate Trap Elbow 17 Silicone hose 18 Outer Door Service Panel Specify model 19 Clip 20 NSF Escutcheon 21 Exhaust Pressure Switch 22 Nuts 23 Collector Limit Switch 24 Screw 6 32 x 3 8 25 Clean...

Страница 17: ...ition Specify model 3A Burner Ass y Specify model 16A Screw 8 32 x 1 4 RHCR 4A Blower Specify model 17A Gasket Flame Sensor 5A Silicone Hose 18A Flame Sensor 6A Burner Mounting Insert Gasket 19A Trans...

Страница 18: ...s pending Current Canadian Patents 2 092 105 2 107 012 2 108 186 2 112 515 2 143 031 2 239 007 2 262 174 2 314 845 2 409 271 2 476 685 2 504 824 2 548 958 CC Ignition Control Assembly 1C Control Mount...

Страница 19: ...19 NOTES...

Страница 20: ...20 NOTES...

Отзывы: