Fault finding and diagnostics
6 720 808 928 (2017/06)
64
9.6.4
Heat Interface Unit function test menu
▶ Enter the
Service
menu and navigate through the menus and select
the
Diagnosis
menu.
▶ Navigate through the
Diagnosis
menu and select the
Function test
menu.
▶ Navigate through the
Function test
menu and select the
Heat
Interface Unit
menu.
▶ Select the parameter and adjust to test the valve.
9.7
Central heating pump test
To check the pump operation of the central heating pump
▶ Set the central heating rotary switch to the pump (
) position.
– Ensure the central heating rotary switch is returned to its original
position for normal central heating operation.
9.8
Heat meter (if fitted)
The integrator display an error message with the 3 letters “Err” and a
code. If several errors occur at the same time, the different codes are
shown sequentially.
The error is displayed in the first position of the display menu. It will still
be possible to select all the other display menus by pressing the
navigation button, refer to section 6.8.
If the navigation button is no longer pressed for a period of 3 minutes,
the error code automatically appear again in the first position of a display
menu. Display of an error automatically disappears when the error is no
longer present.
• Err. 1
– Flow higher that 1.2 x qs or defective hydraulic sensor.
• Err. 2
– Measured temperature outside the homologated range or
temperature sensor is defective.
Fig. 80 Error display
9.9
Component resistance characteristics
9.9.1
Flow/return temperature NTC sensors
9.9.2
DHW NTC wet sensor
9.9.3
Outdoor weather compensation sensor
Heat Interface Unit
parameter
Description
DHW
Set DHW control valve position (%).
• 0%(closed - 100% (fully open)
CH
Set CH control valve position (%).
• 0%(closed - 100% (fully open)
Table 41
6720808928-56.1W
o
1
Resistance (
Ω
)
Temperature ( °C)
29529
0
18787
10
12257
20
8186
30
5586
40
3889
50
Table 42 Central heating/district sensors
Resistance (
Ω
)
Temperature ( °C)
14772
20
11981
25
9786
30
8047
35
6653
40
5523
45
4608
50
3856
55
3243
60
2744
65
2322
70
1990
75
1704
80
1464
85
1262
90
1093
95
950
100
Table 43 DHW wet sensor
Resistance (
Ω
)
Temperature ( °C)
2392
-20
2088
-16
1811
-12
1562
-8
1342
-4
1149
0
948
4
842
8
781
10
642
15
528
20
436
25
Table 44 Outdoor weather compensation sensor