Therm 8000S
Maintenance | 39
▶ Assemble the condensate unit and all other parts in reverse
order of disassembly.
9.3.1 Cleaning the condensate trap
To clean the condensate trap proceed as follow;
▶ Open the condensate trap cover.
Fig. 60
▶ Check and clean the condensate trap with clean water.
▶ Screw the condensate trap cover.
9.3.2 Filling the condensate trap after the maintenance
works
After the condensate trap maintenance, it’s necessary to fill it
with water.
Proceed as follow;
▶ Remove the clip and disconnect the drain tube, see Fig. 61.
Fig. 61
▶ Fill the condensate trap by pouring approx.14 oz. (400ml)
of water into the top of the drain tube. To avoid damage to
the appliance use a funnel in this operation, see Fig. 62.
Fig. 62
Filling the condensate trap after installation.
▶ Loosen the three screws of the control unit (Fig. 56).
▶ Put the control unit in service position by engaging its tabs
with the holes in the bottom horizontal sheet metal (see
Fig. 63).
It is mandatory to propely replace the
gaskets and o-rings.
WARNING:
Material damage!
▶ Place a suitable container underneath
the appliance before unscrew the
condensate trap cover.