6 720 220 046
Revised 03-11 Subject to change without prior notice
27
TA Series
Troubleshooting
Insufficient
cooling or
heating
Unit undersized
Recalculate heating and or cooling loads. If excessive, possibly adding
insulation and shading will rectify the problem
Loss of conditioned
air by leakage
Check for leaks in duct work or introduction of ambient air through
doors or windows
Airflow
Lack of adequate air flow or improper distribution of air. Replace dirty
filter
Refrigerant charge
Low on refrigerant charge causing inefficient operation
Compressor
Check for defective compressor. If discharge is too low and suction
pressure is too high, compressor is not pumping properly. Replace
compressor.
Reversing Valve
Defective reversing valve creating bypass of refrigerant from discharge
of suction side of compressor. Replace reversing valve
Operating
pressures
Compare unit operation pressures to the pressure/temperature chart
for the unit.
TXV
Check TXV for possible restriction or defect. Replace if necessary.
Moisture,
noncondensables
The refrigerant system may be contaminated with moisture or
noncondensables. Reclaim refrigerant, replace filter dryer, evacuate the
refrigerant system, and recharge with factory recommended charge.