IndraControl L10, the supply terminals and the top-hat rail has been properly
established.
Potential equalization according to DIN VDE 0100 Part 540 must be provided
between the system parts and the voltage supply.
All components of the system must be connected to the PE protective conductor
system at the connectors that are marked accordingly.
8.2.6
Shield System
General Information
The shielding is intended to reduce any effects of interferences on the system.
Both the PROFIBUS line and the connection lines to modules for analog signals
must be shielded.
Observe the following when shielding:
●
Fit the shield over an area as large as possible under the clip in the shield
connector.
●
Ensure proper contact between the connector and the module.
●
Avoid damaging or squeezing of cores. Avoid stripping the lines too much.
●
Connect the cores properly.
8.2.7
Connecting Lines to Tension Spring Connection Points
General Information
Connect the lines for peripheral equipment and voltage supply to the tension
spring connection points both at the IndraControl L10 and the Rexroth Inline
modules.
Use unshielded lines for the digital inputs and outputs and the voltage supply.
Use shielded lines to connect the analog inputs and outputs.
Lines with a connection cross-section ranging from 0.2 mm
2
to 1.5 mm
2
(AWG
24 – 16) can be connected. These lines permit the supply of signals of up to
250 V AC/DC and 5 A.