Time Base
Choose one of the options in the table below for the time base.
Option
Description
1
200 ms
2
1 Second
3
1 Minute
4
1 Hour
Time Base Multiplier
Enter a value between 01 – 99.
One Shot Mode
When you program the output polarity as a one shot, the time base is multiplied by the time base multiplier (eg.
If the time base = 2 and the multiplier = 05, the output will operate for 5 seconds)
Pulsing Mode
When you program the output polarity as pulsing, the time base becomes the ‘ON’ time and the multiplier
becomes the ‘OFF’ time. The ‘OFF’ time is the
time base x the multiplier
(eg. If you want the output to pulse
one (1) second ‘ON’ and five (5) seconds ‘OFF’, you would program time base as one (1) and the multiplier as
five (5)).
Solution Ultima 862
Quick Reference Guide
15
SOL ULTIMA 862 QUICK REF GUIDE
Polarity (Modes)
Option
Description
Option
Description
0
Disabled
1
Normally Open, Going Low
8
Normally Low, Going Open
2
Normally Open, Pulsing Low
9
Normally Low, Pulsing Open
3
Normally Open, One Shot Low
10
Normally Low, One Shot Open
4
Normally Open, One Shot Low (Reset)
11
Normally Low, One Shot Open (Reset)
5
Normally Open, One Shot Low (Re-trigger)
12
Normally Low, One Shot Open (Re-trigger)
6
Normally Open, One Shot Low (Alarm)
13
Normally Low, One Shot Open (Alarm)
7
Normally Open, Latching Low
14
Normally Low, Latching Open