5.5 STATUS Messages
This message group simply shows the UPS STATUS at the upper line of LCD PANEL.
MESSAGE
POSSIBLE CAUSE
BTT.TEST DISABLE
If battery test cannot be perform from any reason this message will be
showed.
BYPASS DISABLED
If load cannot be transfer to bypass from any reason this message will be
showed.
MANUAL BYP.SW.ON
Maintenance Bypass Switch On
ENTER <BYPASS>
If the user press Enter button load will transferred to bypass.
RECTIF.START!
UPS started the rectifier
STATUS NORMAL
UPS is operating.
INVERTER START
UPS started the inverter.
MAINT.SW ON!
Maintenance bypass switch is on
EMERGEN.STOP!
External emergency stop signal is applied to UPS.
MANUAL BYPASS!
Load is transferred to bypass input manually.
<ENTER> START!
Press ENTER to start the UPS.
WAIT SHUTDOWN
Shutdown command is performed from operating system and UPS is waiting for
a certain delay for shutdown.
UPS SHUTDOWN
UPS is in shutdown status
WAIT RESTART
UPS is shutdown but it is waiting for a certain delay for restart
SHUTDOWN&RESTART
Shutdown command received from RS232 interface. Currently UPS is in slip
mode. After given time delay it will be restart again.
ALARM
POSSIBLE CAUSE
A23 MODE FAILURE
In parallel operation the slave device tries to operate as the same mode as the
master device, If the modes are different this message will appear.
Change the mode of the slave UPS from USER OPTION MENU. Press
ENTER button for 3 seconds after mode selection, then restart the UPS.
A24 P.FAILURE 10
RS485 failure
A25 PAR. PSP FAIL
Power supply error in parallel controller board.
A26 4 CABLE FAIL
Master-Slave digital cable connection error.
A27 P.FAILURE 13
Parallel controller board failure, online UPS found in parallel system.
A28 PLUG IN DIG.
Digital connection cable plug in failure
A31 DUBL UPS NR.
Parallel UPS numbers are same change one of them
A40 CANT FIND PR
Parallel mode is selected but main controller could not find parallel control
board. Select ONLINE mode from SETTING MENU.
Turn off the ups and turn on again.
A41 P.BAL.FAIL.
In parallel operation current sharing is not okay
A42 BATTERY TEST
Performing battery test
A43 P.SYNC.FAIL.
In parallel system SLAVE UPS is not synchronized to MASTER UPS
1) Wait for 10 seconds the UPS will be restart
A48 STATIC BYPS.
Load is transferred statically to bypass
A50 EMERGE.STOP
Emergency stop button is pressed.
A51 MAINT.SW.ON
Maintenance bypass switch is open. (optional)
A52 MANUA.BYPASS
Yük elle bypass giri
ş
ine transfer edildi
A53 CHECK +6V
Check +6V on them main controller board.
A54 CHECK DC 1
Battery voltage is below the lower limit.
A55 P.DLY.FAIL
Parallel delay fault
A59 REF.FAILURE
2.5 V ADC reference voltage on MPB211 main controller board exceeds
predefined tolerances.
POWER ON
Cihazın ilk açıldı
ğ
ını gösteren mesajdır.
PAR FAILURE 4
Paralelleme Hatası
PAR FAILURE 5
Paralelleme Hatası
PAR FAILURE 6
Paralelleme Hatası
PAR FAILURE 7
Paralelleme Hatası
PAR FAILURE 8
Paralelleme Hatası
Содержание HP-115
Страница 1: ...USER MANUAL HP 100 SERIES UNINTERRUPTIBLE POWER SUPPLIES 1 Phase Input Output HP 115 NS151A ...
Страница 2: ......
Страница 4: ......
Страница 24: ...20 ...
Страница 25: ...21 Connection Diagram Of The RMP COM1 T MON ...
Страница 28: ...AGKK8480 06 2009 ...