device and the cable shield must be contacted on both ends. This prevents
interference produced by the device from being transmitted externally where it
could penetrate other systems. It also prevents the penetration of interference
signals back into connection wires that have already been filtered.
Line cable
(unshielded)
well-connected
line filter
Line filter
Clips for
screen
contacting
L, N and PE -
as short as possible!
Shield is required
in this section!
Device
Shield housing
of the device
Fig.4-35:
Correct connection of a compact line filter outside the device
When connecting line filters, attention should first be paid to the frequency
ranges to be filtered. If frequencies in the MHz range are also to be filtered,
such a line filter should have a metal housing. Line filters with plastic housings
are normally not suitable for this purpose.
Current-compensated chokes
Device manufacturers sometimes specify the use of current-compensating
chokes or the installation of ferrite loops in the power supply line. Many exam‐
ples of this can be found in motor lines that are fed by frequency inverters. Such
chokes (see the following figures) suppress common-mode interference cur‐
rents (I
S
) and allow the operating currents (I
B
) to pass unhindered. It should be
noted that the operating currents in the core produce self-cancelling magnetic
fields so that the operating current does not saturate the ferrite cores. Such
throttles must also be placed at the inlet to the shielded housing of the device.
1
2
1
2
I
I
S
I
S
I
S
Σ
I =0
B
I
B
B
I
①
Supply lines
②
Ferrite loop
I
S
Interference current
I
B
Operating current
Fig.4-36:
Current flow of a current-compensating choke
Ferrite
Ferrites operating via data lines work in a similar way to current-compensating
chokes. The wanted signals (see figure) can pass unhindered and the interfer‐
ence signals are attenuated. A fundamental difference from current-compen‐
sating chokes is that in the case of ferrites the application range takes place at
Bosch Rexroth AG
DOK-SUPPL*-VCH*08.1***-PR02-EN-P
Rexroth IndraControl VCH 08.1 Hand-held Terminal
48/117
Technical Data
Содержание Rexroth VCH 08.1
Страница 1: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 12: ...Bosch Rexroth AG DOK SUPPL VCH 08 1 PR02 EN P Rexroth IndraControl VCH 08 1 Hand held Terminal 10 117 ...
Страница 28: ...Bosch Rexroth AG DOK SUPPL VCH 08 1 PR02 EN P Rexroth IndraControl VCH 08 1 Hand held Terminal 26 117 ...
Страница 60: ...Bosch Rexroth AG DOK SUPPL VCH 08 1 PR02 EN P Rexroth IndraControl VCH 08 1 Hand held Terminal 58 117 ...
Страница 92: ...Bosch Rexroth AG DOK SUPPL VCH 08 1 PR02 EN P Rexroth IndraControl VCH 08 1 Hand held Terminal 90 117 ...
Страница 114: ...Bosch Rexroth AG DOK SUPPL VCH 08 1 PR02 EN P Rexroth IndraControl VCH 08 1 Hand held Terminal 112 117 ...
Страница 118: ...Bosch Rexroth AG DOK SUPPL VCH 08 1 PR02 EN P Rexroth IndraControl VCH 08 1 Hand held Terminal 116 117 ...
Страница 119: ...Notes DOK SUPPL VCH 08 1 PR02 EN P Rexroth IndraControl VCH 08 1 Hand held Terminal Bosch Rexroth AG 117 117 ...