Product Information
9
Uni Condens 8000 F – 6720867056 (2016/10)
Table 5 Boiler dimensions
2.9
Operation conditions
Observe the maximum rated heat input Qn (Hi) specified on the data
plate when setting the burner output.
Table 6 Operation conditions
Table 7 Operation conditions
It must be possible to check the number of burner starts, e.g. at the user
interface, third-party control unit, building control system or burner
control unit.
Boiler return (RK1)
2)
Ø RK1
DN
100
125
125
H
RK1
mm
1007
1148
1148
A
5
mm
320
380
380
Boiler return (RK2)
2)
Ø RK2
DN
80
100
100
H
RK2
mm
300
263
263
A
6
mm
320
390
390
Pressure relief valve/flow safety pipe
3)
Ø VSLP
DN
65
65
65
A
3
mm
400
400
400
Boiler safety assembly connection
Ø AAB
inch
G1
G1
G1
A
1
mm
1200
1245
1245
Condensate discharge
Ø AKO
DN
40
40
40
H
AKO
mm
180
180
180
A
7
mm
71
70
70
Drain
Ø EL
inch
R1
R1
R1
H
EL
mm
161
164
164
Fitting clearance (width)
B
mm
960
1040
1040
Fitting clearance height
1)
H
EB
mm
1874
2052
2052
Delivery length
4)
–
mm
2405
2455
2455
1) The transport height can be reduced by removing the base frame rails.
2) Acc. to EN 1092-1 PN 6.
3) Acc. to EN 1092-1 PN 16.
4) Following disassembly of burner door
Abbreviation
Unit
Boiler type
800
1000
1200
Operation conditions
Unit
Value
Maximal permissible temperature of
high limit safety cut-out /(STB)
°C
110
Maximum operating pressure
bar
Dependent on boiler
size
Maximum number of burner starts
per
annum
15 000
Operation conditions Uni Condens 8000 F
800...1200 with
modulating
operation
Uni Condens 8000 F
800...1200 with
constant boiler
temperature
Volumetric flow rate
None –
In conjunction with a
CFB/CC control unit
for modulating
operation (CFB 840;
CFB 810; CFB 830 or
CC 8311; CC 8312).
None
In conjunction with a
CFB/CC control unit
for constant boiler
temperature CFB 810
or CC 8312, or when
supplemented by a
third party control
unit.
Min. boiler water
temperature
Operating Interruption
(complete boiler shut-
down)
Heating circuit control
unit with heating mixer
Minimum return
temperature
Miscellaneous
1)2)
1) Maximum 15,000 burner starts per year. In order not to exceed the number of
burner starts, observe the information on setting the control unit and burner in
the technical guide or installation instructions. If this value is still however
exceeded, please contact the customer service of the manufacturer.
2) The number of burner starts per year is influenced by the boiler system's
operating settings (control parameters in the boiler control and the combustion
setting) and by the design of the boiler system with regard to the consumer's
heat requirement. To avoid exceeding the number of burner starts per year as a
result of operating settings that have not been optimised, the manufacturer
offers complete commissioning and regular system inspections for boilers,
burners and boiler controls (CFB/CC controllers with function modules).