background image

8

PRESSURE REGULATION

The  pressure  regulator  supplied  with  the  water  heater  is
adjusted to operate on the gas specified on the rating plate,
and:

·

In Canada, is factory preset to deliver gas at the high
altitude pressure setting listed on the rating plate and
as shown below;

·

In  the  U.S.A.,  is  factory  preset  to  deliver  gas  at  the
standard altitude setting listed on the rating plate and
as shown below.

The pressure setting of the gas pressure regulator should
be checked at installation to assure that the setting is correct
for  the  gas  being  used  and  the  altitude  at  which  the
appliance is installed. See rating plate of the unit, or Table
1, below, for proper setting.

In Canada, for a heater being installed at standard altitude
(0- 2,000 ft. above sea level), the manifold pressure should
be reset at installation to value shown on the rating plate, or
Table 1, below, for standard altitude.

* Note: The high altitude ratings listed are Canadien Gas

Association high altitude ratings for the appliances
and  are  only  valid  in  Canada.  In  the  U.S.A.  the
National Fuel Gas Code, ANSI Z223.1/NFPA  54,
recommends  for  high  altitude  installations,  above
2,000 feet, that the input rate be reduced 4% for
each 1,000 feet above sea level.

Your appliance dealer and/or your local gas supplier should
be  consulted  in  regard  to  any  high  altitude  installation.  If
filed adjustment is required it should be performed by a quali-
fied serviceman experienced in such work.

TEMPERATURE REGULATION

The BOSCH WR400-1 is equipped with a modulating gas
valve  which  adjusts  the  flow  of  gas  to  the  main  burner  in
proportion to the water flow rate. Within its heating capac-
ity the WR400-1 attempts to maintain burner in proportion
to  the  water  flow  rate.  Within  its  heating  capacity  the
WR400-1  attempts  to  maintain  the  set  temperature  rise
across the heater. This temperature rise can be set in range
of  25ºC  –to-  50ºC  (45º  F  –  to  –  90ºF),  by  means  of  the
water  flow  selector.  See  figure  10.  With  the  gas  control
button slid all the way to the right under the “ON” position
mark @ when the water flow selector is turned to the right
hand stop the water flow selector is turned to the right hand
stop  the  water  heater  is  set  for  50ºC  (90ºF)  temperature
rise;  when  the  water  flow  selector  is  set  to  the  left  hand
stop it is set for 25ºC (45ºF) temperature rise.

Figure 10

With the water flow selector turned to its right hand stop
position  (50ºC  rise  setting)  and  with  an  inlet  water
temperature  of  10ºC  (50ºF)  the  outlet  water  temperature
will be maintained at approximately 60ºC (140ºF) in the water
flow rate range of approximately 2 litres/min. (0.5 U.S.gals/
min) to 8 litres /min. (2.1 U.S. gals/min.).

The minimum flow rate for operation, the “Threshold Flow
Rate” referred to in the lighting instructions is 2 litres/min
(0.5 U.S. gals./min). If the water flow rate is below this level
the main burner will not fire. If the flow rate excess 8 litres/
min (2.1 U.S. gals/min.) the temperature rise across the heater
will decrease in proportion to the rate above this temperature.

HIGH TEMPERATURE LIMIT SWITCH

The BOSCH WR series instantaneous gas water heaters
are equipped with a high temperature limit switch with a set
point of approximately 90ºC (194ºF). If the water temperature
at the sensing points exceeds the set point the switch will
open, interrupting the safety circuit and stopping gas flow
to the pilot and main burner.

Outage as the result of high limit operation indicates that
the heater is not functioning properly. The heater should be
checked by a qualified serviceman and the reason for the
malfunction  is  corrected.  To  relight  the  pilot,  follow
instructions provided on the unit.

Figure 9

The gas pressure specified below refer to flow pressure taken
at  the  pressure  tap  in  the  gas  inlet  pipe  (just  above  the
pressure regulator), see figure 9 while the heater is operating
at full input.

GAS  CONTROL
SLIDE

WATER  FLOW
SELECTOR

Type

Pressure tap

Altitude

of gas

kPa

inches W.C.

Natural

1.41

5.7

standard

Propane

2.61

10.5

(0 - 2,000 ft)

Natural

1.14

4.6

high*

Propane

2.09

8.4

(2,000 - 4,500 ft)

PRESSURE TAP

PRESSURE
REGULATOR

Содержание WR400-1 K P

Страница 1: ...tore or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departmen...

