Fan Motor Options
SV Heat PumpSeries
SV Heat Pump Series
8 733 914 818 (2014?08)
Subject to change without prior notice
Constant Airflow Motors (ECM)
For installations where constant air delivery is
critical or where external static pressure drop can
vary greatly (such as with high MERV value filters)
the SV series is offered with a constant air flow
ECM motor option. This option provides ECM
motor efficiency combined with a constant air
delivery across a wide range of external static
pressures. These motors dynamically adjust their
power output to precisely match the desired air
flow on a pre-programmed fan curve. Additionally
these motors feature:
1. A low CFM ventilation feature that circulates
air at 70% of full load when fan only is called.
2. A passive dehumidification mode that reduces
air flow during a cooling call when
dehumidification is also required – this
reduces the sensible heat ratio of the cooling
coil and extends cooling run time to more
effectively dehumidify. (refer to the ECM
Interface Board section of this manual)
3. 3 speed settings per model. Units are factory
set to “NORM” but can be field adjusted to “+”
to increase CFM by 15% or to “-“to reduce CFM
by 15%. (refer to the ECM Interface Board
section of this manual)
4. A “TEST” mode that operates the motor at a
70% torque setting. This setting can be used to
diagnose programming problems in the motor
itself. (refer to the ECM Interface Board
section of this manual)
5. A CFM indicator light that provides a blink for
each 100 CFM of air delivered (note that this
blink code is approximate and should not
replace test and balancing).
Refer to the constant air flow motor performance
tables for heat pump blower performance with the
constant air flow motor option.
SV-048
1
1390
1370
1350
1320
-
-
-
-
-
-
-
-
2
1600
1580
1550
1530
1510
-
-
-
-
-
-
-
3
1600
1730
1700
1670
1650
1630
1600
1580
1540
-
-
-
-
4
1830
1810
1780
1760
1740
1710
1670
1600
1520
-
-
-
5
1930
1910
1880
1860
1830
1780
1720
1640
1540
1420
-
-
SV-060
1
1900
1880
1860
1820
-
-
-
-
-
-
-
-
2
2000
1970
1950
1920
1890
1860
-
-
-
-
-
-
3
2000
2110
2090
2060
2030
2010
1970
1940
1910
1880
-
-
-
4
2220
2200
2170
2140
2110
2080
2050
2060
2050
2000
1920
-
5
2340
2320
2290
2260
2230
2210
2180
2150
2110
2070
2000
1930
SV-070
1
2050
2010
1970
1930
-
-
-
-
-
-
-
-
2
2150
2120
2080
2030
1990
1960
-
-
-
-
-
-
3
2100
2270
2230
2200
2160
2120
2080
2040
2010
1980
-
-
-
4
2390
2350
2320
2280
2250
2200
2160
2130
2100
2070
2030
-
5
2520
2480
2450
2420
2380
2330
2290
2260
2220
2170
2100
2020
Table 6: Constant Torque Blower Motor Data
Model
Fan
Spee
d
Rated
Airflow
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
1.20
Содержание SV007
Страница 53: ...Notes 53 Revised 08 14 8 733 914 818 2014 08 SV Heat Pump Series NOTES ...
Страница 54: ...54 Notes SV Heat PumpSeries SV Heat Pump Series 8 733 914 818 2014 08 Subject to change without prior notice ...
Страница 55: ...Notes 55 Revised 08 14 8 733 914 818 2014 08 SV Heat Pump Series ...