EMC Manual ServodynT, D
Switch cabinet structure
313
1070 066 074-101
PE bus
The cross section of the PE bus and mounting plate earthing must be one
level wider than that of the mains supply cable to the supply module.
24 V power
The PE connection and the secondary circuit earthing must be designed
supply module
in accordance with the secondary current, but must have a cross section
of at least 1,5 mm
2
.
0 V bus
The 0 V bus is provided with insulation and earthed at one place only.
This prevents 24 V operating currents in the earthing and screen connec
tions.