Страница 2: ...tings and are only valid in Canada In the U S the National Fuel Gas Code ANSI Z223 1 NFPA 54 recommends for high altitude installations above 2 000 feet that the input rate be reduced 4 for each 1 000 feet above sea level See page 8 Model dimensions A B D E F milimetres 460 755 130 diam 740 542 inches 18 1 8 29 3 4 5 1 8 diam 29 1 8 21 11 32 WR400 1 Size mm Qt standard 34 28 kW 1 20 diam 18 0 2 00...

Страница 3: ...ions will not result in damage to the area adjacent to the heater or to lower floors of the structure Note When such locations cannot be avoided it is recommended that a suitable drain pan adequately drained be installed under the water heater The pan must no restrict combustion air flow AIR REQUIREMENTS For safe operation sufficient air combustion ventilation and dilution of the flue gas must be ...

Страница 4: ... for installation on a combustible wall and for installation in an alcove or closet with minimum clearances to combustible construction of 0mm from back 102mm 4 inches from sides 305mm 12 inches from top and bottom and 102mm 4 inches from front A minimum of 305mm 12 inches shall be allowed for maintenance of serviceable parts Clearance from vent is dependent upon the clearance rating of the ventin...

Страница 5: ...of two screws Also in Canada the gas pressure regulator supplied with the water heater is factory preset to deliver gas to the water heater at the proper pressure setting for high altitude operation see PRESSURE REGULATION section of this manual WARNING Failure to increase the vent size of the WR400 1 to six inches and or to assure that manifold pressure is set to proper value listed on rating pla...

Страница 6: ... be sure that all gas pipe is clean on the inside To trap any dirt or foreign material in the gas supply line a drip leg must be readily accessible and not subject to freezing conditions Install in accordance with the recommendations of the serving gas supplier Joint compounds pipe dope shall be applied sparingly and only to the male threads of pipe joints Do not apply compound to the first two th...

Страница 7: ...TING INSTRUCTIONS 1 STOP Read the safety information above on this plate 2 The gas valve should be turned off by sliding the gas valve button to the far left under the OFF mark 3 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information above on this plate If you don t smell gas go to next step 4 The pilot burner is located behind the peephole located i...

Страница 8: ...See figure 10 With the gas control button slid all the way to the right under the ON position mark when the water flow selector is turned to the right hand stop the water flow selector is turned to the right hand stop the water heater is set for 50ºC 90ºF temperature rise when the water flow selector is set to the left hand stop it is set for 25ºC 45ºF temperature rise Figure 10 With the water flo...

Страница 9: ...rner assembly 3 Wash the gas burner assembly in soap and water and then rinse 4 Dry thoroughly 5 Reassemble Check for gas leaks after reassembly and correct as required 6 Refer to LIGHTING INSTRUCTIONS to relight the heater VENTING The vent piping and finned heat exchanger should be checked at least once a year for dust and carbon deposits and cleaned as necessary PRESSURE RELIEF VALVE At least on...

Страница 10: ...10 ...

Страница 11: ...700507055 13 Sparking plug 8708107002 14 Pilot injector 5 NG 8708200005 14 Pilot orifice 49 LPG 8748200173 15 Pilot gas pipe 8700707320 16 Thermocouple 8747202083 17 Washer 1 8710103060 18 Throttle disc 7 0 LPG 8700100174 19 Gas valve LPG 8707011463 19 Gas valve NG 8707011459 20 Gas supply pipe 8700705552 21 Magnetic unit 8707201012 22 Termo connection 8747202209 23 Water valve 8707002499 24 Repai...

Страница 12: ......

Страница 13: ...en peut blesser les personnes ou endommager la propriété Référer a ce manuel Pour assistance ou informations qualifié pour ce travail votre agence de service ou le fournisseur de gaz A noter En cas de problème contacter votre vendeur ou l ouvrier d installation POURVOTRESECURITE CONSIGNE DE SECURITE SI VOUS SENTEZ UN GAZ ODORANT N essayer pas d allumer aucun appareil Ne toucher pas à aucun contact...

