Standards and certifications • Requirements for emissions
Chap
ter 5
Sta
nda
rds a
nd
certi
fica
tion
s
177
Automation PC 820 User's Manual V 1.00
3.2 Emissions / Electromagnetic emissions
Test carried out according to
EN 55011 / EN 55022
Limits according to
EN 61000-6-4
Limits according to
EN 61131-2
Limits according to
47 CFR Part 15 Subpart B
Class A
AC mains connections
500 kHz - 30 MHz
-
73 dB (µV)
Quasi-peak value
60 dB (µV)
Average
73 dB (µV)
Quasi-peak value
60 dB (µV)
Average
Other connections
150 kHz - 500 kHz
-
-
-
Other connections
500 kHz - 30 MHz
-
-
-
Test carried out according to
EN 55011 / EN 55022
Limits according to
EN 61000-6-4
Limits according to
EN 55011 class A
Limits according to
EN 55022 class A
30 MHz - 230 MHz
measured at a distance of 10 m
< 40 dB (µV/m)
Quasi-peak value
< 40 dB (µV/m)
Quasi-peak value
< 40 dB (µV/m)
Quasi-peak value
230 MHz - 1 GHz
measured at a distance of 10 m
< 47 dB (µV/m)
Quasi-peak value
< 47 dB (µV/m)
Quasi-peak value
< 47 dB (µV/m)
Quasi-peak value
Test carried out according to
EN 55011 / EN 55022
Limits according to
EN 61131-2
Limits according to
EN 50091-2 Class A
Limits according to
EN 61800-3
30 MHz - 230 MHz
measured at a distance of 10 m
< 40 dB (µV/m)
Quasi-peak value
< 40 dB (µV/m)
Quasi-peak value
< 50 dB (µV/m)
Quasi-peak value
230 MHz - 1 GHz
measured at a distance of 10 m
< 47 dB (µV/m)
Quasi-peak value
< 47 dB (µV/m)
Quasi-peak value
< 60 dB (µV/m)
Quasi-peak value
Test carried out
Limits according to 47 CFR Part
15 Subpart B class A
30 MHz - 88 MHz
measured at a distance of 10 m
< 90 dB (µV/m)
Quasi-peak value
88 MHz - 216 MHz
measured at a distance of 10 m
< 150 dB (µV/m)
Quasi-peak value
216 MHz - 960 MHz
measured at a distance of 10 m
< 210 dB (µV/m)
Quasi-peak value
>960 MHz
measured at a distance of 10 m
< 300 dB (µV/m)
Quasi-peak value
Table 123: : Test requirements - Electromagnetic emissions for industrial areas
Table 122: Test requirements - Network-related emissions for industrial areas (cont.)
Содержание Automation PC 820
Страница 2: ...2 Automation PC 820 User s Manual V 1 00...
Страница 4: ...4 Automation PC 820 User s Manual V 1 00...
Страница 6: ...6 Automation PC 820 User s Manual V 1 00...
Страница 80: ...80 Commissioning Installation Automation PC 820 User s Manual V 1 00 Figure 26 Tightening the fastening screws...
Страница 212: ...212 Commissioning USB flash drive Automation PC 820 User s Manual V 1 00...
Страница 246: ...Model number index 246 Automation PC 820 User s Manual V 1 00...