R911299726
/
02
|
Rexroth IndraControl VCP 05
Electric Drives and Controls |
Bosch Rexroth AG
7
-21
Interfaces
The maximum cable length depends on the baud rate (DIN EN 19245
Part 3).
7.2.6
Termination
Terminate the PROFIBUS at both ends by terminating resistors. If you
are using special PROFIBUS connectors, these resistors are usually
integrated into the connector and can be connected.
7.2.7
Diagnostics
A diagnostic LED is located on the rear of the small operator terminal.
The LED shows a state of the bus system.
Fig. 7-32:
Arrangement of the PROFIBUS DP diagnostic LED
The diagnostic LED on the small operator terminal has the following
function:
Baud Rate
Cable Length
187.5 kbits/s
1000 m
500 kbits/s
400 m
1500 kbits/s
200 m
3000 to 12000 kbits/s 100 m
Fig. 7-31:
Baud rate PROFIBUS DP
Color
State
Function
Green
On
Communication active
Fig. 7-33:
Function of the PROFIBUS-DP diagnostic LED
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com