Страница 14: ...el Gaz Code ANSI Z223 1 1984 recommandé pour une installation de plus de 2 000 pieds au dessus du niveau de la mer que la consommation soit réduite de 4 pour chaque 1 000 pieds au dessus du niveau de la mer Voir page 8 Dimension mm Qte normale 34 28 kW 1 20 diam 18 0 2 000 Pieds 117 000Btu hr Propane BP 0 79 diam 18 haute 30 85 kW 1 20 diam 18 2 000 4 500 Pieds 105 000Btu hr Propane BP 0 79 diam 1...

Страница 15: ...t pour l emplacement L emplacement doit être proche d une cheminée ou un évent à gaz si possible et que l endroit offre une bonne provision d air et centré avec le système de tuyautage Le chauffe eau ne peut pas être installé dans un endroit exposé au gel Le chauffe eau doit être placé dans un endroit qui ne sera pas endommagé en cas de fuite du chauffe eau ou d un de ces raccords A noter quand te...

Страница 16: ...de dégagement pour le matériel de l éventail utiliser c est à dire le type B 1 éventail est approuvez pour un espace de 1 pouce le B 2 éventail pour 2 pouces etc Au Etats Unis Le WR325 et le WR400 sont de conceptions certifié pour l installation sur un mur de construction combustible pour le WR325 la console de mur fourni avec l appareil doit être utilisé pour le montage sur une construction combu...

Страница 17: ...Canada le régulateur de pression du gaz fournie avec le chauffe eau est réglé à l avance en usine pour livrer la bonne pression de gaz au chauffe eau pour un fonctionnement en haute altitude voir la section REGULATION DE PRESSION dans ce manuel AVERTISSEMENT L omission d agrandir la grandeur du conduit sur le WR400 1 de six pouces et ou s assurer que la pression du collecteur est mise à la valeur ...

Страница 18: ...re Pour se débarrasser de la saleté et de toutes corps étrangers dans le tuyau d alimentation de gaz un mamelon purgeur doit être installé dans la tuyauterie Le mamelon purgeur doit être accessible et sans danger de gel L installation doit être en accordante avec les recommandations du fournisseur de gaz Le composé de l encolleuse le composé du filetage doit être appliqué avec modération et seulem...

Страница 19: ...rité sur la plaque au dessus 2 Le robinet de gaz devrait être fermé en tournant le bouton du robinet de gaz vers la gauche en dessous de la position OFF 3 Attendre cinq minutes pour les gaz est le temps de se dissiper Si vous sentez une odeur de gaz ARRETEZ Aller voir la partie B dans les informations de sécurité sur la plaque au dessus Si vous ne détectez pas aucune senteur de gaz passer al l éta...

Страница 20: ... position ON quand le sélecteur de débit d eau est tourné vers la position d arrêt de droite le chauffe eau est ajusté pour une température de 50ºC 90ºF quand le sélecteur de débit d eau est ajusté vers la position d arrêt de gauche l appareil est réglé pour une température de 25ºC 45ºF Figure 10 Quand le sélecteur de débit d eau est ajusté à la position STOP du côté température de 50ºC et avec un...

Страница 21: ...r fuite de gaz après le remontage et faire les ajustements si nécessaire 5 Référer aux procedures d allumages pour allumer le chauffe eau SYSTEM D AERATION L évent et l échangeur de chaleur avec ailette doivent être vérifié au moins une fois par année pour sédiment de poussière de carbone et nettoyer si nécessaire SOUPAPE DE SURETE A PRESSION Au moins une fois par année le soupape de sûreté de pre...

Страница 22: ...10 ...

Страница 23: ...8107002 14 Injecteur de veilleuse 5 GN 8708200005 14 Injecteur de veilleuse 49 PROP 8748200173 15 Tube veilleuse 8700707320 16 Thermoélément Sécurité veilleuse 8747202083 17 Joint 1 8710103060 18 Diaphragme 7 0 PROP 8700100174 19 Bloc gaz PROP 8707011463 19 Bloc gaz GN 8707011459 20 Tuyau d arrivée gaz 8700705552 21 Tête magnétique 8707201012 22 Thermocâbles 8747202209 23 Valve eau 8707002499 24 C...

Страница 24: ...ents are higher than normal domestic supply temperatures to reduce scald hazard potential Particular care must be taken to select the correct type of thermal mixing valve to satisfy the installed application requirements i e If full anti scald protection is specified then only that type of valve must be selected that is supported by the manufacturer s claim Below is a typical schematic which shoul...

Отзывы: