Servicing
5
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 28C • 01/2004
59
Subject to modifications resulting from technical improvements!
Boulter Buderus Ltd. • http://www.boulter-boilers.com
z
Reconnect the the servomotor to the three-way valve in
reverse order.
z
Check to see if the BC10 knobs are returned to the desired
settings.
5.3.15 Replacing the servomotor of the three-way valve.
z
Set DHW temperature knob to "0".
z
Disconnect the boiler from the mains power supply.
z
Remove the securing pin (see fig. 95, item 1) and remove
the servomotor.
z
Disconnect the plug (fig. 96, item 1) of the servomotor.
z
Install new servomotor in reverse order.
z
Check to see if the BC10 knobs are returned to the desired
settings.
5.3.16 Replacing the internal mechanism of the three-way
valve
z
Disconnect the system from the mains spower supply.
z
Drain the system.
z
Remove the securing pin (see fig. 95, item 1).
z
Remove the servomotor of the three-way valve.
z
Remove the internal mechanism of the three-way valve
(fig. 97).
fig. 95 Remove securing pin
1
fig. 96 Disconnect plug
fig. 97 Remove the internal mechanism of three-way valve
CAUTION
Some remaining water may come out.