10.5.3 24V DC cabling
PE bar
B
Overvoltage category I
XS1
FE
VEP
24 V
6 mm² (blue)
A
A
0 V
2
1
2
2
1
10 mm (green/yellow)
2
①
Easy to remove and visible
②
Cable length b24 V power sup-
ply unit and the VEP is 6 m max. at a
minimum cross-section of 0.75 mm
2
. Ca-
ble length b24 V power supply
unit and the VEP is 10 m max. at a mini-
mum cross-section of 1.5 mm
2
. An addi-
tional power supply unit is required if
the length exceeds 10 m.
A
Insulated terminal block
B
Non-insulated terminal block
FE Functional earth
Fig. 10-11: Wiring the embedded terminal
10.5.4 Keypad connection scheme
S1
emergency stop
LED2
LED4
X3
X2
S2
S3
S4
Fig. 10-12: Keypad connection diagram
The maximum load for each contact must not exceed 500 mA.
32/49
Mounting, demounting and electric installation
IndraControl VEP 30.6, VEP 40.6,
VEP 50.6 Embedded Terminals
Bosch Rexroth AG R911403058_Edition 01