FAULT FINDING
6 720 644 593 (2010/04)
10 Fault Finding
10.1 Faults indicated on the display
When indicating a fault, the display is back-lit in red. In addition, the type of fault is indicated by
symbols. The individual fault messages can be retrieved using the rotary selector. Fault messages
continue to be displayed until the fault is rectified.
B
In the case of sensor faults, eliminate the cause of the fault to cancel display of the fault.
B
With other faults, eliminate the cause of the fault and then press the rotary selector
to cancel
display of the fault.
Indication/Type of fault
Effect
Possible causes
Remedy
Sensor failure S1 ... S8
Associated components
(pumps/valves) are switched
off.
Temperature sensor not/
incorrectly connected.
Check sensor connections.
Check temperature sensors for
breakages or incorrect
positioning.
Temperature sensor or sensor
lead defective.
Replace temperature sensor.
Check sensor lead.
Sensor short circuit S1 ... S8
Associated components
(pumps/valves) are switched
off.
Temperature sensor or sensor
lead defective.
Replace temperature sensor.
Check sensor lead.
“No fluid flow in solar systems”/“secondary system”
The temperature difference
between collector
temperature sensor and
bottom cylinder temperature
sensor or between heat
exchanger flow temperature
sensor and bottom cylinder
temperature sensor is too
great.
Air in the system.
Bleed the system.
Pump is stalled.
Check the pump.
Valves or shut-offs are closed.
Check valves and isolators.
Pipe clogged.
Check/flush out pipe.
Tab. 13
Possible faults indicated on the display