 PD-Monitor Operation & Maintenance Manual 

(V1.0 Feb 2018)

Page 1 

Содержание PD-Monitor

Страница 1: ...BOSSTM PD Monitor Operation Maintenance Manual V1 0 Feb 2018 Page 1...

Страница 2: ...ting principles 23 Markings 24 Installation 25 Electrical connections and wiring diagram 26 Commissioning 27 VEXO iX 2 controller 28 Monitoring Parameters 29 Electrical checks inspection 30 Decommisio...

Страница 3: ...trained competent engineer or qualified person who can verify the integrity of the equipment at that time The qualified person must confirm in writing that the equipment is undamaged as a result of tr...

Страница 4: ...es in the event of damage or loss Definitions Operator Natural person or legal entity who owns and uses the product or whom use of the product has been entrusted to on the basis of a contractual agree...

Страница 5: ...y capable to do so effectively Operating instructions are transferred by BSS Industrial representatives or others assigned by them during delivery negotiations or on demand On site requirements includ...

Страница 6: ...E To prevent or minimize the risk of personal injury PPE must be used when doing potentially dangerous work or other activities if alternative safety measures cannot be taken Any alternative safety me...

Страница 7: ...with the heating or chilled installation at least every 12 months Maintenance Repair These services may only be carried out when the BOSS PD Monitor is shut down The BOSS PD Monitor equipment must be...

Страница 8: ...sducers VEXO iX 2 12 volt Controller with BMS connectivity option Strobe light visual warning alarm 5 amp Relay for blocked filter and sensor fail alarm 5 amp Common alarm relay to be used as a signal...

Страница 9: ...r Operation Maintenance Manual V1 0 Feb 2018 Page 9 SCHEMATIC LAYOUT OF VARIOUS INSTALLATIONS COMPONENT LIST This diagram is for visual purposes only and does not signify exact pipework layouts or val...

Страница 10: ...ated up stream pressure transducer and down stream pressure transducer connection to a sealed or open vented system As system fluid passes through the hydraulic components in the flow sequence below i...

Страница 11: ...s as a main point of electrical isolation The isolator can then be served by a dedicated 240V mains power supply or for example a 230V connection from a dedicated pump which supplies the system in whi...

Страница 12: ...maintenance On a flat vertical level solid wall or frame with clear access of 200mm all around the controller unit Care must be taken when handling this equipment Appropriate safety measures must be...

Страница 13: ...rovision of a power supply protective ground wire connection and line protection must be made according to local regulations and the applicable harmonised standards Please check the electrical ratings...

Страница 14: ...unit schematic item 10 on page 9 Schematic of this document The power is then distributed throughout the BOSSTM PD MonitorTM via an internal wiring loom 2 BOSSTM PD MonitorTM Specification 2No 4 20 mi...

Страница 15: ...ition The VEXO iX 2 Controller will now scroll the following Run VEXO iX 2 Controller 1 SETTING PARAMETERS The Differential Pressure is factory set to 0 4 Bar To reset the parameters for example the p...

Страница 16: ...he controller can be reset by re powering the unit To power up the unit switch the electrical isolation switch on the fascia to on Monitoring will resume 4 FAULT MESSAGES The VEXO iX 2 Controller disp...

Страница 17: ...er The VEXO iX 2 Controller will scroll Sensor 1 Fail in the event of an upstream pressure transducer failure Upstream Pressure Transducer Failure The screen scrolls Sensor 1 Fail The VEXO iX 2 Contro...

Страница 18: ...his equipment must only be used maintained or serviced by trained competent engineers If in any doubt please do not touch this equipment Please contact BSS Industrial or your reseller for additional a...

Страница 19: ...TM OPERATING THE BOSS PD Monitor 89 1 8m FLYING CABLE 1 4 BSP THREAD PRESSURE SENSOR PACKARD PLUG 89 144 MOUNTING HOLES 7mm 8 Leave at least 100mm free space in all directions to ensure suf cient acce...

Страница 20: ...gland Wales No 072 05096 BOSS Court 7 Barton Close Grove Park Leicester LE19 1SJ Range Name TM BOSS PD Monitor Operating Conditions 10 Bar Maximum Working Pressure uid 40 C Minimum Working Temperature...

Страница 21: ...BOSSTM PD Monitor Operation Maintenance Manual V1 0 Feb 2018 Page 21 BOSSTM WATER TREATMENT PRODUCTS...

Страница 22: ...ING WEAR APPROPRIATE PPE WHEN TM OPERATING THE BOSS PD MONITOR INSTALLED BY DATE Y Y M M D D NOTES SERVICED BY DATE Y Y M M D D NOTES SERVICED BY DATE Y Y M M D D NOTES SERVICED BY DATE Y Y M M D D NO...

Страница 23: ...General notes...

Страница 24: ...nitor is distributed exclusively by BSS Industrial BOSS Court 7 Barton Close Grove Park Leicester LE19 1SJ www bssindustrial co uk Tel 0116 245 5940 PD Monitor X PO10 and X POT are trademarks of VEXO...